| 2006-06-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FIRST REVIEW THIS PERMIT NUMBER |
| | |
| | PLANS FIRST REVIEWED UNDER THE PERMIT |
| | NUMBER 05040948. COMMENT NUMBERS FROM |
| | FIRST REVIEW WILL REMAIN THE SAME. FROM |
| | PREVIOUS REVIEW: |
| | |
| | 1. PLANS SHALL BE ROUTED TO DBPR HOTEL & |
| | RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY WPB FOR REVIEW. |
| | SUBMIT A MINIMUM OF 3 SETS OF PLANS |
| | STAMPED BY DBPR WITH THE TWO PAGE "WORK |
| | SHEETS" ATTACHED TO EACH SET. SECTION |
| | 101.4.7. |
| | ***PLANS NOT STAMPED AND "WORK SHEETS" |
| | NOT ATTACHED. FBC-2004 SECTION 102.2.1. |
| | |
| | 5. SHTS A-2.01 & A-2.02 TOILET ROOMS. |
| | SHOW CLEAR FLOOR SPACE FOR EACH |
| | ACCESSIBLE FIXTURE. SHOW TURNING AREA IN |
| | EACH TOILET ROOM. NOT REQUIRED IN STALL. |
| | SECTION 11-4.22.3 |
| | ***RESPONSE NOTED, BUT CLEAR FLOOR SPACE |
| | FOR W/C'S ARE NOT SHOWN ON SHT A-2.01, |
| | AND NOT SHOWN FOR W/C AND LAV ROOM 138 |
| | SHT A-2.02. - THE W/C'S OR LAV VANITY |
| | CAN NOT BE IN THE TURNING AREA IN THE |
| | TOILET ROOMS. THE TURNING AREA SHALL BE |
| | UNOBSTRUCTED. FBC-2004 SECTION |
| | 11-4.22.3. |
| | |
| | 6. SHTS A-2.01 & A-2.02 SUBMIT |
| | CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1103.1 & 403.1 FOR ALL COMMON |
| | AREAS. SHOW THE SQUARE FOOTAGE OF EACH |
| | COMMON AREA ON THE FLOOR PLAN. |
| | ***RESPONSE NOTED, BUT NO CALCULATIONS |
| | FOR MINIMUM FACILITIES SHOWN. NOT ALL |
| | COMMON USE AREAS SHOW SQUARE FOOTAGE. |
| | SEE ALL OCCUPANCIES FIRST FLOOR |
| | INCLUDING BUSINESS, KITCHEN, LIBRARY, |
| | E-SPACE, EMPLOYEE BREAK ROOM, |
| | HOUSEKEEPING LAUNDRY, GREAT ROOM, |
| | NETWORK ROOM, MANAGERS OFFICE, |
| | ADMINISTRATION, SALES OFFICE, |
| | REGISTRATION, SUITE SHOP, BUFFET, |
| | PANTRY, ETC. ALL AREAS ALL OCCUPANCY. |
| | FBC-2004 TABLES 1004.1.2 & 403.1. |
| | |
| | 7. SHT A-2.02 SINK IN EMPLOYEE BREAK |
| | ROOM SHALL COMPLY WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. (FORWARD APPROACH |
| | REQUIRED MAXIMUM 19" UNDERNEATH THE |
| | SINK. SINK SHALL BE CENTERED ON THE 30" |
| | WIDTH OF THE CLEAR FLOOR SPACE). |
| | ***RESPONSED NOTED, BUT THE FOLLOWING |
| | INFORMATION REQUIRED: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | D. 11-4.24.7 FAUCETS |
| | DETAILS 11/A-8.04 & 11A/A-8.04 ARE |
| | LAVATORY DETAILS. - FLOOR PLAN A-2.02 |
| | INDICATES EMPLOYEE BREAK ROOM, WHERE AS |
| | DETAIL 7/A-8.04 INDICATES AN EMPLOYEE |
| | KITCHEN. PLEASE CORRELATE FLOOR PLAN AND |
| | DETAILS. FBC-2004 SECTIONS 106.1.1 & |
