Plan Review Notes
Plan Review Notes For Permit 06040135
Permit Number 06040135
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-14 00:00:00ONE ROLL IN ELEC FOR REVIEW,
 ******** UNSAT 2ND REVIEW *******
  
 **FAIRFIELD INN/SUITES, FIRST REVIEW
 UNDER 2004 FBC.
  
 ** PLEASE KNOW, PLANS ARE NOT COMPLETE
 AT THIS TIME FOR A COMPLETE REVIEW FOR
 CODE COMPLIANCE.
  
  
 ** PLEASE KNOW, PLANS ORIGINALLY CAME IN
 UNDER THE 2001 FBC AND NOW PLANS ARE
 SUBMITTED UNDER THE 2004 FBC. PLEASE SEE
 MOST OF THE COMMENTS ARE NEW, HOWEVER
 SOME ARE FROM PREVIOUS REVIEW.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ANY OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
  
 1) NOTE: PLEASE SEE ADDRESSING FOR
 PROJECT SHOULD BE ON TITLE BLOCK FOR
 LOCATION OF PROJECT.
 FAC61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE CLARIFY TITLE BLOCK ON
 COVER SHEETS AND ALL TRADE SHEETS.
 PLEASE ALSO SEE STUCTURAL, MECHANICAL
 AND PLUMBING SHEETS AS THESE DO NOT
 CONTAIN ANY TITLE BLOCKS FOR THE
 ENGINEERS OR ENGINEERING FIRMS AS LISTED
 ON COVER SHEETS.
 ** PLEASE SEE A PRINT OUT FROM THE
 STATE'S WEBSITE IS NOW ATTACHED TO
 NOTES, AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER AS INDICATE ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM IS
 "NULL AND VOID" PER DEPARTMENT OF
 BUSINESS AND PROFESSIOAL REGULATION.
 PLEASE SEE ELECTRICAL SHEETS DO NOT
 INDICATE THIS AND LIST THE ENGINEER AS
 AN INDIVIDUAL?
 PLEASE SEE FAC 61G15-23.002, FS 471.023,
 IF ARCHITECTURAL FIRM IS OFFERING
 ENGIEERING SERVICES, PLEASE PROVIDE
 CERTIFICATE OF AUTHORIZATION FOR THIS.
 THE CA # WAS ADDED FOR ARCHITECTURAL
 FIRM AS REQUESTED ON PREVIOUS REVIEW
 HOWEVER AS NOTED ABOVE, SEEMS NOT BE
 ACTIVE.
 ** PLEASE SEE TITLE BLOCKS ARE MISSING
 THE PRINTED NAME AND LICENSE NUMBER THE
 ARCHITECT AS REQUIRED PER FAC
 61G1-16.004
  
 ** PLEASE BE SURE ALL THREE SETS ARE
 SIGNED, DATED AND SEALED AS REQUIRED
 UNDER FS 481.221,471.025, FAC
 61G1-16,61G15-23.002
 PLEASE SEE MANY SHEETS IN SOME SETS ARE
 NOT SIGNED OER SEALED. PLEASE ALSO SEE
 SOME ROLLS SUBMITTED ARE NOT SIGNED AND
 SEALED AT ALL??
 ***************************************
 **THIS IS FOR ALL TRADES AND FOR ALL
 REVIEWS, WHETHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
 **************************************
  
 3) NOTE: PLEASE SEE FP SHEETS, AS SOME
 SHEETS IN SOME SETS ARE PHOTO-COPIES OF
 SIGNED AND SEALED PLANS.
  
