| 2006-05-15 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06040135 |
| | ADD: 2208045TH ST |
| | CONT:O'CONNORS& TAYLOR, INC. |
| | TEL: (561)863-7349 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) PLEASE CONTACT LILI URSA MIS |
| | ADDRESSING TECHNITION FOR THE CORRECT |
| | ADDRESS. CITY RECORDS INDICATE THE |
| | CORRECT ADDRESS TO BE 2200 45TH STREET |
| | FOR THIS PARCEL. CONTACT LILI @ (561) |
| | 805-1239. |
| | |
| | THE LETTER FROM THE ARMY CORP OF |
| | ENGINEERS IS FOR THE PROPERTY LOCATED AT |
| | 2200 45TH ST NOT 2208 45TH STREET. |
| | |
| | 3) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 4)DLW ARCHITECTS- AA0002714 THE |
| | CERTIFICATE OF AUTHORIZATION IS NULL & |
| | VOID SINCE 02/28/2003. |
| | 481.219 F.S.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING |
| | ARCHITECTURAL SERVICES, SHALL INCLUDE |
| | THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER.ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 5) ALL A-10 SHEETS (PRODUCT APPROVALS) |
| | THE DESIGN PROFESSIONAL FAILED TO SIGN |
| | AND SEAL THESE SHEETS. |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 6) THIS STRUCTURE IS CONCIDERED A |
| | THRESHOLD BUILDING REQUIRING (3) OF ALL |
| | DOCUMENTS TO BE SUBMITTED TO THE |
| | BUILDING DEPARTMENT, PLANS, REVISIONS, |
| | LETTERS,AND OR SUBMITTALS,ETC |
| | |
| | 7A) WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 7B)FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A |
| | BUILDING PERMIT FOR THE CONSTRUCTION OF |
| | A THRESHOLD BUILDING. THE PURPOSE OF |
| | THE SRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES |
| | AND SCHEDULES SO THAT THE BUILDING CAN |
| | BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | T-0.01INSPECTION PLAN DOESN'T |
| | INDICATE ANY SHORING OR RESHORING IN THE |
| | INSPECTION PLAN, NOR LENGTH OF TIME |
| | SHORING SHOULD BE PLACED THERE. |
| | |
| | 8) SOILS REPORT SUBMITTED IS A COPY OF |
| | THE SOILS ENGINEERS' SIGNATURE. NO |
| | RAISED SEAL. |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORICSURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 10) 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM |
| | HIGHWINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 11) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G) NUMBER OF UNITS |
| | H) NUMBER OF FLOORS |
| | I) NUMBER OF BEDROOMS |
| | J) NUMBER OF ROOMS |
| | K) NUMBER OF BEDROOMS |
| | L) SQ. FT. LIV SPACE/ FL |
| | M) SQ. FT. FOOTPRINT |
| | N) SQ. FT. UNDER ROOF (TOTAL) |
| | O) OCCUPANT LOAD |
| | P) FLOOD ZONE |
| | |
| | 12) 1609.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | |
| | 13) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 14) THE DESIGNER OF RECORD PRINTING THE |
| | PRODUCT APPROVALS AS PART OF THE PLAN |
| | MAKES IT DIFFICULT TO SEE WHAT APPROVALS |
| | ARE PRESENT AND WHICH AREN'T. ALSO NOTE |
| | IF THE CONTRACTOR CHANGES OUT PRODUCTS |
| | ( A REVISION) THE PRODUCT APPROVALS |
| | PRINTED ON THE ARCHITECTURAL SHEETS WILL |
| | BE CHARGED A BASE FEE OF $50.00 AND |
| | $10.00 A PAGE WHERE AS THE PRODUCT |
| | APPROVAL ITSELF IS CHARGED A TOTAL OF |
| | $60.00. |
| | |
| | 15) FL BLD CODE CHAP 13 ENERGY EFFICENCY |
| | PROVIDE ENERGY CALS/ W MANUAL "J". |
| | PLEASE USE THE 2004 FORMS. IF A DESIGN |
| | PROFESSIONAL PRODUCES THE ENERGY CALS, |
| | MUST BE SIGNED AND SEALED. |
| | |
| | 16A) PLANS DO NOT SHOW AN ACCESSIBLE |
| | ENTRANCE, PASSENGER LOADING ZONE, |
| | 11-4.1.2(1). FIGURE 10 ACCESS AISLE AT |
| | PASSENGER LOADING ZONE. |
| | |
| | 16B) 11-4.1.3(1) AT LEAST ONE ACCESSIBLE |
| | ROUTE COMPLYING WITH 11-4.3 SHALL |
| | CONNECT ACCESSIBLE BUILDINGS OR FACILITY |
| | ENTRANCES WITH ALL ACCESSIBLE SPACES AND |
| | ELEMENTS WITHIN THE BUILDING OR |
| | FACILITY. |
| | |
| | 17) A-0.1.1 THE PLANS DO NOT SHOW AN |
| | ACCESSIBLE ROUTE TO 45TH ST.11-4.1.2(1) |
| | AN ACCESSIBLE SITE SHALL MEET THE |
| | FOLOWING MINIMUM REQUIREMENTS: |
| | (1) AT LEAST ONE ACCESSIBLE ROUTE |
| | COMPLYING WITH SECTION 11-4.3 SHALL BE |
| | PROVIDED WITHIN THE BOUNDRY OF THE SITE |
| | FROM PUBLIC TRANSPORTATION STOPS, |
| | ACCESSIBLE PARKING SPACES, PASSENGER |
| | LOADING ZONES IF PROVIDED, AND PUBLIC |
| | STREETS OR SIDEWALKS, AND ACCESSIBLE |
| | BUILDING ENTRANCE. |
| | |
| | 18) SHEET A-0.1.1 INDICATES THERE TO BE |
| | A TOTAL OF 102 PARKING SPACES REQUIRING |
| | (5) HANDICAPPED PARKING SPACES NOT 4. |
| | SEE 11-4.1.2(5) 101-150 +5 ACCESSIBLE |
| | SPACES. |
| | |
| | 19) SHEET FP-1 PLANS SUBMITTED BY THOMAS |
| | TOWMEY, PE NOT SEALED, |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 20) SHEET FP-6 INDICATES IN (2) SECTIONS |
| | THAT THE 4" MAIN IS GOING THE LENGTH OF |
| | THE ATTIC AREA, A-5.1 AND OTHER CUT |
| | SHEETS INDICATE THE STRUCTURE IS TO HAVE |
| | A FLAT ROOF WITH ARCHITECTURAL PEDIMENTS |
| | |
| | 21A) FIRE SPRINKLER PLANS WERE SUBMITTED |
| | BUT NO CALCULATIONS? |
| | |
| | 21B) FP-5INDICATES USE OF A CPVC |
| | SPRINKLER SYSTEM WHICH IS A R-13(FOUR |
| | STORIES) WHERE AS THE PLAN CALLS OUT FOR |
| | A FULL 13 SYSTEM.903.3.1.1 NFPA 13 |
| | SPRINKLER SYSTEMS. |
| | |
| | 22) THE FIRE PUMP STRUCTURE FOUND ON |
| | FP-1 DOES NOT SHOW UP ON A-0.1.1, OR |
| | OTHER SHEETS? |
| | |
| | 23) S2.03 INDICATES A MECHANICAL ROOM |
| | FOR THE POOL EQUIPMENT BUT NOT ON THE |
| | SITE PLAN? NOR DOES THE FIRE PUMP ROOM. |
| | |
| | 24) EMERGENCY GENERATOR PROVIDE |
| | ADDITIONAL INFORMATION: |
| | GENERATOR SLAB & ANCHOR REQUIREMENT |
| | PLEASE PROVIDE SIZE OF GENERATOR(WXL), |
| | PLUS PROVIDE PLANS WITH THE INFORMATION |
