| Plan Review Notes For Permit 06040085 |
| Permit Number |
06040085 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-06-29 00:00:00 | DENIED; | | | | | | 1. (THIRD REQUEST) FLOOR DRAIN IN 2ND | | | FLOOR APARTMENT RIGHT SIDE IS STILL | | | SHOWN ON THE FLAT DRAWING AND RISER | | | DIAGRAM. PLEASE DELETE. | | | 2. (SECOND REQUEST) DRINKING FOUNTAINS | | | ARE REQUIRED PER FBC-2006 PLUMBING SEC. | | | 410.1. NO BOTTLED WATER. | | | 3.(SECOND REQUEST) WATER HEATER DETAIL; | | | SHUTOFF VALVE FORWATER HEATER IS | | | REQUIREDTO BE BEFORE THE EXPANTION TANK | | | FOR SERVICE. | | | 4.(THIRD REQUEST) H/C BATHROOM DOORIN | | | SUITE "A" IS REQUIRED TO BE CATTY-CORNER | | | TO THE TOILET FBC-2004 SEC. 11-4.17.3. | | | 5.(SECOND REQUEST)AUTOMATIC CLOTHES | | | WASHERS BRANCH DRAINS TO BE 3" PER | | | PLUMBING CODE SEC.406.3 WITH A CLEANOUT | | | AT 48" ABOVE FINISH FLOOR. | | | 6.(SECOND REQUEST) PLEASE DELETE WALK IN | | | COOLER FROM PAGE P-2. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|