 4) NOTE: PLEASE KNOW, PLANS ARE NOW
 BEING SUBMITTED UNDER THE 2004 FBC,
 HOWEVER NO CHANGES IN ELECTRICAL DESIGN
 WERE MADE TO THE NEW 2004 CHAPTER 13.
 PLEASE SEE CHAPTER 13, 13-413.1ABC.1,
 PLEASE PROVIDE ALL WORST CASE CALCS, AND
 ADJUST AS NEEDED FOR LONGEST RUNS.
 PLEASE SEE 13-415.1.ABC.1.1, &.2, & .3
 WHICH GREATLY AFFECT ELECTRICAL DESIGN.
 COULD NOT LOCATE ANY INFORMATION FOR
 THIS ON PLANS.?
 PLEASE SEE ALL OTHER CHANGES IN CHAPTER
 13. FIXTURE TYPES, TANDEM WIRING ETC.
  
 5)NOTE: PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR ALL EGRESS
 AREAS/PATHS.
 PLEASE SEE NFPA-101 2003, 7.8.1.3,
 7.9.2.2. PLEASE SEE STAIRS FOR EGRESS
 SHALL CONTAIN A MIN OF 10FT CANDLES AVG
 UNDER NORMAL CONDITIONS AND 1FT CANDLE
 AVG UNDER EM POWER.
 PLEASE SEE MIN REQUIRED FOR ALL OTHER
 PATHS SHALL BE 1FT CANDLE.
 PLEASE ALSO KNOW, AN EM BATTERY BACK UP
 FIXTURE OF SOME TYOE WILL BE REQUIRED IN
 THE MAIN ELECTRICAL ROOM.
 ** PLEASE SEE NOTES ON PLANS MENTIONS
 THE 10 FT CANDLES AT "WAIST LEVEL"?
 PLEASE SEE NFPA-101, AS THIS IS MEASURED
 AT THE WALKING SURFACE.
  
 6) NOTE:PLEASE SEE THE FOLLWOING WAS
 ALSO NOTED ON PREVIOUS REVIEW NOTE #15.
 PLEASE SEE NO INFORMATION WAS SUBMITTED
 FOR THE FIRE PUMP, FIRE PUMP CONTROLLER.
 PLEASE KNOW, ALL PLANS AND INFORMATION
 FOR THIS SHALLBE SUBMITTED.
 PLANS NOW INDICATE A FIRE PUMP LOCATED
 IN A DETACHED BUIDLING? WHICH WILL FEED
 TWO DIFFERENT HOTELS.
 PLEASE KNOW, APPROVAL BY THE FIRE
 MARSHAL'S OFFICE SHALL FIRST BE OBTAINED
 FOR THIS SCENERIO. PLEASE ALSO KNOW,
 PERMIT FOR EITHER BUILDING CAN NOT BE
 PASSED FOR PERMITING UNTIL ALL
 INFORMATION, PLANS ETC FOR FIRE PUMP,
 FIRE PUMP CONTROLLER CAN BE REVIEWED. IF
 ELECTRICAL DRIVEN FIRE PUMP, PLEASE
 PROVIDE ALL INFORMATION.
 PLEASE SEE FP SEEMS TO INDICATE
 ELECTRICAL FIRE PUMP.PLEASE SEE THIS
 FIRE PUMP IS STILL BEING SHOWN BEING FED
 FROM THE MSB WHICH IS NOT PERMITTED AS
 STATED IN PREVIOUS NOTES. PLEASE SEE
 695.4 NEC, NFPA-20 2002.
 PLEASE KNOW, THIS INFORMATION WILL BE
 REQUIRED UNDER THIS PERMIT. THE FIRE
 SPRINKLER AND FIRE ALARM ARE ALSO UNDER
 A SEPARATE PERMIT.MININUM INFORMATION IS
 REQUIRED FOR THE PERMIT ISSUANCE OF EACH
 HOTEL.
  
 7) NOTE: PLEASE SEE PLANS ARE NOW
 INDICATING A BACK UP GENERATOR OF SOME
 SORT? IF ANY PART OF THIS SYSTEM IS
 GOING TO BE INSTALLED, PLEASE SUBMIT ALL
 INFORMATION FOR ATS, GENERATOR,
 ELECTRICAL RISER, SUB BASE FUEL ETC.
 PLEASE SEE TWO SEPARATE ATS'S ARE BEING
 SHOWN ON PLANS AT THIS TIME, HOWEVER
 THIS IS NOTBEING SHOWN WIRED INTO
 RISER?
 PLEASE KNOW, IF NO PART OF THIS SYSTEM
 IS GOING TO BE INSTALLED AT THIS TIME,
 PLEASE REMOVE FROM PLANS AS LONG AS ALL
 MIN LIFE SAFETY BACK UP SYSTEMS ARE
 PROVIDED BY OTHER MEANS.
 **
 PLEASE SUBMIT ALL MANUFACTURE CUT
 SHEETS/SPEC FOR GEN, ATS'S, FIRE PUMP,
 FIRE PUMP CONTROLLER, AND ANY FUEL TANKS
 FOR ITEMS BEING INSTALLED.
  
 8) NOTE: PLEASE SEE PANEL "P" ON SHOWS
 MCB AS REQUIRED, YET PANEL SCHEDULE
 SHOWS THIS PANEL AS "MLO". PLEASE KNOW,
 THIS PANEL IS NOT SHOWN ON PLANS AND
 COULD NOT BE LCOATED?? IS THIS IN A
 DETACHED STRUCTURE? PLEASE KNOW A MEANS
 OF DISCONNECT WILL BE REQUIRED PER
 225.31 AND ALL GROUNDING SHALL BE
 INDICATED PER 250.32
  
 9) NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR ON RISER IS SHOWN AS 1/0?
 PLEASE SEE MIN SHALL BE SIZED PER
 250.66. PLEASE SEE GROUNDING DETAIL
 SUBMITTED INDICATE 1/0 AND 3/0??
 PLEASE CORRELATE WITH MIN REQUIRED.
  
 10) NOTE: PLEASE PROVIDE REFERENCES TO
 THE FOLLOWING CODES ON ELECTRICAL PLANS.
 NFPA-101 2003, NFPA-70 2002, NFPA-72
 2002, NFPA-110 2002, NFPA-20 2002.
 ** PLEASE SEE REPSONSE MENTIONS TO SEE
 COVER SHEET FOR CORRECTED CODES, HOWEVER
 PLEASE SEE COVER SHEETS REFERENCE A
 "2003" NEC? PLEASE SEE WE ARE UNDER 2002
 AND A 2003 IS NOT IN ISSUE. (MISPRINT)?
  
 10) NOTE: PLEASE INDICATE ALL ELECTRICAL
 PANELS ON ALL SHEETS FOR POWER.PLEASE
 SEE ELECTRICAL ROOMS ARE BEING SHOWN
 WITH EGRESS THORUGH "MAIDS CLOSETS".
 THIS WILL NOT BE PERMITTED. MAY NOT
 ACCESS ELECTRICAL ROOMS THROUGH STORAGE
 CLAOSETS OF ANY TYPE.
 PLEASE SEE ALL EGRESS SHALL CONTAIN A
 CLEAR AND UN-OBSTRUCTED PATH OF TRAVEL.
 110.26,408.7,240.24 ETC
  
 11) NOTE: PLEASE SEE PLANS FOR "LARGE
 SCALECOMMERCIAL AREA" ARE NOT
 COMPLETE. PLEASE SEE MISSING LAYOUT FOR
 AREAS LOCATED ON THE FIRST FLR.?
 PLEASE COMPLETE SETS AND PLANS. 215.5
  
 12) NOTE: PLEASE SEE 210.8B3 FOR
 KITCHENS, SEE ALL RECEPTS 15/20A 120 V
 SHALL BE GFI/GFI PROTECTED.
 PLEASE SEE MOST AREAS WERE DONE, HOWEVER
 PLEASE SEE ALL AREAS ARE REQUIRED.
 PREVIOUS REVIEW COMMENT.
  