| | DEPICTING HOLD DOWN BRACKETS, TYPE OF |
| | FASTENER, AND THE MINIMUM EDGE DISTANCE |
| | THE DEVICE REQUIRES WITHOUT LOAD |
| | REDUCTION. |
| | SECOND, PROVIDE INFORMATION ON THE |
| | SLAB, THICKNESS, WIDTH AND LENGTH, IF |
| | WIREMESH, FIBER MESH OR IF STEEL REBAR |
| | WILL BEUSED. |
| | THE NEW SLAB AND HOLD DOWN DETAILS: |
| | 104.2.1* ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 25) SHEET A-0.03 RAMP COMMENT(2) READS |
| | THAT LANDING LENGTH SHALL BE A MINIMUM |
| | OF 60" CLEAR. SHOULD READ: 11-4.8.4(2) |
| | ALL LANDINGS ON RAMPS SHALL BE NOT LESS |
| | THAN 60" CLEAR, AND THE BPTTOM OF EACH |
| | RAMP SHALL HAVE NOT LESS THAN 72" OF |
| | STRAIGHT AND LEVEL CLEARENCE. |
| | |
| | 26) SHEET A0.05 4.3.3 WIDTH SEE |
| | EXEMPTION (44") IF PART OF A MEANS OF |
| | EGRESS. |
| | |
| | 27) SHEET A1.1 INDICATES A DETAIL SEE |
| | A6.2 DETAIL# 3. PLANS INDICATE THAT IT |
| | IS AN ELEC ROOM# 151, BUT THE DETAIL |
| | INDICATES A STAIRWELL? |
| | |
| | 28) SHEET A6.1 UL LISSTING WALL LISTING |
| | SHEET, THE PRINTING IS TO LIGHT, |
| | ILLEGIBLE. |
| | |
| | 29)SHEET A1.1 LAUNDRY CHUTE TERMINATION |
| | ROOM, WALLS ARE TO BE 1HR RATED, A-3.1 |
| | INDICATES A WALL W8 MO SUCH DETAIL? |
| | |
| | 30) SAME ENLARGED LAUNDRY DETAIL SHEET |
| | A-3.1 NOW SHOWS THE LAUNDRY CHUTE ROOM |
| | IN THE LOWWER RIGHT SIDE OF THE LAUNDRY? |
| | |
| | 31) ELEVATOR TO THE LAUNDRY AREA DOESN'T |
| | INDICATE ANY DOOR, 1 1/2 HR PROTECTIVES, |
| | SHAFT OPENING. |
| | |
| | 32) SHEET A-3.1 LOWER LEFT INDICATES A |
| | SECTION 5/A3.2A, MISSING, NO SUCH PAGE. |
| | |
| | 33) A-1 DOOR# C101 & C102 BOTH APPEAR |
| | NOT TO HAVE 18" CLEAR ON THE LATCH SIDE. |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 34) A-1.1/ A-3.1 ROOM# 122, 124& 125. |
| | SAME FOR ALL SLEEPING UNITS. SEE: |
| | 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING |
| | ASSEMBLIES SEPARATING DWELLING UNITS |
| | FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND |
| | TRANSMISSION CLASS (STC) OF NOT LESS |
| | THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. PENETRATIONS |
| | OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| | FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| | VENTILATING OR EXHAUST DUCTS SHALL BE |
| | SEALED, LINED, INSULATED OR OTHERWISE |
| | TREATED TO MAINTAIN THE REQUIRED |
| | RATINGS. THIS REQUIREMENT SHALL NOT |
| | APPLY TO DWELLING UNIT ENTRANCE DOORS; |
| | HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 35) 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN |
| | THE STRUCTURE SHALL HAVE AN IMPACT |
| | INSULATION CLASS (IIC) RATING OF NOT |
| | LESS THAN 50 (45 IF FIELD TESTED) WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 36) A-1.2- A-1.6.THE 2ND THROUGH THE |
| | 6TH FLOORS, ELEVATOR LOBBIES REQUIRED. |
| | SEE 2004 CODE COMMENTARY. "EFFECTIVELY, |
| | THE FOLLOWING BUILDINGS THAT CONTAIN |
| | ELEVATOR OPENINGS INTO A CORRIDOR WOULD |
| | RECEIVE ELEVATOR LOBBIES: |
| | FIVE STORY AND HIGHER FULLY SPRINKLERED |
| | BUILDINGS OF GROUP H,I-1 AND R. |
| | ALL GROUPI-3 BUILDINGS. |
| | NONSPRINKLERD BUILDINGS OF ALL GROUPS |
| | THAT HAVE REQUIRED FIRE-RESISTANCE-RATED |
| | CORRIDORS, EXCEPT OFFICE BUILDINGS IN |
| | COMPLIANCE WITH EXCEPTION # 1. |
| | 707.14.1 ELEVATOR LOBBY. |
| | ELEVATORS OPENING INTO A |
| | FIRE-RESISTANCE-RATED CORRIDOR AS |
| | REQUIRED BY SECTION 1016.1 SHALL BE |
| | PROVIDED WITH AN ELEVATOR LOBBY AT EACH |
| | FLOOR CONTAINING SUCH A CORRIDOR. THE |
| | LOBBY SHALL SEPARATE THE ELEVATORS FROM |
| | THE CORRIDOR BY FIRE PARTITIONS AND THE |
| | REQUIRED OPENING PROTECTION. ELEVATOR |
| | LOBBIES SHALL HAVE AT LEAST ONE MEANS OF |
| | EGRESS COMPLYING WITH CHAPTER 10 AND |
| | OTHER PROVISIONS WITHIN THIS CODE. |
| | |
| | 37) PRODUCT APPROVALS: |
| | 37A) KAWNEER DOORS A10.16, FL 629 |
| | NOA 04-0123.02, PLEASE HIGHLIGHT WHICH |
| | GLAZING SYSTEM IS TO BE USED. |
| | |
| | 37B) STANLEY AUTO DOOR A10.18, FL 3627 |
| | REPORT NOT FOUND ON THE STATE WEBSITE |
| | FBC 2004.FOUND FL 5503 & 6249. |
| | |
| | 37C)SENTRY GLASS (R) & SAF-GLAS POLY |
| | CARBONATE 11/32" METRO-DADE NOA NO FL |
| | LISTING, NEEDS TO BE A TESTED ASSEMBLY |
| | TAS 201 (LARGE MISSLE). |
| | |
| | 37D) A10.36 BERRIDGE MANUFACTURING |
| | REPORT SUBMITTED IS FL 489/ 2001 PLANS |
| | ARE FILED UNDER FBC 2004.SEE NEW |
| | LISTINGS. HIGHLIGHT SYSTEMS USED. |
| | |
| | 37E) A10.48 PGT HORIZONTAL SLIDERS, |
| | FL 242-R1/ FBC 2001, PLANS FILED UNDER |
| | FBC 2004. |
| | |
| | 37F) A10.50 PGT FIXED WINDOWS, |
| | FL 243-R1/ FBC 2001, PLANS FILED UNDER |
| | FBC 2004. |
| | |
| | 37G) SIMPSON STRONG-TIE FL 474 2001 FBC, |
| | PLANS FILED UNDER FBC2004. |
| | |
| | 37H) JAMES HARDIE BOARD FL 889 2001 FBC |
| | |
| | 37I) FLAT ROOF NO REPORT SUBMITTED. |
| | HIGHLIGHT WHICH SUBSYSTEM TO BE USED. |
| | |
| | 37J) DRYVIT SYSTEMS, NO REPORT |
| | SUBMITTED.NOTE SEE SYSTEMS LIMITATIONS |
| | FOR HORIZONTAL USEAGE! |
| | |
| | 37K) TRUSS ANCHORS, NO REPORT SUBMITTED |
| | |
| | 37L) DENSEGLASS GOLD- NO REPORT |
| | SUBMITTED. |
| | |
| | 38) SHEET A-3.3 DETAIL #9 A5.5 AND |
| | DETAIL# 10 BOTH DEAL WITH THE PORTACO |
| | ROOF SHEATHING, WALL AND ROOF SHEATHING. |
| | THE PLANS ARE NOT CLEAR AS TO WHAT TYPE |
| | OF MATERIAL WILL BE USED. TABLE 601 FOR |
| | TYPE IB ROOF CONSTRUCTION FOOTNOTE "C" |
| | WILL NOT ALLOW FIRE RETARDANT TREATED |
| | WOOD SINCE THE BUILDING IS OVER (2) |
| | STORIES TALL. |
| | |
| | 39) SAME SHEET A5.5 DETAILS 2 & 3 DEAL |
| | WITH STEEL EXTERIOR FRAMING, WHERE AS |
| | S-2.01 INDICATES THE USE OF BLOCK.PLEASE |
