| Plan Review Notes For Permit 06040085 |
| Permit Number |
06040085 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-22 00:00:00 | | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PER 700.12(E) UNIT EQUIPMENT. | | | INDIVIDUAL UNIT EQUIPMENT FOR EMERGENCY | | | ILLUMINATION SHALL CONSIST OF THE | | | FOLLOWING: "THE BRANCH CIRCUIT FEEDING | | | THE UNIT EQUIPMENT SHALL BE THE SAME | | | BRANCH CIRCUIT AS THAT SERVING THE | | | NORMAL LIGHTING IN THE AREA AND | | | CONNECTED AHEAD OF ANY LOCAL SWITCHES." | | | | | | 2} THE GEC MUST BE 2/0 MINIMUM PER | | | 250.66. THE SERVICE CONDUCTORS ARE | | | EQUIVALENT. | | | NOTE: WHILE NOT A VIOLATION, ALL THE | | | EQUIPMENT GROUNDS FROM THE DISCONNECTS | | | TO THE PANELS ARE, CONSIDERABLY, TOO | | | LARGE. SEE 250.122. | | | | | | 3} THE GROUNDING ELECTRODE SYSTEM IS | | | REQUIRED TO HAVE A SUPPLEMENTAL GROUND | | | ROD PER 250.53(D)(2). | | | | | | 4} THE APARTMENT UNITS MUST HAVE SMOKE | | | DETECTORS INSTALLED INSIDE, AND OUTSIDE | | | THE BEDROOMS. | | | | | | PLEASE CHECK RECEPTACLE SPACING IN THE | | | APARTMENT UNITS PER 210.52. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|