 13) NOTE: PLEASE SEE GUEST RMS WHICH ARE
 BEING NOTED AS SUITES/DWELLINGS AND
 ROOMS.
 PLEASE SEE 210.60,210.52 PLEASE ADJUST
 ALL CIRCUITING AND LOAD CALCULATIONS,
 PANELS ON PLANS.
 215.5
  
 14) NOTE: PLEASE SUBMIT WIND LOAD
 CALCUALTIONS FOR SITE LIGHTING POLES AS
 REQUESTED ON PREVIOUS REVIEW. THIS COULD
 NOT BE LOCATED ON SITE LIGHTING PLANS?
 215.5
  
 15) NOTE: PLEASE SEE A PREVIOUS NOTE
 MENTIONED THE USE OF A SHUNT TRIP
 BREAKER AND THE MCB STILL BEING REQUIRED
 TO HAVE A MANUAL MEANS OF DISCONNECT
 LOCATED ON THE OUTSIDE RATED RATED FOR
 THE LOAD SERVED. 230.76,230.79 ETC.
 PLEASE SEE PLANS SHALL INDICATE A
 MANUALS MEANS, ETC.
 ** PLEASE ALSO SEEPLANS INDICATE A
 "SERVICE MAIN" LOCATED OUTSIDE HOWEVER
 THIS IS NOT INCLUDED IN RISER?
 215.5
  
 16) NOTE: PLEASE INDICATE PANELS AS
 "FEEDE-THRU" AS PANEL BOARDS SHALL NOT
 CONTAIN MORE THE 42 SPACES.408.15
 PLEASE SEE ALL PANELS ON UPPER FLRS.
  
 17) NOTE: PLEASE SEE A/C UNIT IN ROOMS
 CONSIDERED TO MEET DWELLING UNIT BEDRMS
 SHALL ALSO MEET 210.12B NEC. 2002
  
 18) NOTE: PLEASE SEE NOTES ON RISER AS
 THESE WILL BE AFFECTED BY REVISONS ON
 PLANS.
  
 19) NOTE: PLEASE SEE FIRE REVIEW
 COMMENTS FOR STRETCHER ACCESSIBLE ELEV.
  
 20) NOTE: PLEASE SUBMIT HP RATINGS OF
 ELEVATOR MOTORS, UNABLE TO VERIFY AT
 THIS TIME. NO HP RATING SOR SIZES
 SUBMITTED.
 215.5
  
 21) NOTE: PLEASE SEE CIRCUITES FOR
 ELEVATOR EQUIPMENT DOES NOT CORRELATE
 WITH MSB>.
 215.5
  
 22) NOTE: PLEASE ALSO CORRELATE
 SERVICE MAIN.
 PLEASE SEE RISER IDENTIFIES MAIN AS MSB
 AND SCHEDULE SHOWS MDP?
 PLEASE KEEP IN MIND THE PREVIOUS NOTE
 WIH RESPECT TO THE PLANS ALSO INDICATING
 A "MAIN SERVICE DISC" OUTSIDE?
 215.5
  
 23) NOTE: PLEASE SEE A PANEL "EG" IS
 SHOWN ON PANEL SCHEDULES, HOWEVER NOT
 INFORMATION ON RISER FOR THIS?:
 PLEASE SEE THIS IS ALSO ON PLANS,
 HOWEVER THERE IS NOT ENOUGH INFORMATION
 FOR THIS PANEL, ATS ETC.
 215.5
  
 24) NOTE: PLEASE SEE PANEL 1A SHOWS
 CIRCUITED TO MSB W/ 100A OCP, YET
 MSB/MDP LIST THIS WITH 125A OCP?? PLEASE
 CORRELATE.
  
  
 ** PLEASE KNOW, BASED ON THE PLANS AND
 INFORMATION SUBMITTED THERE MAY BE OTHER
 COMMENTS AS A COMPLETE REVIEW FOR CODE
 COMPLIANCE COULD NOT BE DONE AT THIS
 TIME.
 PLEASE BE SURE TO SEE ALL OF THE 2004
 FBC CHAPTER 13 FOR ELECTRICAL CHANGES.
  
 ** PLEASE KNOW, ONE SET OF PLANS ARE
 BEING RETAINED.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  