| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE INDICATE THE LOCATION OF THE |
| | HOUSE PANEL ON THE PLAN. |
| | |
| | 2} PLEASE LOCATE THE SERVICE EQUIPMENT |
| | ON THE PLAN. |
| | |
| | 3} PLEASE SEE THE SERVICE CONDUCTORS AT |
| | THE SERVICE ENTRANCE HEAD ARE EXPOSED TO |
| | RAIN AND SHOULD BE TYPE THHN. SEE |
| | 310.8(C). |
| | |
| | 4} THE FEEDERS MUST CONTAIN AN EQUIPMENT |
| | GROUND FROM THE FIRST MEANS OF |
| | DISCONNECT TO THE PANELS PER 215.6. |
| | |
| | 5} THE LIGHTING LOADS IN THE OFFICES |
| | MUST BE CALCULATED AS CONTINUOUS. |
| | |
| | 6} PLEASE SEE ARTICLE 220 FOR |
| | RESIDENTIAL CALCULATIONS WHICH MUST BE |
| | USED FOR THE DWELLING UNITS. A |
| | COMMERCIAL CALCULATIION IS SHOWN ON THE |
| | PLAN. |
| | |
| | 7} THE CODE REFERENCES ON SHEET E0.0 |
| | SHUOLD INDICATE THE ADOPTED VERSION PER |
| | YEAR. NEC-2002, NFPA-101-2003, |
| | NFPA-72-2002. |
| | |
| | 8} THERE IS NO SHEET A1 WITH THE |
| | SUBMITTED PLANS. |
| | |
| | 9} AS PER ARTICLE 600.5 BRANCH CIRCUITS. |
| | (A) REQUIRED BRANCH CIRCUIT. EACH |
| | COMMERCIAL BUILDING AND EACH COMMERCIAL |
| | OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE |
| | OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| | ENTRANCE TO EACH TENANT SPACE FOR SIGN |
| | OR OUTLINE LIGHTING SYSTEM USE. THE |
| | OUTLET(S) SHALL BE SUPPLIED BY A BRANCH |
| | CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| | SUPPLIES NO OTHER LOAD. SERVICE HALLWAYS |
| | OR CORRIDORS SHALL NOT BE CONSIDERED |
| | ACCESSIBLE TO PEDESTRIANS. INCLUDE IN |
| | CALCULATION. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |