Plan Review Notes For Permit 06040085
Permit Number 06040085
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-04-12 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT IN ADDITION TO
 APPLICABLE BUILDING CODES, LIFE SAFETY
 SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 3) PLEASE BE AWARE THAT THE REQUIREMENTS
 OF NFPA 101, SECTION 7.2.2.6.3 REGARDING
 SEPARATION AND PROTECTION OF OUTSIDE
 STAIRS SHALL BE MET. PLEASE INDICATE IF
 BUILDING IS PROTECTED BY AN AUTOMATIC
 FIRE SPRINKLER SYSTEM.
  
 4) PLEASE INDICATE THE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR NEW HANDRAILS
 AND GUARDS.
  
 5) PLEASE SHOW THE LOCATIONS OF REQUIRED
 SMOKE DETECTORS IN RESIDENTIAL UNITS.
  
 6) IF APPLICABLE, SEPARATE SHOP DRAWINGS
 AND PERMITS REQUIRED FOR FIRE
 SPRINKLER/FIRE ALARM SYSTEMS OR REMODEL.
  
 7) PLEASE PROVIDE FURTHER INFORMATION
 REGARDING FIRE RATING OF OPENINGS WITHIN
 10' TO THE OUTSIDE STAIRS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722