| 2006-05-14 00:00:00 | ******** UNSAT 2ND REVIEW ******* |
| | |
| | **STAYBRIDGE SUITES, FIRST REVIEW UNDER |
| | 2004 FBC. |
| | |
| | |
| | ** PLEASE KNOW, PLANS ORIGINALLY CAME IN |
| | UNDER THE 2001 FBC AND NOW PLANS ARE |
| | SUBMITTED UNDER THE 2004 FBC. PLEASE SEE |
| | MOST OF THE COMMENTS ARE NEW, HOWEVER |
| | SOME ARE FROM PREVIOUS REVIEW. |
| | |
| | ** PLEASE BE SURE TO COMPLETELY REMOVE |
| | ANY OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE ADDRESSING FOR |
| | PROJECT SHOULD BE ON TITLE BLOCK FOR |
| | LOCATION OF PROJECT. |
| | FAC61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE CLARIFY TITLE BLOCK ON |
| | COVER SHEETS AND ALL TRADE SHEETS, AS |
| | THESE STATE THE ELECTRICAL ENGINEER OF |
| | RECORD AS UNDER THE ARCHITECTURAL FIRM? |
| | PLEASE ALSO SEE STRUCTURAL, MECHANICAL |
| | AND PLUMBING SHEETS AS THESE DO NOT |
| | CONTAIN ANY TITLE BLOCKS FOR THE |
| | ENGINEERS OR ENGINEERIN FIRMS AS LISTED |
| | ON COVER SHEETS. |
| | ** PLEASE SEE A PRINT OUT FROM THE |
| | STATE'S WEBSITE IS NOW ATTACHED TO |
| | NOTES, AS THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER AS INDICATE ON |
| | TITLE BLOCKS FOR ARCHITECTURAL FIRM IS |
| | "NULL AND VOID" PER DEPARTMENT OF |
| | BUSINESS AND PROFESSIOAL REGULATION. |
| | PLEASE SEE ELECTRICAL SHEETS DO NOT |
| | INDICATE THIS AND LIST THE ENGINEER AS |
| | AN INDIVIDUAL? |
| | PLEASE SEE FAC 61G15-23.002, FS 471.023, |
| | IF ARCHITECTURAL FIRM IS OFFERING |
| | ENGIEERING SERVICES, PLEASE PROVIDE |
| | CERTIFICATE OF AUTHORIZATION FOR THIS. |
| | THE CA # WAS ADDED FOR ARCHITECTURAL |
| | FIRM AS REQUESTED ON PREVIOUS REVIEW |
| | HOWEVER AS NOTED ABOVE, SEEMS NOT BE |
| | ACTIVE. |
| | PLEASE SEE THE PRINTED NAME AND LICENSE |
| | NUMBER OF THE ARCHITECT IS ALSO REQUIRED |
| | ON TITLE BLOCKS FOR ALL SHEETS. |
| | FAC 61G1-16.004 |
| | ** PLEASE KNOW, THIS COMMENT IS FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE FP SHEETS, AS ONE |
| | SHEET IS A COPY OF SIGNED AND SEALED |
| | PLANS SUBMITTED. |
| | |
| | 4) NOTE: PLEASE KNOW, PLANS ARE NOW |
| | BEING SUBMITTED UNDER THE 2004 FBC, |
| | HOWEVER NO CHANGES IN ELECTRICAL DESIGN |
| | WERE MADE TO THE NEW 2004 CHAPTER 13. |
| | PLEASE SEE CHAPTER 13, 13-413.1ABC.1, |
| | PLEASE PROVIDE ALL WORST CASE CALCS, AND |
| | ADJUST AS NEEDED FOR LONGEST RUNS. |
| | PLEASE SEE 13-415.1.ABC.1.1, &.2, & .3 |
| | WHICH GREATLY AFFECT ELECTRICAL DESIGN. |
| | COULD NOT LOCATE ANY INFORMATION FOR |
| | THIS ON PLANS.? |
| | PLEASE SEE ALL OTHER CHANGES IN CHAPTER |
| | 13. FIXTURE TYPES, TANDEM WIRING ETC. |
| | |
| | 5)NOTE: PLEASE PROVIDE COMPLETE |
| | PHOTO-METRICS FOR ALL EGRESS |
| | AREAS/PATHS. |
| | PLEASE SEE NFPA-101 2003, 7.8.1.3, |
| | 7.9.2.2. PLEASE SEE STAIRS FOR EGRESS |
| | SHALL CONTAIN A MIN OF 10FT CANDLES AVG |
| | UNDER NORMAL CONDITIONS AND 1FT CANDLE |
| | AVG UNDER EM POWER. |
| | PLEASE SEE MIN REQUIRED FOR ALL OTHER |
| | PATHS SHALL BE 1FT CANDLE. |
| | PLEASE ALSO KNOW, AN EM BATTERY BACK UP |
| | FIXTURE OF SOME TYOE WILL BE REQUIRED IN |
| | THE MAIN ELECTRICAL ROOM. |
| | |
| | 6) NOTE: PLEASE SEE NO INFORMATION WAS |
| | SUBMITTED FOR THE FIRE PUMP, FIRE PUMP |
| | CONTROLLER. |
| | PLEASE KNOW, ALL PERMITS, PLANS AND |
| | INFORMATION FOR THIS SHALLBE |
| | SUBMITTED. PLANS NOW INDICATE A FIRE |
| | PUMP LOCATED IN A DETACHED BUIDLING |
| | WHICH WILL FEED TWO DIFFERENT HOTELS. |
| | PLEASE KNOW, APPROVAL BY THE FIRE |
| | MARSHAL'S OFFICE SHALL FIRST BE OBTAINED |
| | FOR THIS SCENERIO. PLEASE ALSO KNOW, |
| | PERMIT FOR EITHER BUILDING CAN NOT BE |
| | PASSED FOR PERMITING UNTIL ALL |
| | INFORMATION, PLANS ETC FOR FIRE PUMP, |
| | FIRE PUMP CONTROLLER CAN BE REVIEWED. IF |
| | ELECTRICAL DRIVEN FIRE PUMP, PLEASE |
| | PROVIDE ALL INFORMATION. |
| | PLEASE SEE FP SEEM TO INDICATE |
| | ELECTRICAL FIRE PUMP, BUT UNCLEAR AT |
| | THIS TIME. |
| | PLEASE SEE NFPA-20 2002. PLEASE SUBMIT |
| | ALL RELEVANT INFORMATION FOR FIRE PUMP |
| | CONTROLLER ETC. |
| | |
| | 7) NOTE: PLEASE SEE PLANS ARE NOW |
| | INDICATING A BACK UP GENERATOR OF SOME |
| | SORT? IF ANY PART OF THIS SYSTEM IS |
| | GOING TO BE INSTALLED, PLEASE SUBMIT ALL |
| | INFORMATION FOR ATS, GENERATOR, |
| | ELECTRICAL RISER, SUB BASE FUEL ETC. |
| | PLEASE SEE AN ATS IS BEING SHOWN ON |
| | PLANS AT THIS TIME, HOWEVER HOW THIS IS |
| | NOT BEING SHOWN WIRED INTO RISER? |
| | PLEASE KNOW, IF NO PART OF THIS SYSTEM |
| | IS GOING TO BE INSTALLED AT THIS TIME, |
| | PLEASE REMOVE FROM PLANS AS LONG AS ALL |
| | MIN LIFE SAFETY BACK UP SYSTEMS ARE |
| | PROVIDED BY OTHER MEANS. |
| | PLEASE SUBMIT ALL MANUFACTURE CUT |
| | SHEETS/SPEC FOR GEN, ATS'S, FIRE PUMP, |
| | FIRE PUMP CONTROLLER, AND ANY FUEL |
| | TANKS. |
| | |
| | 8) NOTE: PLEASE SEE PANEL "P" ON SHOWS |
| | MCB AS REQUIRED, YET PANEL SCHEDULE |
| | SHOWS THIS PANEL AS "MLO". PLEASE KNOW, |
| | THIS PANEL IS NOW SHOWN IN A DETACHED |
| | STRUCTURE AND A MEANS OF DISCONNECT WILL |
| | BE REQUIRED PER 225.31. |
| | |
| | 9) NOTE: PLEASE SEE PLANS INDICATE A |
| | "IT" , NETWORK RM? PLEASE SEE NFPA-75, |
| | AND NFPA-70, 645. |
| | PLEASE SHOW ALL ELECTRICAL MEETING 645. |
| | PLEASE ALSO SEE ANY OTHER REQUIREMENTS |
| | FOR A/C SYSTEMS, IF FOR THIS ROOM ALONE |
| | OR IF SYSTEM ALSO FEEDS OTHER AREAS AND |
| | POSSIBLE FIRE DAMPERS. |
| | PLEASE ALSO SEE MIN CONSTRUCTION FOR |
| | ROOM PARTITIONS. |
| | |
| | 10) NOTE: PLEASE PROVIDE REFERENCES TO |
| | THE FOLLOWING CODES ON ELECTRICAL PLANS. |
| | NFPA-101 2003, NFPA-70 2002, NFPA-72 |
| | 2002, NFPA-110 2002, NFPA-20 2002. |
| | |
| | 10) NOTE: PLEASE SEE PANEL "IC" SHOWN ON |
| | ELECTRICAL ROOM LAYOUT, HOWEVER NOT ON |
| | RISER. |
| | 215.5 |
| | |
| | 11) NOTE: PLEASE CORRELATE GROUNDING |
| | ELECTRODE CONDUCTOR ON GROUNDING DETAIL |
| | AS SHOWN ON RISER. |
| | 250.50, 215.5 |
| | |
| | 12) NOTE: PLEASE SEE 210.8B3 FOR |
| | KITCHENS, SEE ALL RECEPTS 15/20A 120 V |
| | SHALL BE GFI/GFI PROTECTED. |
| | PREVIOUS REVIEW COMMENT. |
| | |
| | 13) NOTE: PLEASE SEE PREVIOUS REVIEW |
| | NOTED THE SERVICE ENTRANCE CONDUCTORS |
| | NOT BEING LARGE ENOUGH AND RESPONSE FROM |
| | DESIGN PROFESSIONAL MENTIONS SERVICE |
| | REVISED TO 2500A'S, HOWEVER PLANS |
| | INDICATE 3000A'S? |
| | PLEASE KNOW, THE SEC'S ARE REVISED NOW |
| | TO 3000A'S AND ARE OK. THIS WAS ONLY A |
| | NOTE. |
| | |
| | 14) NOTE: PLEASE SUBMIT WIND LOAD |
| | CALCUALTIONS FOR SITE LIGHTING POLES AS |
| | REQUESTED ON PREVIOUS REVIEW. THIS COULD |
| | NOT BE LOCATED ON SITE LIGHTING PLANS? |
| | 215.5 |
| | |
| | 15) NOTE: PLEASE SEE A PREVIOUS NOTE |
| | MENTIONED THE USE OF A SHUNT TRIP |
| | BREAKER AND THE MCB STILL BEING REQUIRED |
| | TO HAVE A MANUAL MEANS OF DISCONNECT |
| | LOCATED ON THE OUTSIDE RATED RATED FOR |
| | THE LOAD SERVED. 230.76,230.79 ETC. |
| | PLEASE SEE RESPONSE FORM DESIGN |
| | PROFESSIONAL MENSITONS "SHUNT TRIP" |
| | BREAKER REMOVED, HOWEVER PLANS STILL |
| | INDICATE THIS ON PANEL SCHEDULE AND |
| | PLANS?? |
