| 2006-06-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | **THIS PLAN HAS BEEN REVIEWED UNDER |
| | PERMIT NUMBER 05090945 WHICH HAS BEEN |
| | VOIDED. ORIGINALLY REVIEWED UNDER |
| | FBC-2001. SINCE A NEW PERMIT HAS BEEN |
| | APPLIED FOR, THIS REVIEW WILL BE UNDER |
| | FBC-2004. THE FOLLOWING COMMENTS ARE |
| | FROM THE PREVIOUS REVIEW. THE COMMENT |
| | NUMBER WILL REMAIN THE SAME: |
| | |
| | (FIRST REVIEW THIS PERMIT NUMBER) |
| | |
| | 1. PLANS SHALL BE ROUTED TO DBPR HOTEL & |
| | RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY WPB FOR REVIEW. |
| | SUBMIT A MINIMUM OF 3 SETS OF PLANS |
| | STAMPED BY DBPR WITH THE TWO PAGE "WORK |
| | SHEETS" TO EACH SET. SECTION 101.4.7. |
| | ***NO RESPONSE NOTED. NO STAMPED SHEETS |
| | FROM DBPR FOUND, WORKSHEETS NOT |
| | ATTACHED. SECTION 102.2.1. |
| | |
| | 4. SHT 3.1 TOILET ROOMS SHOW CLEAR FLOOR |
| | SPACE FOR EACH ACCESSIBLE FIXTURE. SHOW |
| | TURNING AREA IN EACH TOILET ROOM. |
| | SECTION 11-4.22.3. |
| | ***RESPONSE NOTED, BUT CLEAR FLOOR SPACE |
| | PER 11-4.22.3 NOT TUB CONTROLS WAS |
| | REQUESTED. THE CLEAR FLOOR SPACE FOR THE |
| | W/C'S ARE NOT SHOWN. SECTION 11-4.22.3. |
| | |
| | 5. SHTS A-2.01 & A-2.02 SUBMIT |
| | CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1003.1 & 403.1 FOR ALL COMMON |
| | AREAS. SHOW THE SQUARE FOOTAGE OF EACH |
| | COMMON AREA ON THE FLOOR PLAN. |
| | ***RESPONSE NOTED, (ON COMMENT #6), BUT |
| | SHEET A-2.02 NOT SUBMITTED, AND SHEET |
| | A-2.2 IS A BUILDING EXTERIOR ELEVATION. |
| | INFORMATION REQUESTED NOT FOUND. PLEASE |
| | CLARIFY. SECTION 106.1.1. (SEE TABLES |
| | 1004.1.2 & 403.1). |
| | |
| | 6. SHT A-3.1 SINK IN EMPLOYEE BREAK ROOM |
| | #156 SHALL COMPLY WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. |
| | ***RESPONSE NOTED, BUT SECTION 11-4.24.4 |
| | SINK DEPTH STILL NOT SHOWN. PLEASE |
| | INDICATE ON DETAIL FOR SINK. |
| | |
| | 11. SUBMIT A BUILDING DRAIN SANITARY |
| | ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM, AND |
| | SHOW RISER LOCATIONS WITH RISER |
| | DESIGNATION NUMBERS. SECTION 104.2.1 AND |
| | 104.3.1.1. |
| | ***RESPONSE NOTED, BUT RISER SUBMITTED |
| | ON SHT P-3.03 DOES NOT REFLECT THE FLOOR |
| | PLAN. BUILDING SANT. DRAIN IS SHOWN |
| | EXITING THE BUILDING AT RISERS 14 & 15 |
| | ON THE FLOOR PLAN, BUT EXITING AT RISERS |
| | 1 & 2 ON THE RISER ISOMETRIC. RISER #5 |
| | DOES NOT SHOW THE OFFSET ON THE |
| | ISOMETRIC AS SHOWN ON THE FLOOR PLAN. |
| | RISER ISO. DOES NOT SHOW UNIT K-125 AS |
| | SHOWN ON FLOOR PLAN. FS-1 AND RISER S-15 |
| | DO NOT REFLECT THE FLOOR PLAN AT THE |
| | CONNECTION TO THE BUILD. DRAIN. FS-1 |
| | SHOWN BETWEEN RISER S-1 & S-3 NOT SHOWN |
| | ON THE FLOOR PLAN. INDICATE WHERE THE |
| | BUILDING SANT. DRAIN CHANGES FROM 4" TO |
| | 6" AND SHOW DFU'S AT THAT POINT. SECTION |
| | 106.3.5.1.3 AND TABLE 710.1(1). |
| | |
| | 12. SHT P-3.01 ALL SANT. RISER DIAGRAMS, |
| | (EXCEPT S-16), DO NOT REFLECT THE FLOOR |
| | PLAN, NOR DO THEY MEET CODE |
| | REQUIREMENTS. |
| | ***RESPONSE NOTED, BUT NOT RISER 15 DOES |
| | NOT REFLECT THE FLOOR PLAN. SHOWS FLOOR |
| | DRAIN NOT FLOOR SINK, AND W.B. CONNECTS |
| | UPSTREAM OF FLOOR DRAIN ON FLOOR PLAN. |
| | RISER 14 SHOWS A HORIZONTAL DRY VENT AT |
| | THE BASE OF THE STACK. THIS IS NOT |
| | APPROVED PER SECTIONS 905.3 & 905.4. |
| | (VENT SHOULD CONNECT TO THE STACK WITH |
| | AN UPRIGHT WYE FITTING ON THE VERTICAL |
| | PORTION OF THE STACK). |
| | |
| | 13. SUBMIT A WATER RISER DIAGRAM IN |
| | ISOMETRIC FORM FOR THE LAUNDRY AND ALL |
| | COMMON AREAS SHOWNING ALL PIPE SIZES, |
| | VAVLES, AND WATER HAMMER ARRESTORS, |
| | (WHERE REQUIRED BY SECTION 604.9). |
| | ***RESPONSE NOTED, BUT NO WATER LINES |
| | SHOWN TO THE GUEST LAUNDRY EQUIPMENT |
| | LAYOUT PLAN, SHT A3.2. |
| | |
| | 14. SUBMIT A WATER RISER DIAGRAM IN |
| | ISOMETRIC FORM FOR THE WATER |
| | DISTRIBUTION SYSTEM SHOWING THE LOCATION |
| | OF THE WATER ENTERING THE BUILDING, ALL |
| | PIPING NOT SHOWN ON THE RISERS, ALL PIPE |
| | SIZES, WATER HAMMER ARRESTORS, LOCATION |
| | OF WATER RISERS CONNECTING TO THE |
| | DISTRIBUTION LINE WITH RISER DESIGNATION |
| | NUMBERS ETC. SECTIONS 104.2.1 AND |
| | 104.3.1.1. |
| | ***RESPONSE NOTED, BUT WATER HAMMER |
| | ARRESTORS LOCATED AT THE CLOTHES WASHERS |
| | TO BE LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. CAN WASH IS INDICATED AS H.B. ON |
| | THE FLOOR PLAN. PLEASE CORRELATE. NO |
| | WATER PIPING SHOWN TO 1ST FLOOR UNITS |
| | 122, 124, 125. RISER DOES NOT REFLECT |
| | THE FLOOR PLAN AT EW-1. SEPARATE LINE |
| | SHOWN ON THE FLOOR PLAN TO THIS FIXTURE. |
| | PLEASE CORRELATE FLOOR PLAN AND RISER |
| | INFORMATION. SECTION 106.1.1, PDI-WH 201 |
| | & MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | 16. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR A GAS PERMIT: |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING |
| | USED). |
| | ***NO RESPONSE NOTED FOR PIPE MATERIAL. |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | ***RESPONSE NOTEE, BUT BTU'S FOR THE GAS |
| | GENERATOR AND FIREPLACE AND TOTAL BTU'S |
| | REFLECTING THE ADDITIONAL BUT'S OF THE |
| | GENERATOR AND FIREPLACEBTU'S NOT SHOWN. |
| | FBC-2004 FUEL GAS CODE SECTIONS 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | ***RESPONSE NOTED, BUT THE DISTANCE IS |
| | NOT CORRECT. WHEN ADDING THE DISTANCE TO |
| | THE GENERATOR AS SHOWN, THE TOTAL |
| | DEVELOPED LENGTH IS 372.5 FT. PLEASE |
| | CLARIFY. FBC-2004 FUEL GAS APPENDIX A - |
| | USE OF CAPACITY TABLES A.3.1(4). |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. |
| | ***NO RESPONSE NOTED, AND MANUF. |
| | SPECIFICATION SHEETS NOT FOUND. FBC-2004 |
| | FUEL GAS CODE SECTION 402.2, NFPA 54, & |
| | NFPA 58. |
| | |
| | 19. ALL INFORMATION REQUIRED BY FAC |
| | 61G1-16.004 & FS 481.219 TO BE IN THE |
| | TITLE BLOCK OF THE ARCHITECT. |
| | ***RESPONSE NOTED, BUT INFORMATION STILL |
| | NOT SHOWN ON ALL SHEETS, AND THE FIRM |
| | LICENSE HAS BEEN NULL & VOID SINCE |
| | 02-28-2003. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SHT A-1.7 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. |
| | INDICATE THE SQUARE FOOTAGE BEING |
| | DRAINED BY EACH DOWNSPOUT. SHOW 1/2 AREA |
| | OF ALL VERTICAL WALLS INCLUDING PARAPETS |
| | FOR EACH AREA. - SUBMIT A DETAIL FOR THE |
| | OPENING TO EACH DOWNSPOUT SHOWING HEIGHT |
| | & WIDTH ETC. - SUBMIT A DETAIL FOR THE |
| | EMERGENCY OVERFLOW SCUPPERS. INDICATE |
| | THE SIZE, (LENGHT & WIDTH), AS WELL AS |
| | THE MEASUREMENT FROM THE ROOF TO THE |
| | FLOW LINE OF SCUPPER. (2" TO 4") - |
| | SCUPPERS SHALL BE SIZED PER SECTIONS |
| | 1101.7 & 1107.3 ALONG WITH TABLE 1106.7. |
| | THE SIZING OF THE SCUPPERS CAN NOT BE |
| | DETERMINED WITHOUT REFERENC TO THE |
| | DEFLECTION OF THE ROOF. PLEASE INDICATE |
| | ON PLANS THE CLACULATIONS FOR THE |
| | SCUPPERS. |
| | |
| | 2B. SHT A-3.2 INDICATES A GUEST WASH |
| | MACHINE & DRYER WITH NO APPARANT ACCESS, |
| | SANITARY PIPING OR WATER SUPPLY. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 3B. SHT A-3.3 CANOPY. SUBMIT |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | ROOF DRAINS. SHOW SF BEING DRAINED BY |
| | EACH PRIMARY DRAIN. INDICATE DRAIN SIZE, |
| | RWL SIZE, FOR PRIMARY AND OVERFLOW |
| | DRAINS. SUBMIT RISER DIAGRAMS FOR BOTH |
| | SYSTEMS INDICATING PIPE SIZE, OFFSETS |
| | AND TERMINATION POINTS. SECTIONS 1106 & |
| | 1107 AND TABLE 1106.3. |
| | |
| | 4B. SHTS A10.62 THRU A10.65 REFERENCE A |
| | "HEAT N GLO" GAS FIREPLACE. THIS IS |
| | SHOWN ON THE FLOOR PLAN, BUT NOT THE GAS |
| | RISER DIAGRAM. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 5B. SHT P-1.07 INDICATES A DRAIN FOR THE |
| | FIRE SPRINKLER SYSTEM IN THE STAIRWELL |
| | ADJACENT TO RISER W-2. PLEASE INDICATE |
| | WHAT THE DRAIN WILL DRAIN INTO. SECTION |
| | 106.1.1. |
| | |
| | 6B. SHT P-2.01 LAUNDRY WATER HEATER, |
| | THERMAL EXPANSION CONTROL REQUIRED PER |
| | SECTION 607.3.2. |
| | |
| | 7B. SHT P-3.04 WATER MAIN PIPE SIZES DO |
| | NOT REFLECT PIPE SIZES SHOWN ON SHTS |
| | P-1.07 & P-5.01. PIPE SIZES TO FROM 3" |
| | TO 2" THEN BACK TO 2-1/2". PLEASE |
| | CORRELATE WATER DISTRIBUTION RISERS, |
| | FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 8B. ALL ARCHITECTURAL SHEETS, ALL PME |
| | SHEETS: IF THE DESIGN PROFESSIONAL IS AN |
| | ARCHITECT OR ENGINEER LEGALLY RESISTERED |
| | UNDER THE LAWS OF THIS STATE REGULATING |
| | THE PRACTICE OF ARCHITECTURE AS PROVIDED |
| | FOR IN CHAPTER 481, FLORIDA STATUTES, |
| | PART 1, OR ENGINEERING AS PROVIDED FOR |
| | IN CHAPTER 471, FLORIDA STATUTES, THEN |
| | HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE SEAL |
| | IS AFFIXED TO SAID DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA, AS |
| | REQUIRED BY FLORIDA STATUTES. SECTION |
| | 106.1. |
| | |
| | 9B. A SEPARATE IRRIGATION PERMIT AND |
| | PLANS ARE REQUIRED. THIS MAY BE |
| | SUBMITTED AT A LATER DATE. SECTIONS |
| | 105.1 AND 106.3.5.1.3. |
| | |
| | 10B. SUBMIT A ROOF PLAN SHOWING THE |
| | LOCATION OF ALL VENTS FOR THE SANITARY |
| | SYSTEM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |