| Date |
Text |
| 2006-06-16 00:00:00 | 1. SUITABLE ROADS ARE TO BE PROVIDED |
| | DURING CONSTRUCTION FOR FIRE AND |
| | PARAMEDICAL EQUIPMENT. |
| | |
| | 2. THE SITE PLAN ILLUSTRATING ALL NEW |
| | AND EXISTING FIRE HYDRANTS USED TO |
| | SERVICE THE NEW CONSTRUCTION AREA |
| | APPEARS TO BE CONFUSING. PLEASE EXPLAIN. |
| | |
| | 3. SEPERATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS. |
| | |
| | 4. THE NEW FIRE ALARM SYSTEM SHALL BE |
| | MONITORED BY A UL LISTED CENTRAL STATION |
| | APPROVED FOR CENTRAL STATION SERVICE. |
| | |
| | 5. BACKFLOW PREVENTION DEVICES ARE NOT |
| | SHOWN WITH TAMPER SWITCHES, CHAINS OR |
| | LOCKS ON THE FIRE PROTECTION DRAWINGS. |
| | THE ELECTRICAL DRAWINGS CONFLICT WITH |
| | THE FIRE PROTECTION DRAWINGS. |
| | |
| | 6. THE FIRE ALARM PANEL APPEARS TO BE |
| | SHOWN IN TWO DIFFERENT LOCATIONS ON THE |
| | ELECTRICAL AND THE FIRE ALARM DRAWINGS. |
| | PLEASE CORRECT. |
| | |
| | 7. EMERGENCY INSTRUCTIONS TO OCCUPANTS |
| | SHALL BE PROVIDED IN EACH GUEST ROOM. |
| | |
| | 8. NO UNAUTHORIZED ELECTRIC, MECHANICAL, |
| | OR PLUMBING PERMITTED TO BE INSTALLED |
| | WITHIN THE EXIT STAIRWELLS UNLESS |
| | ALLOWED BY BUILDING AND FIRE CODES. |
| | |
| | 9. TACTILE SIGNAGE ALTHOUGH BY OTHERS |
| | MUST BE NOTED ON THE PLANS TO ENSURE |
| | THAT THE REQUIREMENT IS MET. |
| | |
| | 10. ALL SMOKE DETECTORS SHALL BE A |
| | MINIMUM OF AT LEAST THREE FEET FROM AIR |
| | CONDITIONER DIFFUSERS. |
| | |
| | 11. ALL PROPOSED FIRE DAMPERS AFTER |
| | INSTALLATION SHALL BE TESTED TO ESNURE |
| | PROPER FUNCTION. |
| | |
| | 12. ALL FIRE AND LIFE SAFETY SYSTEM |
| | SHALL BE INSPECTED, TESTED, AND APPROVED |
| | PRIOR TO ANY OCCUPANCY BEING ALLOWED. |
| | |
| | 13. ELEVATOR WARNING SIGNS ARE REQUIRED |
| | AT ELEVATOR LOCATIONS. |
| | |
| | 14. BUILDING ADDRESS REQUIRED. |
| | |
| | 15. NO EXIT SIGNS APPEAR TO BE NEEDED ON |
| | THE MAID AND MECHANICAL ROOMS LOCATED |
| | ADJACENT TO THE EXIT STAIR DOORS. PLEASE |
| | SEE SECTION 7.10.8.3.1 OF NFPA 101, THE |
| | LIFE SAFETY CODE REGARDING THIS MATTER. |
| | |
| | 16. THE COVERED ENTRY BASED ON SOME |
| | INFORMATION WILL BE EXPECTED TO BE FIRE |
| | SPRINKLER PROTECTED SINCE ALL OR SOME |
| | PORTIONS WILL BE COMSBUTIBLE. |
| | |
| | 17. PLEASE INDICATE EMERGENCY |
| | INSTRUCTION LOCATIONS FOR THE COMMON |
| | AREAS OF THE BUILDING. |
| | |
| | 18. THE INSTALLATION OF ANY SOFFITS |
| | SHALL NOT INTERFERE WITH THE OPERATION |
| | OF ANY REQUIRED FIRE SPRINKLER HEADS. |
| | |
| | 19. DOORS FOR STAIRWELLS INDICATES 60 |
| | MINUTES IN SOME LOCALES. PLEASE REVISE |
| | TO INDICATE 90 MINUTE DOORS EQUIPPED |
| | WITH SELF-CLOSING DEVICES. |
| | |
| | 20. ALL REQUIRED RATED FIRE DOORS SHALL |
| | BE EQUIPPED WITH LABELS SPECIFYING THE |
| | FIRE RATING. |
| | |
| | 21. PLEASE ILLUSTRATE ON THE PLANS THAT |
| | THE PROPOSED FIREPLACE MEETS APPLICABLE |
| | FIRE CODE REQUIREMENTS. |
| | |
| | 22. STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION WHILE THE BUILDING IS BEING |
| | CONSTRUCTED. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |
| | 804-4709 |
| | |