| Plan Review Notes For Permit 06040085 |
| Permit Number |
06040085 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-06 00:00:00 | DENIED; | | | 1. (SECOND REQUEST) FLOOR DRAIN IN 2ND | | | FLOOR APARTMENT RIGHT SIDE IS STILL | | | SHOWN ON FLAT PLUMBING DRAWING AND | | | SANITARY RISER DIAGRAM. PLEASE DELETE. | | | 2.DRINKING FOUNTAINS ARE REQUIRED NOT | | | BOTTLE WATER FBC-2004 PLUMBING SECTION | | | 410.1. THE FIRST DRINK FOUNTAIN MUST BE | | | A PLUMBING FIXTURE. | | | 3.WATER HEATER DETAIL; SHUTOFF VALVE FOR | | | HEATER IS REQUIRED TO BE BEFORE | | | EXPANSION TANK FOR SEVICEEASY. | | | 4.(SECOND REQUEST OLD NOTE # 8) H/C | | | BATHROOM DOOR IN SUITE "A" IS REQUIRED | | | TO BE CATTY-CORNER TO THE W/C FBC-2004 | | | SEC 11-4.17.3. REVERSE LOCATION OF W/C | | | AND LAV. | | | 5. W/M BRANCH DRAIN TO BE 3" PER | | | PLUMBING CODE SEC. 406.3 WITH C.O. AT | | | 48" AFF. | | | 6.IF PLANS ARE FOR SHELL ONLY THEN | | | PLEASE DELETE FLOOR DRAIN AND NOTE FOR | | | WALKIN COOLER. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|