Plan Review Notes
Plan Review Notes For Permit 06040134
Permit Number 06040134
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-14 00:00:00******** UNSAT 2ND REVIEW *******
  
 **STAYBRIDGE SUITES, FIRST REVIEW UNDER
 2004 FBC.
  
  
 ** PLEASE KNOW, PLANS ORIGINALLY CAME IN
 UNDER THE 2001 FBC AND NOW PLANS ARE
 SUBMITTED UNDER THE 2004 FBC. PLEASE SEE
 MOST OF THE COMMENTS ARE NEW, HOWEVER
 SOME ARE FROM PREVIOUS REVIEW.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ANY OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
  
 1) NOTE: PLEASE SEE ADDRESSING FOR
 PROJECT SHOULD BE ON TITLE BLOCK FOR
 LOCATION OF PROJECT.
 FAC61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE CLARIFY TITLE BLOCK ON
 COVER SHEETS AND ALL TRADE SHEETS, AS
 THESE STATE THE ELECTRICAL ENGINEER OF
 RECORD AS UNDER THE ARCHITECTURAL FIRM?
 PLEASE ALSO SEE STRUCTURAL, MECHANICAL
 AND PLUMBING SHEETS AS THESE DO NOT
 CONTAIN ANY TITLE BLOCKS FOR THE
 ENGINEERS OR ENGINEERIN FIRMS AS LISTED
 ON COVER SHEETS.
 ** PLEASE SEE A PRINT OUT FROM THE
 STATE'S WEBSITE IS NOW ATTACHED TO
 NOTES, AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER AS INDICATE ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM IS
 "NULL AND VOID" PER DEPARTMENT OF
 BUSINESS AND PROFESSIOAL REGULATION.
 PLEASE SEE ELECTRICAL SHEETS DO NOT
 INDICATE THIS AND LIST THE ENGINEER AS
 AN INDIVIDUAL?
 PLEASE SEE FAC 61G15-23.002, FS 471.023,
 IF ARCHITECTURAL FIRM IS OFFERING
 ENGIEERING SERVICES, PLEASE PROVIDE
 CERTIFICATE OF AUTHORIZATION FOR THIS.
 THE CA # WAS ADDED FOR ARCHITECTURAL
 FIRM AS REQUESTED ON PREVIOUS REVIEW
 HOWEVER AS NOTED ABOVE, SEEMS NOT BE
 ACTIVE.
 PLEASE SEE THE PRINTED NAME AND LICENSE
 NUMBER OF THE ARCHITECT IS ALSO REQUIRED
 ON TITLE BLOCKS FOR ALL SHEETS.
 FAC 61G1-16.004
 ** PLEASE KNOW, THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE FP SHEETS, AS ONE
 SHEET IS A COPY OF SIGNED AND SEALED
 PLANS SUBMITTED.
  
 4) NOTE: PLEASE KNOW, PLANS ARE NOW
 BEING SUBMITTED UNDER THE 2004 FBC,
 HOWEVER NO CHANGES IN ELECTRICAL DESIGN
 WERE MADE TO THE NEW 2004 CHAPTER 13.
 PLEASE SEE CHAPTER 13, 13-413.1ABC.1,
 PLEASE PROVIDE ALL WORST CASE CALCS, AND
 ADJUST AS NEEDED FOR LONGEST RUNS.
 PLEASE SEE 13-415.1.ABC.1.1, &.2, & .3
 WHICH GREATLY AFFECT ELECTRICAL DESIGN.
 COULD NOT LOCATE ANY INFORMATION FOR
 THIS ON PLANS.?
 PLEASE SEE ALL OTHER CHANGES IN CHAPTER
 13. FIXTURE TYPES, TANDEM WIRING ETC.
  
 5)NOTE: PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR ALL EGRESS
 AREAS/PATHS.
 PLEASE SEE NFPA-101 2003, 7.8.1.3,
 7.9.2.2. PLEASE SEE STAIRS FOR EGRESS
 SHALL CONTAIN A MIN OF 10FT CANDLES AVG
 UNDER NORMAL CONDITIONS AND 1FT CANDLE
 AVG UNDER EM POWER.
 PLEASE SEE MIN REQUIRED FOR ALL OTHER
 PATHS SHALL BE 1FT CANDLE.
 PLEASE ALSO KNOW, AN EM BATTERY BACK UP
 FIXTURE OF SOME TYOE WILL BE REQUIRED IN
 THE MAIN ELECTRICAL ROOM.
  
 6) NOTE: PLEASE SEE NO INFORMATION WAS
 SUBMITTED FOR THE FIRE PUMP, FIRE PUMP
 CONTROLLER.
 PLEASE KNOW, ALL PERMITS, PLANS AND
 INFORMATION FOR THIS SHALLBE
 SUBMITTED. PLANS NOW INDICATE A FIRE
 PUMP LOCATED IN A DETACHED BUIDLING
 WHICH WILL FEED TWO DIFFERENT HOTELS.
 PLEASE KNOW, APPROVAL BY THE FIRE
 MARSHAL'S OFFICE SHALL FIRST BE OBTAINED
 FOR THIS SCENERIO. PLEASE ALSO KNOW,
 PERMIT FOR EITHER BUILDING CAN NOT BE
 PASSED FOR PERMITING UNTIL ALL
 INFORMATION, PLANS ETC FOR FIRE PUMP,
 FIRE PUMP CONTROLLER CAN BE REVIEWED. IF
 ELECTRICAL DRIVEN FIRE PUMP, PLEASE
 PROVIDE ALL INFORMATION.
 PLEASE SEE FP SEEM TO INDICATE
 ELECTRICAL FIRE PUMP, BUT UNCLEAR AT
 THIS TIME.
 PLEASE SEE NFPA-20 2002. PLEASE SUBMIT
 ALL RELEVANT INFORMATION FOR FIRE PUMP
 CONTROLLER ETC.
  
 7) NOTE: PLEASE SEE PLANS ARE NOW
 INDICATING A BACK UP GENERATOR OF SOME
 SORT? IF ANY PART OF THIS SYSTEM IS
 GOING TO BE INSTALLED, PLEASE SUBMIT ALL
 INFORMATION FOR ATS, GENERATOR,
 ELECTRICAL RISER, SUB BASE FUEL ETC.
 PLEASE SEE AN ATS IS BEING SHOWN ON
 PLANS AT THIS TIME, HOWEVER HOW THIS IS
 NOT BEING SHOWN WIRED INTO RISER?
 PLEASE KNOW, IF NO PART OF THIS SYSTEM
 IS GOING TO BE INSTALLED AT THIS TIME,
 PLEASE REMOVE FROM PLANS AS LONG AS ALL
 MIN LIFE SAFETY BACK UP SYSTEMS ARE
 PROVIDED BY OTHER MEANS.
 PLEASE SUBMIT ALL MANUFACTURE CUT
 SHEETS/SPEC FOR GEN, ATS'S, FIRE PUMP,
 FIRE PUMP CONTROLLER, AND ANY FUEL
 TANKS.
  
 8) NOTE: PLEASE SEE PANEL "P" ON SHOWS
 MCB AS REQUIRED, YET PANEL SCHEDULE
 SHOWS THIS PANEL AS "MLO". PLEASE KNOW,
 THIS PANEL IS NOW SHOWN IN A DETACHED
 STRUCTURE AND A MEANS OF DISCONNECT WILL
 BE REQUIRED PER 225.31.
  
 9) NOTE: PLEASE SEE PLANS INDICATE A
 "IT" , NETWORK RM? PLEASE SEE NFPA-75,
 AND NFPA-70, 645.
 PLEASE SHOW ALL ELECTRICAL MEETING 645.
 PLEASE ALSO SEE ANY OTHER REQUIREMENTS
 FOR A/C SYSTEMS, IF FOR THIS ROOM ALONE
 OR IF SYSTEM ALSO FEEDS OTHER AREAS AND
 POSSIBLE FIRE DAMPERS.
 PLEASE ALSO SEE MIN CONSTRUCTION FOR
 ROOM PARTITIONS.
  
 10) NOTE: PLEASE PROVIDE REFERENCES TO
 THE FOLLOWING CODES ON ELECTRICAL PLANS.
 NFPA-101 2003, NFPA-70 2002, NFPA-72
 2002, NFPA-110 2002, NFPA-20 2002.
  
 10) NOTE: PLEASE SEE PANEL "IC" SHOWN ON
 ELECTRICAL ROOM LAYOUT, HOWEVER NOT ON
 RISER.
 215.5
  
 11) NOTE: PLEASE CORRELATE GROUNDING
 ELECTRODE CONDUCTOR ON GROUNDING DETAIL
 AS SHOWN ON RISER.
 250.50, 215.5
  
 12) NOTE: PLEASE SEE 210.8B3 FOR
 KITCHENS, SEE ALL RECEPTS 15/20A 120 V
 SHALL BE GFI/GFI PROTECTED.
 PREVIOUS REVIEW COMMENT.
  
 13) NOTE: PLEASE SEE PREVIOUS REVIEW
 NOTED THE SERVICE ENTRANCE CONDUCTORS
 NOT BEING LARGE ENOUGH AND RESPONSE FROM
 DESIGN PROFESSIONAL MENTIONS SERVICE
 REVISED TO 2500A'S, HOWEVER PLANS
 INDICATE 3000A'S?
 PLEASE KNOW, THE SEC'S ARE REVISED NOW
 TO 3000A'S AND ARE OK. THIS WAS ONLY A
 NOTE.
  
 14) NOTE: PLEASE SUBMIT WIND LOAD
 CALCUALTIONS FOR SITE LIGHTING POLES AS
 REQUESTED ON PREVIOUS REVIEW. THIS COULD
 NOT BE LOCATED ON SITE LIGHTING PLANS?
 215.5
  
 15) NOTE: PLEASE SEE A PREVIOUS NOTE
 MENTIONED THE USE OF A SHUNT TRIP
 BREAKER AND THE MCB STILL BEING REQUIRED
 TO HAVE A MANUAL MEANS OF DISCONNECT
 LOCATED ON THE OUTSIDE RATED RATED FOR
 THE LOAD SERVED. 230.76,230.79 ETC.
 PLEASE SEE RESPONSE FORM DESIGN
 PROFESSIONAL MENSITONS "SHUNT TRIP"
 BREAKER REMOVED, HOWEVER PLANS STILL
 INDICATE THIS ON PANEL SCHEDULE AND
 PLANS??
 PLEASE ALSO SEEPLANS INDICATE A
 "SERVICE MAIN" LOCATED OUTSIDE HOWEVER
 THIS IS NOT INCLUDED IN RISER?
  
 16) NOTE: PLEASE INDICATE PANELS AS
 "FEEDE-THRU" AS PANEL BOARDS SHALL NOT
 CONTAIN MORE THE 42 SPACES.408.15
 PLEASE SEE ALL PANELS ON UPPER FLRS.
  
 17) NOTE: PLEASE SEE A/C UNIT IN ROOMS
 CONSIDERED TO MEET DWELLING UNIT BEDRMS
 SHALL ALSO MEET 210.12B NEC. 2002
  
 18) NOTE: PLEASE SEE NOTE #7 ON KEY
 NOTES ON RISER SHEET. PLEASE CORRELATE
 WITH NOTE #11 ON 2.01A.???
 CLARIFY?
  
 19) NOTE: PLEASE SEE KEY NOTE ON RISER
 #5, PLEASE CORRELATE WITH NOTE #2 ON
 2.01A. PLEASE SEE ONE SHOWS 175A FUSES
 AND THE OTHER 150A??
  
 20) NOTE: PLEASE SUBMIT HP RATINGS OF
 ELEVATOR MOTORS, UNABLE TO VERIFY AT
 THIS TIME.
 215.5
  
 21) NOTE: PLEASE VERIFY EQUIPEMTN BEING
 SHOWN ON 4TH FLR ELEV LOBBY. ONE AREA
 INDICATE THE EQUIPMENT IN A MECHANICAL
 CLOSET OF SOME SORT, HOWEVER PLANS ALSO
 INDICATE EQUIPMENT OUTSIDE EACH ELEVATOR
 IN OTHER TYPE OF RM/CLOSET??
  
 22) NOTE: PLEASE ALSO CORRELATE
 CIRCUITING ON PLANS FOR ELEVATOR
 EQUIPMENT, AS ONE SHOWN TO A COMPLETEY
 DIFFERENT CIRCUIT AND THE OTHER IS SHOWN
 BEING FED FROM THE "POOL PANEL"??
 215.5
  
 23) NOTE: PLEASE SEE A PANEL "EG" IS
 SHOWN ON PANEL SCHEDULES, HOWEVER NOT
 INFORMATION ON RISER FOR THIS?:
 PLEASE SEE THIS IS ALSO ON PLANS,
 HOWEVER THERE IS NOT ENOUGH INFORMATION
 FOR THIS PANEL, ATS ETC.
 215.5
  
  
  
 ** PLEASE KNOW, BASED ON THE PLANS AND
 INFORMATION SUBMITTED THERE MAY BE OTHER
 COMMENTS AS A COMPLETE REVIEW FOR CODE
 COMPLIANCE COULD NOT BE DONE AT THIS
 TIME.
 PLEASE BE SURE TO SEE ALL OF THE 2004
 FBC CHAPTER 13 FOR ELECTRICAL CHANGES.
  
 ** PLEASE KNOW, ONE SET OF PLANS ARE
 BEING RETAINED.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ***PLEASE KNOW, ALL THREE SETS SHALL
 BE SIGNED, DATED AND SEALED.
 PLEASE KNOW, THERE ARE ROLLS IN EACH
 PACKAGE FOR HOTELS WHICH ARE NOT SIGNED
 OR SEALED.
2006-05-11 00:00:00REVIEW IS DONE, PLANS ARE IN "F"STATUS,
 NOTES TO FOLLOW ON 5/14/06