Plan Review Notes
Plan Review Notes For Permit 06040135
Permit Number 06040135
Review Stop M
Sequence Number 1
Notes
Date Text
2006-06-15 00:00:00CCCDENIED:2004 FLORIDA BUILDING CODE
  
 1.PLAN SHEET A-6.1, PARTITION DETAILS
 ARE NOT LEGIBLE ON TYPES W1 THROUGH W7
 AND W9 THROUGH W11.
  
 2.PLAN SHEET M-1.01 PLEASE CLARIFY THE
 SHAFTS LOCATED IN ROOM 181 & 151.
 ACCORDING TO THE PLAN THE SHAFT WILL
 START AT THE SECOND FLOOR AND A FIRE
 DAMPER WILL BE INSTALLED AT THE
 PENETRATION THROUGH THE 1ST FLOOR
 CEILING/2ND FLOOR SLAB, IS THIS CORRECT?
  
 3.PLAN SHEET A-1.1 AHU CLOSET IN ROOM
 159 (MAINT/ENGINEERING) INDICATES A 20
 MINUTE LOUVERED DOOR.WILL THE LOUVER
 HAVE A FIRE DAMPER?PLEASE CLARIFY IF
 THIS WILL BE USED FOR STORAGE?THE DOOR
 SCHEDULE ON PLAN SHEET A-6.3.2 INDICATES
 THIS AS A "JANITOR" ROOM.RETURN AIR IS
 ONLY REQUIRED FROM HABITABLE ROOMS,
 STORAGE & LAUNDRY ROOMS ARE EXCLUDED.
 2004 FMC 601.4 EXCEPTION #3.
  
 4.MECHANICAL CLOSETS SHALL COMPLY WITH
 2004 FMC 603.9.
  
 5.PLEASE PROVIDE ENERGY AND MANUAL N
 CALCULATIONS IN ACCORDANCE WITH
 407.1.ABC.1 & SECTION 3.1 OF APPENDIX
 13-B.
  
 6.PLEASE PROVIDE MANUFACTURE SUBMITTAL
 DATA FOR THE GENERATOR INSTALLATION.
 PLAN SHEET P-3.05 INDICATES NATURAL GAS
 AS THE FUEL TYPE.PLEASE NOTE,
 GENERATOR SHALL BE PROTECTED FROM
 DAMAGE 2004 FMC 303.4.
  
 7.PLEASE PROVIDE DETAIL FOR THE
 VENTING OF THE GAS DRYERS.PLEASE
 INDICATE DUCT SIZE, MATERIAL &
 TERMINATION. SHOW COMPLIANCE WITH 2004
 FFGC 614 & APPENDIX B.PLEASE INDICATE
 IF THE DRYERS WILL BE DUCTED SINGLE
 APPLIANCE OR TWO OR MORE APPLIANCES
 VENTED TOGETHER.PLEASE PROVIDE
 MANUFACTURE SUBMITTAL DATA FOR THE GAS
 DRYERS.
  
 8.PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE LAUNDRY ROOM.
  
 9.PLEASE PROVIDE MANUFACTURE SUBMITTAL
 DATA FOR THE LAUNDRY CHUTE.SHOW
 COMPLIANCE WITH 2004 FBC 903.2.10.2 &
 NFPA 13.15.2.1.1.
  
 10. PLEASE PROVIDE ANCHORING DETAIL FOR
 THE CONDENSING UNITS IN ACCORDANCE WITH
 2004 FMC 301.13 & 301.13.1.
  
 11. PLEASE PROVIDE SUBMITTAL FOR MAU-1 &
 2.
  
 12. PLEASE PROVIDE ANCHORING DETAIL FOR
 THE CURBS LOCATED ON THE ROOF.
  
 13. FAN SHUTDOWN BY DUCT SMOKE DETECTOR.
 PER 2004 FMC 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  