Plan Review Notes
Plan Review Notes For Permit 06040067
Permit Number 06040067
Review Stop E
Sequence Number 4
Notes
Date Text
2006-10-15 15:40:27*** UNSAT4THREVIEW *****
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF COMPPLIANCE.
  
  
 1) NOTE: PLEASE SEE AS STATED IN PREVIOUS REVIEWS, ALL
 SEPARATE SPACES REQUIRE OVER-RIDE DEVICE(S) .
 PLEASE SEE PREVIOUS NOTES FOR SCHEDULING.
 PLEASE SEE PREVIOUS NOTES FOR MAX WATTAGE PERMITTED.
 BASED ON THE WATTAGE ON FIXTURES ON PLANS, THIS EXCEEDS
 THE "PROPOSED WATTAGE" WHICH IS STATED ON PLANS. PLEASE
 PROVIDE A COMPLETE SUMMARY OF AREAS FOR LIGHTING POWER
 DENSITIES AS ALLOWED PER CODE. PLEASE SEE TABLES AS
 PERVIOUSLY NOTED.
 PLEASE SEE SOME FIXTURES AND EM LTS ARE SHOWN BEING
 CIRCUITED THROUGH TIMER WHICH IS OK, HOWEVER THESE ARE
 NOTEDBEING WIRED AHEAD OF CONTROLS, HOWEVER SHOULD BE
 SHOWN ON LIGHTING DETAIL SO THIS ALLEAVIATES ANY
 CONFUSION. THIS ITEM IS NOT REQUIRED , HOWEVER
 RECOMMENDED. IT IS CLEAR TO THE DESIGNER AND REVIEWER
 OF THE INTENT, HOWEVER THE TIME CONTROL PANEL DOES NOT
 INDICATE THIS AND HOW THIS WILL TAKE PLACE.
 PLEASE ALSO CORRELATE WITHTHE WATTAGE BEING SHOWN ON
 PANEL SCHEDULES, AS THIS WATTAGE EXCEED ACTUAL SHOWN
 AND PROPOSED DESIGN WATTAGE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-415..ABC.1. , PLEASE SEE WHERE TRADES
 OFFS ARE NOT PERMITTED UNDER CERTAINS CIRCUMSTANCES.
 PLEASE SEE TABLES 415.2.C.1, 415.2.B.1
 IT APPERS A WATTAGEAS SHOWN IS COMING FROM THE SPACE
 BY SPACE TABLES AT 2.1, HOWEVER PLEASE SEE FBCAS
 NOTED.
  
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEWS WITH RESPECT
 RELEVANT CODES NOT CURRENT. PLEASE SEE PREVIOUS NOTES
 WHICH ALSO MENTIONED "A" SHEET(S). STILL SHOW 1999
 NEC.
  
  
 3) NOTE: PLEASE SEE FEES FOR FS 553.80(2)(B) HAS NOW
 BEEN ASSESSED AND MUST BE PAID BEFORE PLANS ARE
 RESUBMITTED ON NEXT REVIEW.
 THIS FEE IS $3132.00
 PLANS WILL RETAINED BY THIS OFFICE FOR POSSIBLE REVIEW
 FROM THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  