Plan Review Notes
Plan Review Notes For Permit 06040134
Permit Number 06040134
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-16 00:00:001. SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
 2. THE SITE PLAN ILLUSTRATING ALL NEW
 AND EXISTING FIRE HYDRANTS USED TO
 SERVICE THE NEW CONSTRUCTION AREA
 APPEARS TO BE CONFUSING. PLEASE EXPLAIN.
  
 3. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS.
  
 4. THE NEW FIRE ALARM SYSTEM SHALL BE
 MONITORED BY A UL LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 5. BACKFLOW PREVENTION DEVICES ARE NOT
 SHOWN WITH TAMPER SWITCHES, CHAINS OR
 LOCKS ON THE FIRE PROTECTION DRAWINGS.
 THE ELECTRICAL DRAWINGS CONFLICT WITH
 THE FIRE PROTECTION DRAWINGS.
  
 6. THE FIRE ALARM PANEL APPEARS TO BE
 SHOWN IN TWO DIFFERENT LOCATIONS ON THE
 ELECTRICAL AND THE FIRE ALARM DRAWINGS.
 PLEASE CORRECT.
  
 7. EMERGENCY INSTRUCTIONS TO OCCUPANTS
 SHALL BE PROVIDED IN EACH GUEST ROOM.
  
 8. NO UNAUTHORIZED ELECTRIC, MECHANICAL,
 OR PLUMBING PERMITTED TO BE INSTALLED
 WITHIN THE EXIT STAIRWELLS UNLESS
 ALLOWED BY BUILDING AND FIRE CODES.
  
 9. TACTILE SIGNAGE ALTHOUGH BY OTHERS
 MUST BE NOTED ON THE PLANS TO ENSURE
 THAT THE REQUIREMENT IS MET.
  
 10. ALL SMOKE DETECTORS SHALL BE A
 MINIMUM OF AT LEAST THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
  
 11. ALL PROPOSED FIRE DAMPERS AFTER
 INSTALLATION SHALL BE TESTED TO ESNURE
 PROPER FUNCTION.
  
 12. ALL FIRE AND LIFE SAFETY SYSTEM
 SHALL BE INSPECTED, TESTED, AND APPROVED
 PRIOR TO ANY OCCUPANCY BEING ALLOWED.
  
 13. ELEVATOR WARNING SIGNS ARE REQUIRED
 AT ELEVATOR LOCATIONS.
  
 14. BUILDING ADDRESS REQUIRED.
  
 15. NO EXIT SIGNS APPEAR TO BE NEEDED ON
 THE MAID AND MECHANICAL ROOMS LOCATED
 ADJACENT TO THE EXIT STAIR DOORS. PLEASE
 SEE SECTION 7.10.8.3.1 OF NFPA 101, THE
 LIFE SAFETY CODE REGARDING THIS MATTER.
  
 16. THE COVERED ENTRY BASED ON SOME
 INFORMATION WILL BE EXPECTED TO BE FIRE
 SPRINKLER PROTECTED SINCE ALL OR SOME
 PORTIONS WILL BE COMSBUTIBLE.
  
 17. PLEASE INDICATE EMERGENCY
 INSTRUCTION LOCATIONS FOR THE COMMON
 AREAS OF THE BUILDING.
  
 18. THE INSTALLATION OF ANY SOFFITS
 SHALL NOT INTERFERE WITH THE OPERATION
 OF ANY REQUIRED FIRE SPRINKLER HEADS.
  
 19. DOORS FOR STAIRWELLS INDICATES 60
 MINUTES IN SOME LOCALES. PLEASE REVISE
 TO INDICATE 90 MINUTE DOORS EQUIPPED
 WITH SELF-CLOSING DEVICES.
  
 20. ALL REQUIRED RATED FIRE DOORS SHALL
 BE EQUIPPED WITH LABELS SPECIFYING THE
 FIRE RATING.
  
 21. PLEASE ILLUSTRATE ON THE PLANS THAT
 THE PROPOSED FIREPLACE MEETS APPLICABLE
 FIRE CODE REQUIREMENTS.
  
 22. STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION WHILE THE BUILDING IS BEING
 CONSTRUCTED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709
  