Plan Review Notes
Plan Review Notes For Permit 06040134
Permit Number 06040134
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06040134
 ADD: 2216 45TH ST
 CONT:O'CONNORS& TAYLOR, INC.
 TEL: (561)863-7349
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLEASE CONTACT LILI URSA MIS
 ADDRESSING TECHNITION FOR THE CORRECT
 ADDRESS. CITY RECORDS INDICATE THE
 CORRECT ADDRESS TO BE 2200 45TH STREET
 FOR THIS PARCEL. CONTACT LILI @ (561)
 805-1239.
  
 3) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 4)DLW ARCHITECTS- AA0002714 THE
 CERTIFICATE OF AUTHORIZATION IS NULL &
 VOID SINCE 02/28/2003.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 5) ALL A-10 SHEETS (PRODUCT APPROVALS)
 THE DESIGN PROFESSIONAL FAILED TO SIGN
 AND SEAL THESE SHEETS.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6) THIS STRUCTURE IS CONCIDERED A
 THRESHOLD BUILDING REQUIRING (3) OF ALL
 DOCUMENTS TO BE SUBMITTED TO THE
 BUILDING DEPARTMENT, PLANS, REVISIONS,
 LETTERS,AND OR SUBMITTALS,ETC
  
 7A) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7B)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING. THE PURPOSE OF
 THE SRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES
 AND SCHEDULES SO THAT THE BUILDING CAN
 BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
 T-0.01 INSPECTION PLAN DOESN'T
 INDICATE ANY SHORING OR RESHORING IN THE
 INSPECTION PLAN, NOR LENGTH OF TIME
 SHORING SHOULD BE PLACED THERE.
  
 8) SOILS REPORT SUBMITTED IS A COPY OF
 THE SOILS ENGINEERS' SIGNATURE. NO
 RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF UNITS
 H) NUMBER OF FLOORS
 I) NUMBER OF BEDROOMS
 J) NUMBER OF ROOMS
 K) NUMBER OF BEDROOMS
 L) SQ. FT. LIV SPACE/ FL
 M) SQ. FT. FOOTPRINT
 N) SQ. FT. UNDER ROOF (TOTAL)
 O) OCCUPANT LOAD
 P) FLOOD ZONE
 Q) MEAN ROOF HEIGTH, A-0.01 PLANS
 INDICATE FROM GRADE TO PLANK @ ROOF, SEE
 A-5.12 DETAIL# 1 TRUSSES NO CONCRETE
 PLANK.MEAN ROOF HEIGHT. THE AVERAGE OF
 THE ROOF EAVE HEIGHT AND THE HEIGHT TO
 THE HIGHEST POINT ON THE ROOF SURFACE,
 EXCEPT THAT EAVE HEIGHT SHALL BE USED
 FOR ROOF ANGLE OF LESS THAN OR EQUAL TO
 10 DEGREES (0.1745 RAD). GREATER THAN
 50'-0".
  
 12) 1609.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 13) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 14) THE DESIGNER OF RECORD PRINTING THE
 PRODUCT APPROVALS AS PART OF THE PLAN
 MAKES IT DIFFICULT TO SEE WHAT APPROVALS
 ARE PRESENT AND WHICH AREN'T. ALSO NOTE
 IF THE CONTRACTOR CHANGES OUT PRODUCTS
 ( A REVISION) THE PRODUCT APPROVALS
 PRINTED ON THE ARCHITECTURAL SHEETS WILL
 BE CHARGED A BASE FEE OF $50.00 AND
 $10.00 A PAGE WHERE AS THE PRODUCT
 APPROVAL ITSELF IS CHARGED A TOTAL OF
 $60.00.
  
 15) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J".
 PLEASE USE THE 2004 FORMS. IF A DESIGN
 PROFESSIONAL PRODUCES THE ENERGY CALS,
 MUST BE SIGNED AND SEALED.
  
 16A) PLANS DO NOT SHOW AN ACCESSIBLE
 ENTRANCE, PASSENGER LOADING ZONE,
 11-4.1.2(1). FIGURE 10 ACCESS AISLE AT
 PASSENGER LOADING ZONE.
  
 16B) 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDINGS OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 17) A-0.1.1 THE PLANS DO NOT SHOW AN
 ACCESSIBLE ROUTE TO 45TH ST.11-4.1.2(1)
 AN ACCESSIBLE SITE SHALL MEET THE
 FOLOWING MINIMUM REQUIREMENTS:
 (1) AT LEAST ONE ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 SHALL BE
 PROVIDED WITHIN THE BOUNDRY OF THE SITE
 FROM PUBLIC TRANSPORTATION STOPS,
 ACCESSIBLE PARKING SPACES, PASSENGER
 LOADING ZONES IF PROVIDED, AND PUBLIC
 STREETS OR SIDEWALKS, AND ACCESSIBLE
 BUILDING ENTRANCE.
  
 18) SHEET A-0.1.1 INDICATES THERE TO BE
 A TOTAL OF 101 PARKING SPACES REQUIRING
 (5) HANDICAPPED PARKING SPACES NOT 4.
 SEE 11-4.1.2(5) 101-150 +5 ACCESSIBLE
 SPACES.
  
 19) A-0.04A THE POOL EQUIPMENT BUILDING
 AND PAVILION BOTH INDICATE STRUCTURAL
 DETAILS ON SHEET SA3 NOT FOUND IN PLANS.
 ARE THESE STRUCTURES TO BE PART OF THIS
 PERMIT? WHAT BUILDING TYPE?
  
 20) A-0.04A PLANS FOR THE POOL EQUIPMENT
 AND PAVILION BOTH INDICATE FIBERGLASS
 SHINGLES. SUBMIT PRODUCT APPROVALS.
 RULE 9B-72.
  
 21) A-0.04B PLANS INDICATE FOOTER
 INFORMATION ON S1.3, ROOF FRAMING ON
 SHEET S2.3 & 6.1, WHERE?
  
 22) A-0.05HEADING: RAMPS/ LANDING
 LENGTH SHALL BE A MINIMUM OF 60". SEE
 11-4.8.4(2)ALL LANDINGS ON RAMPS SHALL
 BE NOT LESS THAN 60 INCHES (1524 MM)
 CLEAR, AND THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72 INCHES (1829 MM)
 OF STRAIGHT AND LEVEL CLEARANCE.
  
 23) A-1.01,A-2.01 & A2.02 DOOR# 142 &
 142A MISSING THE 18" ON THE PULL LATCH
 SIDE OF DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 24)A-1.06 DETAIL# 9 ROOF HATCH INDICATES
 SHEET A6.02 DETAILS 1,2,3&4 WHERE?
  
 25)A-1.06 DETAIL# 2, DETAIL INDICATES
 USE OF STANDING SEAM METAL ROOF, WITH
 THE USE OF A CONTINIOUS VENTCOVERED WITH
 SHINGLES. PROVIDE THE PRODUCT APPROVALS
 WITH THIS TYPE OF APPROVED APPLICATION.
 ADDITIONAL INFORMATION REQUIRED.
  
 26) A-1.06 DETAIL# 10, INDICATES THE USE
 OF SHINGLES FOR A CRIKET, IS THIS ALSO
 TO BE USED WITH A STANDING SEAM METAL
 ROOF, IF SO PROVIDE THE PRODUCT APPROVAL
 WITH THIS TYPE OF APPLICATION.
 ADDITIONAL INFORMATION REQUIRED.
  
 27) A-1.06 DETAIL# 7 IS FOR THE ACCESS
 LADDER MISSING ANCHOR LENGTH? PROVIDE A
 SECTION THROUGH, HOW FAR DOES THE LADDER
 AND SIDE RAILS RUN WITHIN AN INCH OF THE
 ROOF HATCH?
  
 28) A2.01 DOOR# 112,114& 116 SEE:
 1008.1.8.8 DURING ITS SWING, ANY DOOR IN
 A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST ONE HALF OF THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE
 THAN 7 INCHES (178 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY
 OR LANDING, WHEN FULLY OPEN.
  
 29) A-2.01 GUEST ROOM DOORS 115& 115A,
 PLANS DO NOT PROVIDE THE INFORMATION ON
 THE EXTERIOR SIDE DOOR LANDING.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 30) A-2.02 LAUNDRY CHUTE PROVIDE
 INFORMATION AS TO THE ACTUAL LAUNDRY
 CHUTE AND ACCESS DOORS THAT ARE BUILT
 INTO THE CHUTE.
  
 31) 707.13.1 REFUSE AND LAUNDRY CHUTE
 ENCLOSURES.
 A SHAFT ENCLOSURE CONTAINING A REFUSE OR
 LAUNDRY CHUTE SHALL NOT BE USED FOR ANY
 OTHER PURPOSE AND SHALL BE ENCLOSED IN
 ACCORDANCE WITH SECTION 707.4 . OPENINGS
 INTO THE SHAFT, INCLUDING THOSE FROM
 ACCESS ROOMS AND TERMINATION ROOMS,
 SHALL BE PROTECTED IN ACCORDANCE WITH
 THIS SECTION AND SECTION 715 . OPENINGS
 INTO CHUTES SHALL NOT BE LOCATED IN EXIT
 ACCESS CORRIDORS. OPENING PROTECTIVES
 SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE ACTUATION OF
 A SMOKE DETECTOR INSTALLED IN ACCORDANCE
 WITH SECTION 907.10 , EXCEPT THAT
 HEAT-ACTIVATED CLOSING DEVICES SHALL BE
 PERMITTED BETWEEN THE SHAFT AND THE
 TERMINATION ROOM.
  
 32)A-2.02 LAUNDRY CHUTE ALSO HAS A
 WALL CUT SECTION W-11 INDICATING A 2 HR
 WALL, A-5.14 PROVIDES A SECTION THROUGH
 THE LAUNDRY CHUTE BUT THE SHAFT IS
 INTERRUPTED AT FLOOR LEVEL LOSING THE 2
 HR RATING AS DEPICTED.
  
 33) A-2.02 THE LAUNDRY ROOM ALSO DOESN'T
 INDICATE A DOOR TO THE TERMINATION ROOM
 OF THE LAUNDRY CHUTE?
  
 34) A-2.11 THE 2 BEDROOM ACCESIBLE UNIT
 IS MISSING THE 3'-0" CLEAR BETWEEN BEDS.
 11-9.2.2(1). AT THE FOOT OF THE KING
 SIZE BED THERE IS LESS THAN 36".
 11-9.2.2(2).
  
 35) A2-11 THE SAME 2 BEDROOM ACCESSIBLE
 UNIT THE KITCHEN SINK NEEDS TO BE
 ACCESSIBLE ALSO.11-9.2.2(2)AN
 ACCESSIBLE ROUTE COMPLYING WITH SECTION
 11-4.3 SHALL CONNECT ALL ACCESSIBLE
 SPACES AND ELEMENTS, INCLUDING
 TELEPHONES, WITHIN THE UNIT, SLEEPING
 ROOM, OR SUITE.
  
 36) A-2.11 ONE BEDROOM ACCESSIBLE KING
 MISSING A CLEAR 36" PATH TO THE CLOSET.
 11-9.2.2(4)(4) IF FIXED OR BUILT-IN
 STORAGE FACILITIES SUCH AS CABINETS,
 SHELVES, CLOSETS, AND DRAWERS ARE
 PROVIDED IN ACCESSIBLE SPACES, AT LEAST
 ONE OF EACH TYPE PROVIDED SHALL CONTAIN
 STORAGE SPACE COMPLYING WITH SECTION
 11-4.25 . ADDITIONAL STORAGE MAY BE
 PROVIDED OUTSIDE OF THE DIMENSIONS
 REQUIRED BY SECTION 11-4.25 .
  
 37) THE SAME SITUATION WITH THE KITHCEN
 SINK, IN CORNER CAN'T MAKE A FRONTAL
 APPROACH REQUIRES 30" CLEAR, 15"
 CENTERLINE OF SINK.
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 38) A-5.10 INDICATES VARIOUS WINDOWS AND
 DETAIL A3/ A9.08 THAT DO NOT HAVE
 ADEQUATE ATTACHMENT WHERE DEPICTD IN THE
 PLANS. THEY DO NOT HAVE FASTENING INTO
 STRUCTURAL MEMBERS INSTALLED AS
 ILLUSTRATED.
  
 39) A-5.11 DETAIL 6 & 6A:
 39A) BRICK VENEER/ CULTURED STONE: THE
 6"CLEAR INSPECTION SPACE OF THE
 FOUNDATION SIDEWALL EXTERIOR EXIST
 BETWEEN THE VENEER AND THE TOP OF ANY
 SOIL, SOD, MULCH OR OTHER ORGANIC
 LANDSCAPING COMPONENT, DECK, APRON,
 PORCH, WALK OR ANY OTHER WORK
 IMMEDIATELY ADJACENT TO OR ADJOINING THE
 STRUCTURE.
 1405.3.2 MASONRY.
 FLASHING AND WEEPHOLES SHALL BE LOCATED
 IN THE FIRST COURSE OF MASONRY ABOVE
 FINISHED GROUND LEVEL ABOVE THE
 FOUNDATION WALL OR SLAB, AND OTHER
 POINTS OF SUPPORT, INCLUDING STRUCTURAL
 FLOORS, SHELF ANGLES AND LINTELS WHERE
 ANCHORED VENEERS ARE DESIGNED IN
 ACCORDANCE WITH SECTION 1405.5 .
  
 39B)DETAIL 5A)EFIS SYSTEMS,2603.9.2
 CLEARANCE BETWEEN EARTH AND FOAM
 PLASTICS APPLIED TO THE EXTERIOR WALL
 SHALL BE NOT LESS THAN 6 INCHES (152
 MM). NOTE DETAIL 6A) DOESN'T INDICATE
 USE OF EFIS BUT THE USE OF 7/8" STUCCO?
  
 39C) PLANS DO NOT INDICATE COMPLIANCE
 WITH ANCHORAGE TO METAL STUD WALL.
 1405.5 ANCHORED MASONRY VENEER.
 ANCHORED MASONRY VENEER SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1405.5 ,
 1405.6 , 1405.7 AND 1405.8 AND SECTIONS
 6.1 AND 6.2 OF ACI 530/ASCE 5/TMS 402.
  