| | PLEASE ALSO SEEPLANS INDICATE A |
| | "SERVICE MAIN" LOCATED OUTSIDE HOWEVER |
| | THIS IS NOT INCLUDED IN RISER? |
| | |
| | 16) NOTE: PLEASE INDICATE PANELS AS |
| | "FEEDE-THRU" AS PANEL BOARDS SHALL NOT |
| | CONTAIN MORE THE 42 SPACES.408.15 |
| | PLEASE SEE ALL PANELS ON UPPER FLRS. |
| | |
| | 17) NOTE: PLEASE SEE A/C UNIT IN ROOMS |
| | CONSIDERED TO MEET DWELLING UNIT BEDRMS |
| | SHALL ALSO MEET 210.12B NEC. 2002 |
| | |
| | 18) NOTE: PLEASE SEE NOTE #7 ON KEY |
| | NOTES ON RISER SHEET. PLEASE CORRELATE |
| | WITH NOTE #11 ON 2.01A.??? |
| | CLARIFY? |
| | |
| | 19) NOTE: PLEASE SEE KEY NOTE ON RISER |
| | #5, PLEASE CORRELATE WITH NOTE #2 ON |
| | 2.01A. PLEASE SEE ONE SHOWS 175A FUSES |
| | AND THE OTHER 150A?? |
| | |
| | 20) NOTE: PLEASE SUBMIT HP RATINGS OF |
| | ELEVATOR MOTORS, UNABLE TO VERIFY AT |
| | THIS TIME. |
| | 215.5 |
| | |
| | 21) NOTE: PLEASE VERIFY EQUIPEMTN BEING |
| | SHOWN ON 4TH FLR ELEV LOBBY. ONE AREA |
| | INDICATE THE EQUIPMENT IN A MECHANICAL |
| | CLOSET OF SOME SORT, HOWEVER PLANS ALSO |
| | INDICATE EQUIPMENT OUTSIDE EACH ELEVATOR |
| | IN OTHER TYPE OF RM/CLOSET?? |
| | |
| | 22) NOTE: PLEASE ALSO CORRELATE |
| | CIRCUITING ON PLANS FOR ELEVATOR |
| | EQUIPMENT, AS ONE SHOWN TO A COMPLETEY |
| | DIFFERENT CIRCUIT AND THE OTHER IS SHOWN |
| | BEING FED FROM THE "POOL PANEL"?? |
| | 215.5 |
| | |
| | 23) NOTE: PLEASE SEE A PANEL "EG" IS |
| | SHOWN ON PANEL SCHEDULES, HOWEVER NOT |
| | INFORMATION ON RISER FOR THIS?: |
| | PLEASE SEE THIS IS ALSO ON PLANS, |
| | HOWEVER THERE IS NOT ENOUGH INFORMATION |
| | FOR THIS PANEL, ATS ETC. |
| | 215.5 |
| | |
| | |
| | |
| | ** PLEASE KNOW, BASED ON THE PLANS AND |
| | INFORMATION SUBMITTED THERE MAY BE OTHER |
| | COMMENTS AS A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE COULD NOT BE DONE AT THIS |
| | TIME. |
| | PLEASE BE SURE TO SEE ALL OF THE 2004 |
| | FBC CHAPTER 13 FOR ELECTRICAL CHANGES. |
| | |
| | ** PLEASE KNOW, ONE SET OF PLANS ARE |
| | BEING RETAINED. |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | ***PLEASE KNOW, ALL THREE SETS SHALL |
| | BE SIGNED, DATED AND SEALED. |
| | PLEASE KNOW, THERE ARE ROLLS IN EACH |
| | PACKAGE FOR HOTELS WHICH ARE NOT SIGNED |
| | OR SEALED. |
| 2006-05-11 00:00:00 | REVIEW IS DONE, PLANS ARE IN "F"STATUS, |
| | NOTES TO FOLLOW ON 5/14/06 |