Plan Review Notes
Plan Review Notes For Permit 06040135
Permit Number 06040135
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-15 00:00:00***DENIED***
  
 1) TEMPORARY STANDPIPES REQUIRED WHEN
 BUILDING REACHES (3) STORIES OR 30' IN
 HEIGHT.
  
 2) PLEASE REFER TO NFPA 101, 2003
 EDITION SEC. 28.2.6 REGARDING TRAVEL
 DISTANCE REQUIREMENTS FOR NEW HOTELS.
  
 3) ADDRESS REQUIRED ON BUILDING THAT
 SHALL BE MINIMUM OF 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND. PLEASE
 SHOW ON ELEVATIONS.
  
 4) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR GENERATOR AND ASSOCIATED
 EQUIPMENT.
  
 5) POOL AREA SHOWS (1) EXIT. DOES THIS
 AREA MEET EXCEPTION FOR SINGLE EXIT?
  
 6) WILL CARD READERS IMACT REQUIRED
 EXITING FROM BUILDING?
  
 7) EMERGENCY INSTRUCTIONS SHALL BE
 POSTED IN COMPLIANCE WITH NFPA 101, SEC.
 28.7.4.
  
 8) ELEVATORS SHALL COMPLY WITH ASME
 17.1.
  
 9) SIGNAGE SHALL BE PROVIDED IN
 STAIRWELLS INDICATING FLOOR
 IDENTIFICATION, TOP, BOTTOM AND
 DIRECTION TO EXIT DISCHARGE.
  
 10) TACTILE SIGNAGE REQUIRED AT EXIT
 STAIRS.
  
 11) SAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 12) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, CHAPTER 7. INCORRECT EDITION
 REFERENCED ON SHT A-6.2.
  
 13) SEPARATE SHOPDRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 14) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 15) FIRE SPRINKLER SYSTEM TO COMPLY WITH
 NFPA 13, 2002 EDITION.
  
 16) FIRE DEPARTMENT VALVES SHALL BE 2
 1/2"- 1 1/2" REDUCER WITH CHAIN.
  
 17) NO FIRE SPRINKLER SHOWN IN WOMENS
 ROOM, SHT FP-4.
  
 18) PLEASE SUBMIT MANUFACTURER SPEC
 SHEETS FOR FIRE PUMP AND ASSOCIATED
 EQUIPMENT.
  
 19) LOCKING KNOX CAPS REQUIRED ON FIRE
 DEPARTMENT CONNECTIONS.
  
 20) SOME OF THE GUEST ROOMS SHOW SMOKE
 DETECTORS TIED TO FA. SINGLE STATION
 TYPES ARE REQUIRED AS SHOWN ON SHT
 4.1.1E.
  
 21) ADDITIONAL EXIT SIGNS AND EMERGENCY
 LIGHTS ARE REQUIRED ON SHT 1.1EA.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  