Date Text
2006-05-22 00:00:00 
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 700.12(E) UNIT EQUIPMENT.
 INDIVIDUAL UNIT EQUIPMENT FOR EMERGENCY
 ILLUMINATION SHALL CONSIST OF THE
 FOLLOWING: "THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES."
  
 2} THE GEC MUST BE 2/0 MINIMUM PER
 250.66. THE SERVICE CONDUCTORS ARE
 EQUIVALENT.
 NOTE: WHILE NOT A VIOLATION, ALL THE
 EQUIPMENT GROUNDS FROM THE DISCONNECTS
 TO THE PANELS ARE, CONSIDERABLY, TOO
 LARGE. SEE 250.122.
  
 3} THE GROUNDING ELECTRODE SYSTEM IS
 REQUIRED TO HAVE A SUPPLEMENTAL GROUND
 ROD PER 250.53(D)(2).
  
 4} THE APARTMENT UNITS MUST HAVE SMOKE
 DETECTORS INSTALLED INSIDE, AND OUTSIDE
 THE BEDROOMS.
  
 PLEASE CHECK RECEPTACLE SPACING IN THE
 APARTMENT UNITS PER 210.52.
  