| 2006-06-15 00:00:00 | CCCDENIED:2004 FLORIDA BUILDING CODE |
| | |
| | 1.PLAN SHEET A-6.1, PARTITION DETAILS |
| | ARE NOT LEGIBLE ON TYPES W1 THROUGH W7 |
| | AND W9 THROUGH W11. |
| | |
| | 2.PLAN SHEET M-1.01 PLEASE CLARIFY THE |
| | SHAFTS LOCATED IN ROOM 181 & 151. |
| | ACCORDING TO THE PLAN THE SHAFT WILL |
| | START AT THE SECOND FLOOR AND A FIRE |
| | DAMPER WILL BE INSTALLED AT THE |
| | PENETRATION THROUGH THE 1ST FLOOR |
| | CEILING/2ND FLOOR SLAB, IS THIS CORRECT? |
| | |
| | 3.PLAN SHEET A-1.1 AHU CLOSET IN ROOM |
| | 159 (MAINT/ENGINEERING) INDICATES A 20 |
| | MINUTE LOUVERED DOOR.WILL THE LOUVER |
| | HAVE A FIRE DAMPER?PLEASE CLARIFY IF |
| | THIS WILL BE USED FOR STORAGE?THE DOOR |
| | SCHEDULE ON PLAN SHEET A-6.3.2 INDICATES |
| | THIS AS A "JANITOR" ROOM.RETURN AIR IS |
| | ONLY REQUIRED FROM HABITABLE ROOMS, |
| | STORAGE & LAUNDRY ROOMS ARE EXCLUDED. |
| | 2004 FMC 601.4 EXCEPTION #3. |
| | |
| | 4.MECHANICAL CLOSETS SHALL COMPLY WITH |
| | 2004 FMC 603.9. |
| | |
| | 5.PLEASE PROVIDE ENERGY AND MANUAL N |
| | CALCULATIONS IN ACCORDANCE WITH |
| | 407.1.ABC.1 & SECTION 3.1 OF APPENDIX |
| | 13-B. |
| | |
| | 6.PLEASE PROVIDE MANUFACTURE SUBMITTAL |
| | DATA FOR THE GENERATOR INSTALLATION. |
| | PLAN SHEET P-3.05 INDICATES NATURAL GAS |
| | AS THE FUEL TYPE.PLEASE NOTE, |
| | GENERATOR SHALL BE PROTECTED FROM |
| | DAMAGE 2004 FMC 303.4. |
| | |
| | 7.PLEASE PROVIDE DETAIL FOR THE |
| | VENTING OF THE GAS DRYERS.PLEASE |
| | INDICATE DUCT SIZE, MATERIAL & |
| | TERMINATION. SHOW COMPLIANCE WITH 2004 |
| | FFGC 614 & APPENDIX B.PLEASE INDICATE |
| | IF THE DRYERS WILL BE DUCTED SINGLE |
| | APPLIANCE OR TWO OR MORE APPLIANCES |
| | VENTED TOGETHER.PLEASE PROVIDE |
| | MANUFACTURE SUBMITTAL DATA FOR THE GAS |
| | DRYERS. |
| | |
| | 8.PLEASE PROVIDE COMBUSTION AIR |
| | CALCULATIONS FOR THE LAUNDRY ROOM. |
| | |
| | 9.PLEASE PROVIDE MANUFACTURE SUBMITTAL |
| | DATA FOR THE LAUNDRY CHUTE.SHOW |
| | COMPLIANCE WITH 2004 FBC 903.2.10.2 & |
| | NFPA 13.15.2.1.1. |
| | |
| | 10. PLEASE PROVIDE ANCHORING DETAIL FOR |
| | THE CONDENSING UNITS IN ACCORDANCE WITH |
| | 2004 FMC 301.13 & 301.13.1. |
| | |
| | 11. PLEASE PROVIDE SUBMITTAL FOR MAU-1 & |
| | 2. |
| | |
| | 12. PLEASE PROVIDE ANCHORING DETAIL FOR |
| | THE CURBS LOCATED ON THE ROOF. |
| | |
| | 13. FAN SHUTDOWN BY DUCT SMOKE DETECTOR. |
| | PER 2004 FMC 606.2.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |