| 2006-05-24 00:00:00 | 1) 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 2) INDICATE IN DETAIL DRAWINGS HOW THE |
| | FLOOR RATING WILL COMPLY WITH THE |
| | SEPERATION BETWEEN THE BUSINESS AND THE |
| | RESIDENTAL UNITS ABOVE. SEE FBC TABLE |
| | 302.3.2. |
| | |
| | 3) THE PRESSURES FOR THE WINDOWS ON THE |
| | NORTH AND WEST ELEVATIONS ARE MISSING. |
| | PLEASE SHOW THE PRESSURES FOR THESE |
| | WINDOWS ON THE DRAWINGS. |
| | |
| | 4 ) WPB ADMIN CODE 106.3.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. EACH |
| | PRODUCT WHICH IS APPROVED BY THE STATE |
| | SHOULD HAVE THE STATE COVER SHEET WITH |
| | THE MATCHING FL#. SEE EXAMPLE IN PACKAGE |
| | FOR THE CAMERON ASHLEY-GUARDIAN BUILDING |
| | PRODUCTS. |
| | |
| | 5) I NOTICE THAT THE VALUE HAS BEEN |
| | CHANGED, BUT ACCORDING TO THE SQUARE |
| | FOOTAGE AND THE SCOPE OF WORK DESCRIBED |
| | IT STILL SEEMS LOW. A FAIR MARKET VALUE |
| | IS REQUESTED OR WE WILL USE THE MARSHALL |
| | AND SWIFT MANUAL TO ADJUST THE VALUE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |