Plan Review Notes
Plan Review Notes For Permit 06040067
Permit Number 06040067
Review Stop E
Sequence Number 3
Notes
Date Text
2006-08-25 00:00:00******* UNSAT 3RD REVIEW *****
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEWS STILL NEED TO BE
 ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
  
 1) NOTE:NO. SEE PREVIOUS NOTE.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW **
 NO, PLEASE SEE THERE ARE
 PLACES ON PLANS WHICH STILL REFLECT
 OLDER CODES. PLEASE SEE "A" SHEETS, AND
 E-SHEETS. PLEASE SEE NOW THE CHANGES
 MADE ON E-3 NOW CONTAIN BOTH THE
 PREVIOUS AND CURRENT ELECTRICAL CODE.
 PLEASE SEE E-4 WHICH STILL REFLECTS
 SBCCI, SFBC, 1997 LS 101 ETC.
  
 ** PREVIOUS REVIEW 1ST REVIEW NOTE**
 PLEASE ADJUST AND REFLECT ALL
 CURRENT CODES IN AFFECT.
 PLEASE SEE WE ARE UNDER THE 2002
 NFPA-70( NEC), 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE KNOW THESE CODES AT A MINIMUM
 SHALL BE REFERENCED ON ARCHITECTURAL AND
 ELECTRICAL/ FIRE PLANS.
 PLEASE SEE PLANS REFLECT 1999 NEC, 1997
 SBC, AND THE SBCCI ETC.
 PLEASE SE COMMENTS FROM OTHER TRADES
 WITH RESPECT TO CODES. (BUILDING).
  
 2) NOTE: NO. IT IS BEING NOTED THAT ONE
 FIRM LICENSE NUMBER IS NOW BEING SHOWN,
 HOWEVERPLEASE KNOW WE HAVE BEEN IN
 CONTACT WITH THE STATE'S LEGAL COUNSEL
 TO THE BOARD OF ARCHITECTS AS THE FIRM
 LICENSE NUMBER PROVIDED IS LISTED ON THE
 STATE'S WEBSITE FOR V.Z.AARCHITECT'S
 P.A. AND THERE IS NO LISTING FOR
 "ZAMPARELLI ARCHITECTURAL GROUP" AKA
 "ZAG".
 PLEASE KNOW THIS HAS BEEN CONFIRMED WITH
 DWIGHT CHASTANE FROM THE FIRM WHICH
 REPRESENTSTHE STATE BOARD OF
 ARCHITECTURE'S LEGAL COUNSEL. IT IS
 MENTIONED THAT BOTH COMPANIES AS LISTED
 ON TITLE BLOCKSWHICH ARE REGIESTERED
 WITH THE STATEWOULD EACH REQUIRE A
 CERTIFICATE OF AUTHORIZATION NUMBER.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW**
 NO, PLEASE SEE ONLY THE
 PRINTED NAME AND LICENSE # OF THE
 ARCHITECT WAS ADDED. PLEASE SEE THE FIRM
 TITLE BLOCK IS STILL MISSING THE
 REQUIRED FIRM LICENSE NUMBER WHICH IS
 ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FS 481.219, FAC 61G1-16.004
  
 ** PREVIOUS REVIEW NOTE 1ST REVIEW **
 PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR ARCHITECT AND
 ARCHITECTURAL FIRM. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUES 481.219.
 MISSING THE PRINTED NAME AND LICENSE #
 OF THE ARCHITECT, MISSING THE FIRM
 LICENSE # FOR THE ARCHITECTURAL FIRM.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK
  
 ******** NEW NOTES 2ND REVIEW ******
  
 8) NOTE:NO, PLEASE SEE CONDUCTORS
 STILL DO NOT CORRELATE.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW**
 PLEASE SEE RISER AND PANEL "A"
 AS THE OCP FOR THE AHU WAS ADJUSTED AND
 INCREASED TO 30A?S. PLEASE SEE THAT THE
 CONDUCTOR SIZE WAS CHANGED ON THE PANEL
 SCHEDULE, HOWEVER PLEASE SEE RISER
  
 9) NOTE: NO, PLEASE SEE CONTROLS FOR
 SEPARATE SPACES IS NOT BEING SHOWN.
 PLEASE SEE LOCATIONS AT INGRESS/EGRESS
 FOR OVER-RIDES ARE NOT SHOWN ON PLANS AT
 LOCATION WHERE OCCUPANT ENTERS AND EXITS
 AND CAN VISUALLY SEE LIGHTING BEING
 CONTROLLED BY OVER RIDES.
 PLEASE SEE LIGHTING POWER DENSITIES ON
 PLANS/SEPARATLY COULD NOT BE LOCATED.
 PLEASE SEE EACH DEVICE SHOULD BE LISTED
 AND SHOWN ON SYMBOL LEGEND FOR TYPE AND
 AMOUNT OF OVER RIDES TIME.
  
 ** PREVIOUS REVIEW NOTE 2ND REVIEW**
 PLEASE SEE A LIGHTING CONTROL
 PANEL IS BEING SHOWN TO MEET FBC CHAPTER
 13-415.1.ABC.1.1, .1.2, .1.3, HOWEVER
 PLEASE PROVIDE THE OVER-RIDE DEVICES AT
 THIS TIME AND LOCATED IN THE SPACES AS
 REQUIRED.
 PLEASE INDICATE THE DEVICE AND KNOW,
 WHEN USING A TIMED OVER-RIDE (4HRS MAX)
 AND OCCUPANCY SENSOR TYPE DEVICE (30MINS
 MAX). PLEASE SEE AREAS WITH SEPARATE
 SPACES.
 PLEASE ALSO SEE 13-415.1.AB.1, AND
 13-415.2.ABC.1 FOR MAX LIGHTING
 DENSITIES PERMITTED.
 PLEASE SEE BOTH TABLES AND INDICATE.
 PLEASE PROVIDE ALL CONTROLLED CIRCUITING
 ON TIME/PANEL SCHEDULE. PLEASE ALSO
 PROVIDE THE SCHEDULING TIMES.
  
 ** NEW NOTE **
 10) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS. PLEASE
 KNOW AS PLANS ONLY CMAE IN FOR "PLAN
 REVIEW" FOR THE FIRST REVIEW, PLEASE
 KNOW THE FEE IS NOT ASSESSED AT THIS
 TIME. PLEASE BE SURE ALL COMMENTS ARE
 ADDRESSED AND IF THERE ARE ANY
 QUESTIONS, ONCE AGAIN PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
 ONE SET OF PLANS ARE BEING RETAINED BY
 THIS OFFICE.
  
  
 ** WHEN RESUBMITTING PLANS, PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER@WPB.