| Notes |
| Date |
Text |
| 2006-04-12 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE NOTE THAT IN ADDITION TO | | | APPLICABLE BUILDING CODES, LIFE SAFETY | | | SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 2) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 3) PLEASE BE AWARE THAT THE REQUIREMENTS | | | OF NFPA 101, SECTION 7.2.2.6.3 REGARDING | | | SEPARATION AND PROTECTION OF OUTSIDE | | | STAIRS SHALL BE MET. PLEASE INDICATE IF | | | BUILDING IS PROTECTED BY AN AUTOMATIC | | | FIRE SPRINKLER SYSTEM. | | | | | | 4) PLEASE INDICATE THE PRESCRIPTIVE | | | STRENGTH REQUIREMENTS FOR NEW HANDRAILS | | | AND GUARDS. | | | | | | 5) PLEASE SHOW THE LOCATIONS OF REQUIRED | | | SMOKE DETECTORS IN RESIDENTIAL UNITS. | | | | | | 6) IF APPLICABLE, SEPARATE SHOP DRAWINGS | | | AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER/FIRE ALARM SYSTEMS OR REMODEL. | | | | | | 7) PLEASE PROVIDE FURTHER INFORMATION | | | REGARDING FIRE RATING OF OPENINGS WITHIN | | | 10' TO THE OUTSIDE STAIRS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|