Plan Review Notes
Plan Review Notes For Permit 06040085
Permit Number 06040085
Review Stop P
Sequence Number 2
Notes
Date Text
2006-06-06 00:00:00DENIED;
 1. (SECOND REQUEST) FLOOR DRAIN IN 2ND
 FLOOR APARTMENT RIGHT SIDE IS STILL
 SHOWN ON FLAT PLUMBING DRAWING AND
 SANITARY RISER DIAGRAM. PLEASE DELETE.
 2.DRINKING FOUNTAINS ARE REQUIRED NOT
 BOTTLE WATER FBC-2004 PLUMBING SECTION
 410.1. THE FIRST DRINK FOUNTAIN MUST BE
 A PLUMBING FIXTURE.
 3.WATER HEATER DETAIL; SHUTOFF VALVE FOR
 HEATER IS REQUIRED TO BE BEFORE
 EXPANSION TANK FOR SEVICEEASY.
 4.(SECOND REQUEST OLD NOTE # 8) H/C
 BATHROOM DOOR IN SUITE "A" IS REQUIRED
 TO BE CATTY-CORNER TO THE W/C FBC-2004
 SEC 11-4.17.3. REVERSE LOCATION OF W/C
 AND LAV.
 5. W/M BRANCH DRAIN TO BE 3" PER
 PLUMBING CODE SEC. 406.3 WITH C.O. AT
 48" AFF.
 6.IF PLANS ARE FOR SHELL ONLY THEN
 PLEASE DELETE FLOOR DRAIN AND NOTE FOR
 WALKIN COOLER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695