| | 11-4.24. |
| | |
| | 9.SHTS A-2.10 & A-2.11 SEE COMMENT #5 |
| | CONCERNING TURNING AREA. |
| | ***RESPONSE NOTED, BUT THE TURNING AREA |
| | IS NOT SHOWN IN SOME ACCESSIBLE UNITS. |
| | SEE DETAIL 06/A-2.10. - W/C AND LAV |
| | VANITY SHOWN IN THE TURNING AREA IN |
| | SPECIAL STUDIO ACC. 05/A-2.10 |
| | |
| | 14. SHTS P-3.01, P-3.02, P-3.03 SANT. |
| | RISER DIAGRAMS, TUBS AND SHOWERS REQUIRE |
| | A TRAP. SECTION 1002.1. - RISER DIAGRAMS |
| | DO NOT REFLECT THE FLOOR PLANS. PLEASE |
| | SUBMIT RISER DIAGRAMS IN AN ISOMETRIC |
| | FORM THAT REFLECT THE FLOR PLAN, AND |
| | MEET CODE REQUIREMENTS. SHOW ALL PIPE |
| | SIZES, VENTS AND DFU FOR EACH RISER. |
| | SECTION 104.2.1. |
| | ***RESPONSE NOTED, BUT RISER #7 SHOWS |
| | REVENTS CONNECTING TO THE SANITARY STACK |
| | AND NOT THE VENT STACK AS REQUIRED. - |
| | RISER #9 SHOWS REVENT CONNECTING TO |
| | SANT. STACKNOT THE VENT STACK ON THE |
| | 3RD FLOOR. - RISER #3 SINK DOES NOT |
| | REFLECT THE FLOOR PLAN 1ST FLOOR. (SEE |
| | FLOORS ABOVE). FBC-2004 106.1.1. - |
| | RECHECK RISER DFU'S PER TABLE 709.1. |
| | |
| | 15. SUBMIT A BUILDING DRAIN SANITARY |
| | ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM, AND |
| | SHOW RISERS LOCATIONS WITH RISER |
| | DESIGNATION NUMBERS. SECTION 104.2.1 & |
| | 104.3.1.1. |
| | ***RESPONSE NOTED, BUT PIPE SIZING FOR |
| | BUILDING NOT CORRECT IN SOME AREAS. |
| | TABLE 710.1. - W/C MISSING IN RISER |
| | SECTION FOR TOILET ROOMS 111, & 116. |
| | SECTION 106.3.5.1.3. - BUILDING SANT. |
| | DRAIN DOES NOT REFLECT THE FLOOR PLAN |
| | WHERE DRAIN EXITS THE BUILDING. SECTION |
| | 106.1.1. - BRANCH LINE TO MOP SINK DOES |
| | NOT REFLECT THE FLOOR PLAN WHERE IT |
| | CONNECTS TO THE BUILDING DRAIN, AND THE |
| | FLOOR SINK, FLOOR DRAIN, & TRENCH DRAIN |
| | ARE NOT ON THE RISER SECTION. SECTION |
| | 106.1.1. |
| | |
| | 18. SUBMIT A WATER RISER DIAGRAM IN |
| | ISOMETRIC FORM FOR THE WATER |
| | DISTRIBUTION SYSTEM SHOWING THE LOCATION |
| | OF THE WATER ENTERING THE BUILDING, ALL |
| | PIPING NOT SHOWN ON THE RISERS, ALL PIPE |
| | SIZES, WATER HAMMER ARRESTORS, LOCATION |
| | OF WATER RISERS CONNECTING TO THE |
| | DISTRIBUTION LINE WITH RISER DESIGNATION |
| | NUMBERS ETC. SECTIONS 104.2.1 AND |
| | 104.3.1.1. |
| | ***RESPONSE NOTED, BUT MANY PIPE SIZES |
| | ARE NOT SHOWN, WATER HAMMER ARRESTORS |
| | FOR WB-1, (ALL THREE), ARE NOT SHOWN, |
| | WATER HAMMER ARRESTORS AT THE CLOTHS |
| | WASHERS SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE" NOT IN |
| | THE CEILING AS SHOWN, AND THE PIPING |
| | WHERE THE WATER MAIN ENTERS THE BUILDING |
| | AND THE MIXING VALVE, CIRCULATION PUMP, |
| | HOT WATER LINES, COLD WATER LINES SHALL |
| | REFLECT THE PIPING SCHEMATIC FOR THE |
| | WATER HEATERS ON SHT P-2.01. SECTIONS |
| | 106.1.1, 604.9, PDI-WH 201 & MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 20. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | ***RESPONSE NOTED, BUT PIPING TO |
| | GENERATOR NOT SHOWN ALONG WITH THE |
| | LENGTHS OF PIPE. FBC-2004 FUEL GAS CODE. |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | ***RESPONSE NOTED, BUT NO BTU'S SHOWN |
| | FOR THE GENERATOR, AND NOT ADDED TO THE |
| | TOTAL BTU LOAD OF THE SYSTEM. FBC-2004 |
| | FUEL GAS CODE 2004 SECS. 401.8 THRU |
| | 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | ***RESPONSE NOTED, BUT THE DISTANCE TO |
| | THE GENERATOR IS NOT SHOWN TO VERIFY |
| | MOST REMOTE DISTANCE IN SYSTEM. FBC-2004 |
| | FUEL GAS CODE APPENDIX-A USE OF CAPACITY |
| | TABLES A.3.1(4). |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. |
| | ***NO RESPONSE, NO MANUF. SHEETS FOUND. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SHT A-2.11 INDICATE HOW SECTION |
| | 11-9.1.4 IS BEING COMPLIED WITH WHEN NO |
| | ACCESSIBLE UNITS FOR 1 BEDROOM WITH A |
| | CONFERENCE ROOM ARE AVAILABLE. |
| | |
| | 2B. SHT A-2.01 SHOWS A HEAT N GLO GAS |
| | FIREPLACE THAT IS NOT SHOWN ON THE GAS |
| | RISER DIAGRAM. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 3B. SHT A-201 IN THE PANTRY A SINK TO |
| | THE LEFT OF THE THREE COMPARTMENT SINK |
| | IS NOT IDENTIFIED ON THE FOOD SERVICE |
| | EQUIPMENT SCHEDULE. - HAND SINK #9 |
| | DESIGNATION NUMBER NOT SHOWN AT SINK. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 4B. ALL ARCHITECTURAL SHEETS. |
| | CERTIFICATE OF AUTHROIZATION, (FIRM |
| | LICENSE), IS INDICATED AS "NULL & VOID" |
| | PER DBPR CERTIFICATION WEBSITE. |
| | |
| | 5B. PLUMBING & MECHANICAL SHEETS, |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME AND LICENSE NUMBER, AS WELL AS, THE |
| | NAME, ADDRESS, AND CERTIFICATE OF |
| | AUTHROIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. FAC |
| | 61G15-23.002(2) AND FS 471.025. |
| | |
| | 6B. SHT P-5.01 MECHANICAL & LAUNDRY ROOM |
| | WATER. THE WATER LINES FOR THE WATER |
| | HEATERS, CIRCULATION PUMP, MIXING VALVE, |
| | AND WATER PIPING AS IT ENTERS THE |
| | BUILDING SHALL REFLECT THE PIPING SHOWN |
| | ON SHT P-2.01 PIPING SCHEMATIC AT WATER |
| | HEATERS. PLEASE CORRELATE PIPING. |
| | SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |