| 2006-07-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A. FROM PREVIOUS REVIEW. COMMENT NUMBERS |
| | TO REMAIN THE SAME FOR CLARITY: |
| | |
| | 1. ALL SHEETS, THE TITLE BLOCK FOR THE |
| | ARCHITECT MUST, AT A MINIMUM, CONTAIN |
| | THE FOLLOWING INFORMATION: |
| | 61G1-16.004(2)(5). THE FIRM LICENSE |
| | NUMBER, AND A SPACE FOR THE PRINTED NAME |
| | OF THE PERSON SEALING THE DOCUMENT. FS |
| | 481.219 481.2055. |
| | ***RESPONSE NOTED, BUT THE CERTIFICATE |
| | OF AUTHORIZATION, (BUSINESS NUMBER), IS |
| | NOT SHOWN ON THE TITLE BLOCK. |
| | |
| | 2. SHT A-0 ACCESSIBILITY CODE TO READ |
| | FBC-2001 CHAPTER 11. |
| | ***RESPONSE NOTED, BUT MY FAULT, THIS |
| | SHOULD READ FBC-2004 CHAPTER 11. (SORRY) |
| | |
| | 3. OK |
| | |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | 6. SUBMIT A DETAIL FOR THE DRINKING |
| | FOUNTAIN SHOWING COMPLIANCE WITH 11-4.15 |
| | AND ALL SUBSECTIONS, AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO |
| | HAVE DIFFICULTY BENDING OR STOOPING. - |
| | WALL MOUNTED OR CANTILEVERED UNITS SHALL |
| | HAVE FORWARD APPROACH CLEAR FLOOR SPACE. |
| | ***RESPONSE NOTED, BUT PARALLEL APPROACH |
| | STILL SHOWN AT DETAIL 4. FORWARD |
| | APPROACH REQUIRED. |
| | |
| | 7. OK |
| | |
| | 8. OK |
| | |