| | PROVIDE MORE INFORMATION. |
| | |
| | 40) A5.5 PLAN OF PORTACO INDICATES THE |
| | USE OF STEEL C BEAMS FOR ROOF FRAMING |
| | MEMBERS.S2.02 DETAIL "B" INDICATES A 2X |
| | PLATE, (SEE 38) AND SIMPSON TRUSS |
| | ANCHORS. PLANS DO NOT PROVIDE THE |
| | VERTICAL, HORIZONTAL OR GRAVITY LOADS TO |
| | BE RESISTED. NOR WHAT TYPE OF FASTENER |
| | TOBE USED FOR ANCHORS. |
| | |
| | 41) A5.6 PLANS INDICATE TO SEE |
| | STRUCTURAL PLANS FOR FRAMING OF PORTACO, |
| | WHERE? |
| | |
| | 42) A5.6 PLANS INDICATE THE USE OF 5/8" |
| | PLYWOOD SHEATHING, SEE COMMENT38 TYPE IB |
| | BUILDING. |
| | |
| | 43) TYPE IB BUILDING TABLE 601 REQUIRES |
| | VARIOUS FIRE RATINGS DEPENDING ON THE |
| | STRUCTURAL ELEMENT, PROVIDE INFORMATION |
| | ON CODE COMPLIANCE? |
| | |
| | 44) A5.5 & A5.6 BOTH SHOW DETAILS OF |
| | FOAM TRIM, 1406.2.2ARCHITECTURAL TRIM |
| | THAT EXCEEDS 40 FEET (12 192 MM) IN |
| | HEIGHT ABOVE GRADE PLANE SHALL BE |
| | CONSTRUCTED OF APPROVED NONCOMBUSTIBLE |
| | MATERIALS AND SHALL BE SECURED TO THE |
| | WALL WITH METAL OR OTHER APPROVED |
| | NONCOMBUSTIBLE BRACKETS. |
| | |
| | 45) A6.2 DETAIL# 4 STAIR HANDRAIL |
| | MISSING EXTENTION AT THE BOTTOM OF |
| | STAIR.1009.11.5 HANDRAIL EXTENSIONS. |
| | HANDRAILS SHALL RETURN TO A WALL, GUARD |
| | OR THE WALKING SURFACE OR SHALL BE |
| | CONTINUOUS TO THE HANDRAIL OF AN |
| | ADJACENT STAIR FLIGHT. WHERE HANDRAILS |
| | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE |
| | HANDRAILS SHALL EXTEND HORIZONTALLY AT |
| | LEAST 12 INCHES (305 MM) BEYOND THE TOP |
| | RISER AND CONTINUE TO SLOPE FOR THE |
| | DEPTH OF ONE TREAD BEYOND THE BOTTOM |
| | RISER. |
| | |
| | 46) HANDRAIL DISCREPANCY, A6.2DETAIL # 5 |
| | INDICATES A ROUND HANDRAIL WHERE AS |
| | DETAIL# 1 INDICATES USE OF A 1 1/2" SQ |
| | ALUM TUBE.1009.11.3 HANDRAIL |
| | GRASPABILITY. |
| | HANDRAILS WITH A CIRCULAR CROSS SECTION |
| | SHALL HAVE AN OUTSIDE DIAMETER OF AT |
| | LEAST 1.25 INCHES (32 MM) AND NOT |
| | GREATER THAN 2 INCHES (51 MM) OR SHALL |
| | PROVIDE EQUIVALENT GRASPABILITY. IF THE |
| | HANDRAIL IS NOT CIRCULAR, IT SHALL HAVE |
| | A PERIMETER DIMENSION OF AT LEAST 4 |
| | INCHES (102 MM) AND NOT GREATER THAN |
| | 6.25 INCHES (160 MM) WITH A MAXIMUM |
| | CROSS-SECTION DIMENSION OF 2.25 INCHES |
| | (57 MM). EDGES SHALL HAVE A MINIMUM |
| | RADIUS OF 0.01 INCH (0.25 MM). |
| | |
| | 47) A6.4 WINDOW DETAILS INDICATE BEING |
| | FLUSH WITH THE EXTERIOR. WITH THE EFIS |
| | FINISH THE ANCHORING SCREWS OR TAPCONS |
| | ARE NOT ATTACHING TO ANY FRAMING? |
| | |
| | 48) SHEET A-6.5.3 PLANS DO NOT SPECIFY |
| | THE TYPE OF MATERIAL VARIOUS COMPONENTS |
| | OF TRIM ARE MADE OF.FOAM PLASTICS THAT |
| | ARE USED AS INTERIOR FINISH SHALL ALSO |
| | MEET THE FLAME SPREAD INDEX REQUIREMENTS |
| | FOR INTERIOR FINISH IN ACCORDANCE WITH |
| | CHAPTER 8 . FOAM PLASTICS INSTALLED AS |
| | INTERIOR TRIM SHALL COMPLY WITH SECTION |
| | 2604.2 . |
| | |
| | 2604.2 INTERIOR TRIM. |
| | FOAM PLASTIC USED AS INTERIOR TRIM SHALL |
| | COMPLY WITH SECTIONS 2604.2.1 THROUGH |
| | 2604.2.4 . |
| | |
| | 2604.2.1 DENSITY. |
| | THE MINIMUM DENSITY OF THE INTERIOR TRIM |
| | SHALL BE 20 PCF (320 KG/M 3 ). |
| | |
| | 2604.2.2 THICKNESS. |
| | THE MAXIMUM THICKNESS OF THE INTERIOR |
| | TRIM SHALL BE 0.5 INCH (12.7 MM) AND THE |
| | MAXIMUM WIDTH SHALL BE 8 INCHES (204 |
| | MM). |
| | |
| | 2604.2.3 AREA LIMITATION. |
| | THE INTERIOR TRIM SHALL NOT CONSTITUTE |
| | MORE THAN 10 PERCENT OF THE AGGREGATE |
| | WALL AND CEILING AREA OF ANY ROOM OR |
| | SPACE. |
| | |
| | 2604.2.4 FLAME SPREAD. |
| | THE FLAME SPREAD INDEX SHALL NOT EXCEED |
| | 75 WHERE TESTED IN ACCORDANCE WITH ASTM |
| | E 84. THE SMOKE-DEVELOPED INDEX SHALL |
| | NOT BE LIMITED. |
| | |
| | 49) A-6.5.6 DETAIL# 11 DEALS WITH THE |
| | INSWING RESTROOM DOORS VS FIXTURE CLEAR |
| | FLOOR SPACE. 11-4.19.3 CLEAR FLOOR |
| | SPACE. |
| | A CLEAR FLOOR SPACE 30 INCHES BY 48 |
| | INCHES (760 MM BY 1219 MM) COMPLYING |
| | WITH SECTION 11-4.2.4 SHALL BE PROVIDED |
| | IN FRONT OF A LAVATORY TO ALLOW FORWARD |
| | APPROACH. SUCH CLEAR FLOOR SPACE SHALL |
| | ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE |
| | AND SHALL EXTEND A MAXIMUM OF 19 INCHES |
| | (485 MM) UNDERNEATH THE LAVATORY (SEE |
| | FIGURE 11-32 ). INDICATE A 30"X48" CLEAR |
| | FLOOR SPACE FOR THE LAV.11-4.22.2 DOORS. |
| | |
| | (1)ALL DOORS TO ACCESSIBLE TOILET |
| | ROOMS SHALL COMPLY WITH SECTION 11-4.13 |
| | . DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | |
| | 50) S-0.01DESIGN CRITERIA WRONG EDITION |
| | OF THE FBC. |
| | |
| | 51) S-0.01 WIND LOAD DOES NOT PROVIDE TO |
| | WHICH EDITION OF ASCE-7 THIS BUILDING |
| | WAS DESIGNED TOO? |
| | |
| | 52) S-0.02 WIND DESIGN AGAIN THE WRONG |
| | CODE EDITION, THE WRONG EDITION OF |
| | ASCE-7 AND THE WRONG WIND SPEED, SHOULD |
| | BE 140 MPH ,3 SECOND GUST. |
| | |
| | 53) S-0.02 OPENING FASTENING CHART |
| | INDICATES A 130MPH THIS IS A CONVERSION |
| | FROM 110 MPH FASTEST MILE EQUALS 130MPH |
| | 3 SECOND GUST. PLEASE INDICATE TO WHICH |
| | METHOD OF TESTING THIS CHART IS IN |
| | REFRENCE TOO. |
| | |
| | 54) S-0.03 ROOF END ZONES, THE |
| | ILLUSTRATON OF THE ROOF IS THE TYPICAL |
| | SQUARE BOX TAKEN FROM ASCE7-02. PLEASE |
| | PROVIDE AN ACCURATE DRAWING OF THE |
| | MULTIPLE END ZONES THAT WILL CONFORM TO |
| | THIS STRUCTURE. |
| | |
| | 55) PORTE COCHERE THE T.A.= 50 PLEASE |
| | REVISIT THIS CALCULATION IF THE LEAST |
| | DIMENSION OF THE PORT COCHERE IS 30' |
| | WOULD THE END ZONES BE A TRIBUTARY AREA |
| | OF 10' NOT 50'? |
| | |
| | 56) S-1.01 THE ELEVATOR FOUNDATION IS |
| | NOT SHOWN ON THE FOUNDATION SCHEDULE. |
| | THERE IS A DETAIL A/ S202 WHICH PROVIDES |
| | THE WIDTH BUT NOT THE LENGHT OF THE |
| | FOUNDATION. PLEASE PROVIDE. |
| | |
| | 57) S-2.03 POOL MECHANICAL ROOM, PART OF |
| | THIS PERMIT? INDICATE ON APPLICATION AS |
| | IF ANY OTHER BUILDINGS? |
| | |
| | 58) S-2.03 POOL MECHANICAL BUILDING |
| | THERE IS NO INFORMATION AS TO DESIGN? |
| | |
| | 59) S-2.03 POOL MECH BUILDING, PLAN |
| | INDICATES ROOF FRAMING MEMBERS 2X4, WHAT |
| | TYPE OF MATERIAL? SPACING? DECK? LOADS |
| | TO BE IMPOSED? TYPE OF ROOFING |
| | ASSEMBLIES? |
| | |
| | 60) ELEVATOR VENTS: |
| | 3004.2 LOCATION OF VENTS. |
| | VENTS SHALL BE LOCATED BELOW THE FLOOR |
| | OR FLOORS AT THE TOP OF THE HOISTWAY, |
| | AND SHALL OPEN EITHER DIRECTLY TO THE |
| | OUTER AIR OR THROUGH NONCOMBUSTIBLE |
| | DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE |
| | DUCTS SHALL BE PERMITTED TO PASS THROUGH |
| | THE ELEVATOR MACHINE ROOM PROVIDED THAT |
| | PORTIONS OF THE DUCTS LOCATED OUTSIDE |
| | THE HOISTWAY OR MACHINE ROOM ARE |
| | ENCLOSED BY CONSTRUCTION HAVING NOT LESS |
| | THAN THE FIRE PROTECTION RATING REQUIRED |
| | FOR THE HOISTWAY. HOLES IN THE MACHINE |
| | ROOM FLOORS FOR THE PASSAGE OF ROPES, |
| | CABLES OR OTHER MOVING ELEVATOR |
| | EQUIPMENT SHALL BE LIMITED SO AS NOT TO |
| | PROVIDE GREATER THAN 2 INCHES (51 MM) OF |
| | CLEARANCE ON ALL SIDES. |
| | |
| | 3004.3 AREA OF VENTS. |
| | EXCEPT AS PROVIDED FOR IN SECTION |
| | 3004.3.1 , THE AREA OF THE VENTS SHALL |
| | NOT BE LESS THAN 3? PERCENT OF THE AREA |
| | OF THE HOISTWAY NOR LESS THAN 3 SQUARE |
| | FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR, |
| | AND NOT LESS THAN 3? PERCENT NOR LESS |
| | THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR |
| | EACH DUMBWAITER CAR IN THE HOISTWAY, |
| | WHICHEVER IS GREATER. OF THE TOTAL |
| | REQUIRED VENT AREA, NOT LESS THAN |
| | ONE-THIRD SHALL BE OF THE PERMANENTLY |
| | OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON |
| | DETECTION OF SMOKE FROM ANY OF THE |
| | ELEVATOR LOBBY SMOKE DETECTORS. |
| | |
| | 61)3006.5 SHUNT TRIP. |
| | WHERE ELEVATOR HOISTWAYS OR ELEVATOR |
| | MACHINE ROOMS CONTAINING ELEVATOR |
| | CONTROL EQUIPMENT ARE PROTECTED WITH |
| | AUTOMATIC SPRINKLERS, A MEANS INSTALLED |
| | IN ACCORDANCE WITH NFPA 72, SECTION |
| | 3?9.4, ELEVATOR SHUTDOWN, SHALL BE |
| | PROVIDED TO DISCONNECT AUTOMATICALLY THE |
| | MAIN LINE POWER SUPPLY TO THE AFFECTED |
| | ELEVATOR PRIOR TO THE APPLICATION OF |
| | WATER. THIS MEANS SHALL NOT BE |
| | SELF-RESETTING. THE ACTIVATION OF |
| | SPRINKLERS OUTSIDE THE HOISTWAY OR |
| | MACHINE ROOM SHALL NOT DISCONNECT THE |
| | MAIN LINE POWER SUPPLY. |
| | |
| | 62) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |