Plan Review Notes For Permit 06040134
Permit Number 06040134
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-12 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FIRST REVIEW THIS PERMIT NUMBER
  
 PLANS FIRST REVIEWED UNDER THE PERMIT
 NUMBER 05040948. COMMENT NUMBERS FROM
 FIRST REVIEW WILL REMAIN THE SAME. FROM
 PREVIOUS REVIEW:
  
 1. PLANS SHALL BE ROUTED TO DBPR HOTEL &
 RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW.
 SUBMIT A MINIMUM OF 3 SETS OF PLANS
 STAMPED BY DBPR WITH THE TWO PAGE "WORK
 SHEETS" ATTACHED TO EACH SET. SECTION
 101.4.7.
 ***PLANS NOT STAMPED AND "WORK SHEETS"
 NOT ATTACHED. FBC-2004 SECTION 102.2.1.
  
 5. SHTS A-2.01 & A-2.02 TOILET ROOMS.
 SHOW CLEAR FLOOR SPACE FOR EACH
 ACCESSIBLE FIXTURE. SHOW TURNING AREA IN
 EACH TOILET ROOM. NOT REQUIRED IN STALL.
 SECTION 11-4.22.3
 ***RESPONSE NOTED, BUT CLEAR FLOOR SPACE
 FOR W/C'S ARE NOT SHOWN ON SHT A-2.01,
 AND NOT SHOWN FOR W/C AND LAV ROOM 138
 SHT A-2.02. - THE W/C'S OR LAV VANITY
 CAN NOT BE IN THE TURNING AREA IN THE
 TOILET ROOMS. THE TURNING AREA SHALL BE
 UNOBSTRUCTED. FBC-2004 SECTION
 11-4.22.3.
  
 6. SHTS A-2.01 & A-2.02 SUBMIT
 CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1103.1 & 403.1 FOR ALL COMMON
 AREAS. SHOW THE SQUARE FOOTAGE OF EACH
 COMMON AREA ON THE FLOOR PLAN.
 ***RESPONSE NOTED, BUT NO CALCULATIONS
 FOR MINIMUM FACILITIES SHOWN. NOT ALL
 COMMON USE AREAS SHOW SQUARE FOOTAGE.
 SEE ALL OCCUPANCIES FIRST FLOOR
 INCLUDING BUSINESS, KITCHEN, LIBRARY,
 E-SPACE, EMPLOYEE BREAK ROOM,
 HOUSEKEEPING LAUNDRY, GREAT ROOM,
 NETWORK ROOM, MANAGERS OFFICE,
 ADMINISTRATION, SALES OFFICE,
 REGISTRATION, SUITE SHOP, BUFFET,
 PANTRY, ETC. ALL AREAS ALL OCCUPANCY.
 FBC-2004 TABLES 1004.1.2 & 403.1.
  
 7. SHT A-2.02 SINK IN EMPLOYEE BREAK
 ROOM SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. (FORWARD APPROACH
 REQUIRED MAXIMUM 19" UNDERNEATH THE
 SINK. SINK SHALL BE CENTERED ON THE 30"
 WIDTH OF THE CLEAR FLOOR SPACE).
 ***RESPONSED NOTED, BUT THE FOLLOWING
 INFORMATION REQUIRED:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 DETAILS 11/A-8.04 & 11A/A-8.04 ARE
 LAVATORY DETAILS. - FLOOR PLAN A-2.02
 INDICATES EMPLOYEE BREAK ROOM, WHERE AS
 DETAIL 7/A-8.04 INDICATES AN EMPLOYEE
 KITCHEN. PLEASE CORRELATE FLOOR PLAN AND
 DETAILS. FBC-2004 SECTIONS 106.1.1 &
 11-4.24.
  
 9.SHTS A-2.10 & A-2.11 SEE COMMENT #5
 CONCERNING TURNING AREA.
 ***RESPONSE NOTED, BUT THE TURNING AREA
 IS NOT SHOWN IN SOME ACCESSIBLE UNITS.
 SEE DETAIL 06/A-2.10. - W/C AND LAV
 VANITY SHOWN IN THE TURNING AREA IN
 SPECIAL STUDIO ACC. 05/A-2.10
  
 14. SHTS P-3.01, P-3.02, P-3.03 SANT.
 RISER DIAGRAMS, TUBS AND SHOWERS REQUIRE
 A TRAP. SECTION 1002.1. - RISER DIAGRAMS
 DO NOT REFLECT THE FLOOR PLANS. PLEASE
 SUBMIT RISER DIAGRAMS IN AN ISOMETRIC
 FORM THAT REFLECT THE FLOR PLAN, AND
 MEET CODE REQUIREMENTS. SHOW ALL PIPE
 SIZES, VENTS AND DFU FOR EACH RISER.
 SECTION 104.2.1.
 ***RESPONSE NOTED, BUT RISER #7 SHOWS
 REVENTS CONNECTING TO THE SANITARY STACK
 AND NOT THE VENT STACK AS REQUIRED. -
 RISER #9 SHOWS REVENT CONNECTING TO
 SANT. STACKNOT THE VENT STACK ON THE
 3RD FLOOR. - RISER #3 SINK DOES NOT
 REFLECT THE FLOOR PLAN 1ST FLOOR. (SEE
 FLOORS ABOVE). FBC-2004 106.1.1. -
 RECHECK RISER DFU'S PER TABLE 709.1.
  
