Plan Review Notes
Plan Review Notes For Permit 06040085
Permit Number 06040085
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 HOUSE PANEL ON THE PLAN.
  
 2} PLEASE LOCATE THE SERVICE EQUIPMENT
 ON THE PLAN.
  
 3} PLEASE SEE THE SERVICE CONDUCTORS AT
 THE SERVICE ENTRANCE HEAD ARE EXPOSED TO
 RAIN AND SHOULD BE TYPE THHN. SEE
 310.8(C).
  
 4} THE FEEDERS MUST CONTAIN AN EQUIPMENT
 GROUND FROM THE FIRST MEANS OF
 DISCONNECT TO THE PANELS PER 215.6.
  
 5} THE LIGHTING LOADS IN THE OFFICES
 MUST BE CALCULATED AS CONTINUOUS.
  
 6} PLEASE SEE ARTICLE 220 FOR
 RESIDENTIAL CALCULATIONS WHICH MUST BE
 USED FOR THE DWELLING UNITS. A
 COMMERCIAL CALCULATIION IS SHOWN ON THE
 PLAN.
  
 7} THE CODE REFERENCES ON SHEET E0.0
 SHUOLD INDICATE THE ADOPTED VERSION PER
 YEAR. NEC-2002, NFPA-101-2003,
 NFPA-72-2002.
  
 8} THERE IS NO SHEET A1 WITH THE
 SUBMITTED PLANS.
  
 9} AS PER ARTICLE 600.5 BRANCH CIRCUITS.
 (A) REQUIRED BRANCH CIRCUIT. EACH
 COMMERCIAL BUILDING AND EACH COMMERCIAL
 OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE
 OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR OUTLINE LIGHTING SYSTEM USE. THE
 OUTLET(S) SHALL BE SUPPLIED BY A BRANCH
 CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. SERVICE HALLWAYS
 OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS. INCLUDE IN
 CALCULATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026