 40) SHEET A-10.XX PRODUCT APPROVALS
 PLEASE SUBMIT PRODUCT APPROVALS IN THE
 BROCHURE FORM, IF ON ARCHITECTURAL
 SHEETS THEY MUST BE SEALED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.FL S S 61G15-23.002
 NOTE IF A REVISION COMES IN FOR CHANGE
 OF A SYSTEM YOU WILL BE CHARGES $50BASE
 FEE AND AN ADDITIONAL $10.00 PER SHEET.
 PRODUCT APPROVAL REVISION THAT COEMS IN
 IN BROCHURE FORM IS CHARGED BASE FEE OF
 $50.00 AND AN ADDITIONAL $10.00.
  
 41)PRODUCT APPROVALS SUBMITTED ARE
 EITHER FILED UNDER THE 2001 FBC OR THEY
 WERE FILED WITH REPORTS THAT HAD BEEN
 SUBMITTED UNDER THE FBC 2004 CODE AND
 WERE PULLED BECAUSE THEY DIDN'T STATE
 THE CODE EDITION. NONE OF THE REPORTS
 THAT WERE SUBMITTED ARE ON THE FL WEB
 SITE CURRENTLY!!!!
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED
 B) WINDOWS HORIZONTAL SLIDERS
 C) WINDOWS SINGLE HUNG
 D) GLAZED DOORS
 E) STEEL DOORS
 F) WALL LOUVERS
 G) TRUSS TIES
 H) HARDI-PLANK
 I) EFIS SYSTEMS NOT SYSTEMS LIMITATIONS
  
 FOR HORIZONTAL USE
 J) DENSE-GLASS
 K) ASPHALT SHINGLES
 L) NON-STURTURAL METAL ROOFING
 M) FLAT ROOF - NO INFORMATION WAS
 SUBMITTED AT ALL.
 NOTE HIGHLIGHT WHICH SUB-SYSTEM THAT
 WILL BE USED. NOTE IF LIMITATION
 NUMBER 7 OR 9!!!!!!!!!
  
 42) JAMES HARDI PLANK WHEN CONTRACTOR
 SUBMITS THE UPDATED REPORT HIGHLIGHT
 WHICH SYSTEM IS TO BE USED AND FASTENING
 DEVICE IN THE WIND SPEED TABLES.
  
 43) A5.14 DETAIL# 1 LAUNDRY CHUTE, THIS
 DETAIL IS MISSING THE 2 HR RATING
 BETWEEN FLOORS.
  
 44) S-0.01 SPECIFIC LOADS: ROOF, THERE
 IS NO BOTTOM CHORD LIVE LOADOF 10 PSF,
 TABLE 1607.1.
  
 45) S-0.01 WIND LOAD MISSING THE YEAR
 UNDER ASCE 7-XX.
  
 46) S-0.02 BASIS OF DESIGN WRONG YEAR
 FOR ASCE 7-98.
  
 47) S-0.02 OPENING FASTENING CHART THE
 WRONG WIND ZONE, INDICATES 110/120.
  
 48) S-0.03 THERE IS (3) CHARTS ON THE
 LEFT SIDE OF THE PAGE ALL QUOTING THE
 WRONG CODE SECTIONS.
  
 49) S-1.04 PROVIDE THE TRUSS LAYOUT FOR
 THIS BUILDING WITH THE LOADS TO BE
 IMPOSED, UPLIFT, LATERAL AND GRAVITY.
 PROVIDE WHAT TYPE OF ANCHOR AND THE
 LOADS LISTED IN THE MANUFACTURERS
 BROCHURE.S-2.02 ALSO INDICATES SEE TRUSS
 MANUFACTURER FOR TRUSS LAYOUT. THE
 DESIGNER OF RECORD PROVIDES THE LAYOUT,
 THE TRUSS MANUFACTURER PROVIDES THE
 DETAILED SHOP DRAWINGS. THE DESIGNER OF
 RECORD TO REVIEW AND APPROVE THE SHOP
 TRUSS DRAWINGS.
  
 50) S-6.03DETAIL "F" BASE PLATE, MISSING
 THE THICKNESS OF THE TOP AND BOTTOM
 COLUMN PLATE?
  
 51) S-1.01 FRONT ENTRY AT DOUBLE SET OF
 DOUBLE DOORS, PLANS DO NOT PROVIDE A
 FOUNDATION DETAIL, OR CROSS SECTION
 INDICATING THE FOUNDATION FOR THIS
 SECTION.
  
 52) S-2.01 DISCREPANCY DETAILS A& B BOTH
 INDICATE METAL & WOOD TRUSSES?
  
 53) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  