 15. SUBMIT A BUILDING DRAIN SANITARY
 ISOMETRIC SHOWING ALL PIPE SIZES, DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM, AND
 SHOW RISERS LOCATIONS WITH RISER
 DESIGNATION NUMBERS. SECTION 104.2.1 &
 104.3.1.1.
 ***RESPONSE NOTED, BUT PIPE SIZING FOR
 BUILDING NOT CORRECT IN SOME AREAS.
 TABLE 710.1. - W/C MISSING IN RISER
 SECTION FOR TOILET ROOMS 111, & 116.
 SECTION 106.3.5.1.3. - BUILDING SANT.
 DRAIN DOES NOT REFLECT THE FLOOR PLAN
 WHERE DRAIN EXITS THE BUILDING. SECTION
 106.1.1. - BRANCH LINE TO MOP SINK DOES
 NOT REFLECT THE FLOOR PLAN WHERE IT
 CONNECTS TO THE BUILDING DRAIN, AND THE
 FLOOR SINK, FLOOR DRAIN, & TRENCH DRAIN
 ARE NOT ON THE RISER SECTION. SECTION
 106.1.1.
  
 18. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM FOR THE WATER
 DISTRIBUTION SYSTEM SHOWING THE LOCATION
 OF THE WATER ENTERING THE BUILDING, ALL
 PIPING NOT SHOWN ON THE RISERS, ALL PIPE
 SIZES, WATER HAMMER ARRESTORS, LOCATION
 OF WATER RISERS CONNECTING TO THE
 DISTRIBUTION LINE WITH RISER DESIGNATION
 NUMBERS ETC. SECTIONS 104.2.1 AND
 104.3.1.1.
 ***RESPONSE NOTED, BUT MANY PIPE SIZES
 ARE NOT SHOWN, WATER HAMMER ARRESTORS
 FOR WB-1, (ALL THREE), ARE NOT SHOWN,
 WATER HAMMER ARRESTORS AT THE CLOTHS
 WASHERS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN, AND THE PIPING
 WHERE THE WATER MAIN ENTERS THE BUILDING
 AND THE MIXING VALVE, CIRCULATION PUMP,
 HOT WATER LINES, COLD WATER LINES SHALL
 REFLECT THE PIPING SCHEMATIC FOR THE
 WATER HEATERS ON SHT P-2.01. SECTIONS
 106.1.1, 604.9, PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
  
 20. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 ***RESPONSE NOTED, BUT PIPING TO
 GENERATOR NOT SHOWN ALONG WITH THE
 LENGTHS OF PIPE. FBC-2004 FUEL GAS CODE.
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 ***RESPONSE NOTED, BUT NO BTU'S SHOWN
 FOR THE GENERATOR, AND NOT ADDED TO THE
 TOTAL BTU LOAD OF THE SYSTEM. FBC-2004
 FUEL GAS CODE 2004 SECS. 401.8 THRU
 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 ***RESPONSE NOTED, BUT THE DISTANCE TO
 THE GENERATOR IS NOT SHOWN TO VERIFY
 MOST REMOTE DISTANCE IN SYSTEM. FBC-2004
 FUEL GAS CODE APPENDIX-A USE OF CAPACITY
 TABLES A.3.1(4).
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE, NO MANUF. SHEETS FOUND.
  
 **************NEW COMMENTS**************
  
 1B. SHT A-2.11 INDICATE HOW SECTION
 11-9.1.4 IS BEING COMPLIED WITH WHEN NO
 ACCESSIBLE UNITS FOR 1 BEDROOM WITH A
 CONFERENCE ROOM ARE AVAILABLE.
  
 2B. SHT A-2.01 SHOWS A HEAT N GLO GAS
 FIREPLACE THAT IS NOT SHOWN ON THE GAS
 RISER DIAGRAM. PLEASE CLARIFY. SECTION
 106.1.1.
  
 3B. SHT A-201 IN THE PANTRY A SINK TO
 THE LEFT OF THE THREE COMPARTMENT SINK
 IS NOT IDENTIFIED ON THE FOOD SERVICE
 EQUIPMENT SCHEDULE. - HAND SINK #9
 DESIGNATION NUMBER NOT SHOWN AT SINK.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 4B. ALL ARCHITECTURAL SHEETS.
 CERTIFICATE OF AUTHROIZATION, (FIRM
 LICENSE), IS INDICATED AS "NULL & VOID"
 PER DBPR CERTIFICATION WEBSITE.
  
 5B. PLUMBING & MECHANICAL SHEETS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF
 AUTHROIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) AND FS 471.025.
  
 6B. SHT P-5.01 MECHANICAL & LAUNDRY ROOM
 WATER. THE WATER LINES FOR THE WATER
 HEATERS, CIRCULATION PUMP, MIXING VALVE,
 AND WATER PIPING AS IT ENTERS THE
 BUILDING SHALL REFLECT THE PIPING SHOWN
 ON SHT P-2.01 PIPING SCHEMATIC AT WATER
 HEATERS. PLEASE CORRELATE PIPING.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  