| 2006-06-15 00:00:00 | ***DENIED*** |
| | |
| | 1) TEMPORARY STANDPIPES REQUIRED WHEN |
| | BUILDING REACHES (3) STORIES OR 30' IN |
| | HEIGHT. |
| | |
| | 2) PLEASE REFER TO NFPA 101, 2003 |
| | EDITION SEC. 28.2.6 REGARDING TRAVEL |
| | DISTANCE REQUIREMENTS FOR NEW HOTELS. |
| | |
| | 3) ADDRESS REQUIRED ON BUILDING THAT |
| | SHALL BE MINIMUM OF 6" IN HEIGHT AND |
| | CONTRASTING TO THE BACKGROUND. PLEASE |
| | SHOW ON ELEVATIONS. |
| | |
| | 4) PLEASE PROVIDE MANUFACTURER SPEC |
| | SHEETS FOR GENERATOR AND ASSOCIATED |
| | EQUIPMENT. |
| | |
| | 5) POOL AREA SHOWS (1) EXIT. DOES THIS |
| | AREA MEET EXCEPTION FOR SINGLE EXIT? |
| | |
| | 6) WILL CARD READERS IMACT REQUIRED |
| | EXITING FROM BUILDING? |
| | |
| | 7) EMERGENCY INSTRUCTIONS SHALL BE |
| | POSTED IN COMPLIANCE WITH NFPA 101, SEC. |
| | 28.7.4. |
| | |
| | 8) ELEVATORS SHALL COMPLY WITH ASME |
| | 17.1. |
| | |
| | 9) SIGNAGE SHALL BE PROVIDED IN |
| | STAIRWELLS INDICATING FLOOR |
| | IDENTIFICATION, TOP, BOTTOM AND |
| | DIRECTION TO EXIT DISCHARGE. |
| | |
| | 10) TACTILE SIGNAGE REQUIRED AT EXIT |
| | STAIRS. |
| | |
| | 11) SAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 12) HANDRAILS AND GUARDS TO COMPLY WITH |
| | NFPA 101, CHAPTER 7. INCORRECT EDITION |
| | REFERENCED ON SHT A-6.2. |
| | |
| | 13) SEPARATE SHOPDRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 14) FIRE ALARM SYSTEM SHALL BE UL |
| | CERTIFIED FOR CENTRAL STATION SERVICE. |
| | |
| | 15) FIRE SPRINKLER SYSTEM TO COMPLY WITH |
| | NFPA 13, 2002 EDITION. |
| | |
| | 16) FIRE DEPARTMENT VALVES SHALL BE 2 |
| | 1/2"- 1 1/2" REDUCER WITH CHAIN. |
| | |
| | 17) NO FIRE SPRINKLER SHOWN IN WOMENS |
| | ROOM, SHT FP-4. |
| | |
| | 18) PLEASE SUBMIT MANUFACTURER SPEC |
| | SHEETS FOR FIRE PUMP AND ASSOCIATED |
| | EQUIPMENT. |
| | |
| | 19) LOCKING KNOX CAPS REQUIRED ON FIRE |
| | DEPARTMENT CONNECTIONS. |
| | |
| | 20) SOME OF THE GUEST ROOMS SHOW SMOKE |
| | DETECTORS TIED TO FA. SINGLE STATION |
| | TYPES ARE REQUIRED AS SHOWN ON SHT |
| | 4.1.1E. |
| | |
| | 21) ADDITIONAL EXIT SIGNS AND EMERGENCY |
| | LIGHTS ARE REQUIRED ON SHT 1.1EA. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |