Plan Review Notes
Plan Review Notes For Permit 06040135
Permit Number 06040135
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-09 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 **THIS PLAN HAS BEEN REVIEWED UNDER
 PERMIT NUMBER 05090945 WHICH HAS BEEN
 VOIDED. ORIGINALLY REVIEWED UNDER
 FBC-2001. SINCE A NEW PERMIT HAS BEEN
 APPLIED FOR, THIS REVIEW WILL BE UNDER
 FBC-2004. THE FOLLOWING COMMENTS ARE
 FROM THE PREVIOUS REVIEW. THE COMMENT
 NUMBER WILL REMAIN THE SAME:
  
 (FIRST REVIEW THIS PERMIT NUMBER)
  
 1. PLANS SHALL BE ROUTED TO DBPR HOTEL &
 RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW.
 SUBMIT A MINIMUM OF 3 SETS OF PLANS
 STAMPED BY DBPR WITH THE TWO PAGE "WORK
 SHEETS" TO EACH SET. SECTION 101.4.7.
 ***NO RESPONSE NOTED. NO STAMPED SHEETS
 FROM DBPR FOUND, WORKSHEETS NOT
 ATTACHED. SECTION 102.2.1.
  
 4. SHT 3.1 TOILET ROOMS SHOW CLEAR FLOOR
 SPACE FOR EACH ACCESSIBLE FIXTURE. SHOW
 TURNING AREA IN EACH TOILET ROOM.
 SECTION 11-4.22.3.
 ***RESPONSE NOTED, BUT CLEAR FLOOR SPACE
 PER 11-4.22.3 NOT TUB CONTROLS WAS
 REQUESTED. THE CLEAR FLOOR SPACE FOR THE
 W/C'S ARE NOT SHOWN. SECTION 11-4.22.3.
  
 5. SHTS A-2.01 & A-2.02 SUBMIT
 CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1003.1 & 403.1 FOR ALL COMMON
 AREAS. SHOW THE SQUARE FOOTAGE OF EACH
 COMMON AREA ON THE FLOOR PLAN.
 ***RESPONSE NOTED, (ON COMMENT #6), BUT
 SHEET A-2.02 NOT SUBMITTED, AND SHEET
 A-2.2 IS A BUILDING EXTERIOR ELEVATION.
 INFORMATION REQUESTED NOT FOUND. PLEASE
 CLARIFY. SECTION 106.1.1. (SEE TABLES
 1004.1.2 & 403.1).
  
 6. SHT A-3.1 SINK IN EMPLOYEE BREAK ROOM
 #156 SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 ***RESPONSE NOTED, BUT SECTION 11-4.24.4
 SINK DEPTH STILL NOT SHOWN. PLEASE
 INDICATE ON DETAIL FOR SINK.
  
 11. SUBMIT A BUILDING DRAIN SANITARY
 ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM, AND
 SHOW RISER LOCATIONS WITH RISER
 DESIGNATION NUMBERS. SECTION 104.2.1 AND
 104.3.1.1.
 ***RESPONSE NOTED, BUT RISER SUBMITTED
 ON SHT P-3.03 DOES NOT REFLECT THE FLOOR
 PLAN. BUILDING SANT. DRAIN IS SHOWN
 EXITING THE BUILDING AT RISERS 14 & 15
 ON THE FLOOR PLAN, BUT EXITING AT RISERS
 1 & 2 ON THE RISER ISOMETRIC. RISER #5
 DOES NOT SHOW THE OFFSET ON THE
 ISOMETRIC AS SHOWN ON THE FLOOR PLAN.
 RISER ISO. DOES NOT SHOW UNIT K-125 AS
 SHOWN ON FLOOR PLAN. FS-1 AND RISER S-15
 DO NOT REFLECT THE FLOOR PLAN AT THE
 CONNECTION TO THE BUILD. DRAIN. FS-1
 SHOWN BETWEEN RISER S-1 & S-3 NOT SHOWN
 ON THE FLOOR PLAN. INDICATE WHERE THE
 BUILDING SANT. DRAIN CHANGES FROM 4" TO
 6" AND SHOW DFU'S AT THAT POINT. SECTION
 106.3.5.1.3 AND TABLE 710.1(1).
  
 12. SHT P-3.01 ALL SANT. RISER DIAGRAMS,
 (EXCEPT S-16), DO NOT REFLECT THE FLOOR
 PLAN, NOR DO THEY MEET CODE
 REQUIREMENTS.
 ***RESPONSE NOTED, BUT NOT RISER 15 DOES
 NOT REFLECT THE FLOOR PLAN. SHOWS FLOOR
 DRAIN NOT FLOOR SINK, AND W.B. CONNECTS
 UPSTREAM OF FLOOR DRAIN ON FLOOR PLAN.
 RISER 14 SHOWS A HORIZONTAL DRY VENT AT
 THE BASE OF THE STACK. THIS IS NOT
 APPROVED PER SECTIONS 905.3 & 905.4.
 (VENT SHOULD CONNECT TO THE STACK WITH
 AN UPRIGHT WYE FITTING ON THE VERTICAL
 PORTION OF THE STACK).
  
 13. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE LAUNDRY AND ALL
 COMMON AREAS SHOWNING ALL PIPE SIZES,
 VAVLES, AND WATER HAMMER ARRESTORS,
 (WHERE REQUIRED BY SECTION 604.9).
 ***RESPONSE NOTED, BUT NO WATER LINES
 SHOWN TO THE GUEST LAUNDRY EQUIPMENT
 LAYOUT PLAN, SHT A3.2.
  
 14. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE WATER
 DISTRIBUTION SYSTEM SHOWING THE LOCATION
 OF THE WATER ENTERING THE BUILDING, ALL
 PIPING NOT SHOWN ON THE RISERS, ALL PIPE
 SIZES, WATER HAMMER ARRESTORS, LOCATION
 OF WATER RISERS CONNECTING TO THE
 DISTRIBUTION LINE WITH RISER DESIGNATION
 NUMBERS ETC. SECTIONS 104.2.1 AND
 104.3.1.1.
 ***RESPONSE NOTED, BUT WATER HAMMER
 ARRESTORS LOCATED AT THE CLOTHES WASHERS
 TO BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. CAN WASH IS INDICATED AS H.B. ON
 THE FLOOR PLAN. PLEASE CORRELATE. NO
 WATER PIPING SHOWN TO 1ST FLOOR UNITS
 122, 124, 125. RISER DOES NOT REFLECT
 THE FLOOR PLAN AT EW-1. SEPARATE LINE
 SHOWN ON THE FLOOR PLAN TO THIS FIXTURE.
 PLEASE CORRELATE FLOOR PLAN AND RISER
 INFORMATION. SECTION 106.1.1, PDI-WH 201
 & MANUF. INSTALLATION INSTRUCTIONS.
  
 16. THE FOLLOWING INFORMATION IS
 REQUIRED FOR A GAS PERMIT:
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING
 USED).
 ***NO RESPONSE NOTED FOR PIPE MATERIAL.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 ***RESPONSE NOTEE, BUT BTU'S FOR THE GAS
 GENERATOR AND FIREPLACE AND TOTAL BTU'S
 REFLECTING THE ADDITIONAL BUT'S OF THE
 GENERATOR AND FIREPLACEBTU'S NOT SHOWN.
 FBC-2004 FUEL GAS CODE SECTIONS 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 ***RESPONSE NOTED, BUT THE DISTANCE IS
 NOT CORRECT. WHEN ADDING THE DISTANCE TO
 THE GENERATOR AS SHOWN, THE TOTAL
 DEVELOPED LENGTH IS 372.5 FT. PLEASE
 CLARIFY. FBC-2004 FUEL GAS APPENDIX A -
 USE OF CAPACITY TABLES A.3.1(4).
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED, AND MANUF.
 SPECIFICATION SHEETS NOT FOUND. FBC-2004
 FUEL GAS CODE SECTION 402.2, NFPA 54, &
 NFPA 58.
  
 19. ALL INFORMATION REQUIRED BY FAC
 61G1-16.004 & FS 481.219 TO BE IN THE
 TITLE BLOCK OF THE ARCHITECT.
 ***RESPONSE NOTED, BUT INFORMATION STILL
 NOT SHOWN ON ALL SHEETS, AND THE FIRM
 LICENSE HAS BEEN NULL & VOID SINCE
 02-28-2003.
  
 **************NEW COMMENTS**************
  
 1B. SHT A-1.7 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS.
 INDICATE THE SQUARE FOOTAGE BEING
 DRAINED BY EACH DOWNSPOUT. SHOW 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS
 FOR EACH AREA. - SUBMIT A DETAIL FOR THE
 OPENING TO EACH DOWNSPOUT SHOWING HEIGHT
 & WIDTH ETC. - SUBMIT A DETAIL FOR THE
 EMERGENCY OVERFLOW SCUPPERS. INDICATE
 THE SIZE, (LENGHT & WIDTH), AS WELL AS
 THE MEASUREMENT FROM THE ROOF TO THE
 FLOW LINE OF SCUPPER. (2" TO 4") -
 SCUPPERS SHALL BE SIZED PER SECTIONS
 1101.7 & 1107.3 ALONG WITH TABLE 1106.7.
 THE SIZING OF THE SCUPPERS CAN NOT BE
 DETERMINED WITHOUT REFERENC TO THE
 DEFLECTION OF THE ROOF. PLEASE INDICATE
 ON PLANS THE CLACULATIONS FOR THE
 SCUPPERS.
  
 2B. SHT A-3.2 INDICATES A GUEST WASH
 MACHINE & DRYER WITH NO APPARANT ACCESS,
 SANITARY PIPING OR WATER SUPPLY. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 3B. SHT A-3.3 CANOPY. SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SF BEING DRAINED BY
 EACH PRIMARY DRAIN. INDICATE DRAIN SIZE,
 RWL SIZE, FOR PRIMARY AND OVERFLOW
 DRAINS. SUBMIT RISER DIAGRAMS FOR BOTH
 SYSTEMS INDICATING PIPE SIZE, OFFSETS
 AND TERMINATION POINTS. SECTIONS 1106 &
 1107 AND TABLE 1106.3.
  
 4B. SHTS A10.62 THRU A10.65 REFERENCE A
 "HEAT N GLO" GAS FIREPLACE. THIS IS
 SHOWN ON THE FLOOR PLAN, BUT NOT THE GAS
 RISER DIAGRAM. PLEASE CLARIFY. SECTION
 106.1.1.
  
 5B. SHT P-1.07 INDICATES A DRAIN FOR THE
 FIRE SPRINKLER SYSTEM IN THE STAIRWELL
 ADJACENT TO RISER W-2. PLEASE INDICATE
 WHAT THE DRAIN WILL DRAIN INTO. SECTION
 106.1.1.
  
 6B. SHT P-2.01 LAUNDRY WATER HEATER,
 THERMAL EXPANSION CONTROL REQUIRED PER
 SECTION 607.3.2.
  
 7B. SHT P-3.04 WATER MAIN PIPE SIZES DO
 NOT REFLECT PIPE SIZES SHOWN ON SHTS
 P-1.07 & P-5.01. PIPE SIZES TO FROM 3"
 TO 2" THEN BACK TO 2-1/2". PLEASE
 CORRELATE WATER DISTRIBUTION RISERS,
 FLOOR PLAN. SECTION 106.1.1.
  
 8B. ALL ARCHITECTURAL SHEETS, ALL PME
 SHEETS: IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY RESISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES,
 PART 1, OR ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE SEAL
 IS AFFIXED TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS
 REQUIRED BY FLORIDA STATUTES. SECTION
 106.1.
  
 9B. A SEPARATE IRRIGATION PERMIT AND
 PLANS ARE REQUIRED. THIS MAY BE
 SUBMITTED AT A LATER DATE. SECTIONS
 105.1 AND 106.3.5.1.3.
  
 10B. SUBMIT A ROOF PLAN SHOWING THE
 LOCATION OF ALL VENTS FOR THE SANITARY
 SYSTEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  