| Date |
Text |
| 2006-06-27 00:00:00 | **** PLANS REMOVED FROMHOLD,**** |
| | |
| | PLEASE SEE PERMIT FEES WERE NOT PAID AND |
| | REVIEWS ARE ON HOLD. |
| | CALLED PERMIT PROVIDERS, TO PAY W/IN |
| | 24HRS. SPOKE TO STEVE. |
| | |
| | NO REVIEWS WILL BE DONE. |
| | ******* UNSAT2ND REVIEW ***** |
| | |
| | |
| | |
| | ** PLEASE SEE PLANS ARE NOW SUBMITTED |
| | FOR PERMIT. PLEASE SEE SOME COMMENTS |
| | FROM PREVIOUS REVIEW AND SOME NEW |
| | COMMENTS. |
| | |
| | 1) NOTE:NO, PLEASE SEE THERE ARE |
| | PLACES ON PLANS WHICH STILL REFLECT |
| | OLDER CODES. PLEASE SEE "A" SHEETS, AND |
| | E-SHEETS. PLEASE SEE NOW THE CHANGES |
| | MADE ON E-3 NOW CONTAIN BOTH THE |
| | PREVIOUS AND CURRENT ELECTRICAL CODE. |
| | PLEASE SEE E-4 WHICH STILL REFLECTS |
| | SBCCI, SFBC, 1997 LS 101 ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE ADJUST AND REFLECT ALL |
| | CURRENT CODES IN AFFECT. |
| | PLEASE SEE WE ARE UNDER THE 2002 |
| | NFPA-70( NEC), 2003 NFPA-101, 2002 |
| | NFPA-72. |
| | PLEASE KNOW THESE CODES AT A MINIMUM |
| | SHALL BE REFERENCED ON ARCHITECTURAL AND |
| | ELECTRICAL/ FIRE PLANS. |
| | PLEASE SEE PLANS REFLECT 1999 NEC, 1997 |
| | SBC, AND THE SBCCI ETC. |
| | PLEASE SE COMMENTS FROM OTHER TRADES |
| | WITH RESPECT TO CODES. (BUILDING). |
| | |
| | 2) NOTE:NO, PLEASE SEE ONLY THE |
| | PRINTED NAME AND LICENSE # OF THE |
| | ARCHITECT WAS ADDED. PLEASE SEE THE FIRM |
| | TITLE BLOCK IS STILL MISSING THE |
| | REQUIRED FIRM LICENSE NUMBER WHICH IS |
| | ALSO KNOWN AS THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | FS 481.219, FAC 61G1-16.004 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCKS FOR ARCHITECT AND |
| | ARCHITECTURAL FIRM. PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G1-16.004 AND |
| | FLORIDA STATUES 481.219. |
| | MISSING THE PRINTED NAME AND LICENSE # |
| | OF THE ARCHITECT, MISSING THE FIRM |
| | LICENSE # FOR THE ARCHITECTURAL FIRM. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE:OK, HOWEVER SEE NEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE MINIMUM OCP FOR AHU, |
| | HEAT. PLEASE SEE MIN OCP IS 125%. |
| | PLEASE ADJUST. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK |
| | |
| | ******** NEW NOTES ****** |
| | |
| | 8) NOTE: PLEASE SEE RISER AND PANEL "A" |
| | AS THE OCP FOR THE AHU WAS ADJUSTED AND |
| | INCREASED TO 30A?S. PLEASE SEE THAT THE |
| | CONDUCTOR SIZE WAS CHANGED ON THE PANEL |
| | SCHEDULE, HOWEVER PLEASE SEE RISER |
| | |
| | 9) NOTE: PLEASE SEE A LIGHTING CONTROL |
| | PANEL IS BEING SHOWN TO MEET FBC CHAPTER |
| | 13-415.1.ABC.1.1, .1.2, .1.3, HOWEVER |
| | PLEASE PROVIDE THE OVER-RIDE DEVICES AT |
| | THIS TIME AND LOCATED IN THE SPACES AS |
| | REQUIRED. |
| | PLEASE INDICATE THE DEVICE AND KNOW, |
| | WHEN USING A TIMED OVER-RIDE (4HRS MAX) |
| | AND OCCUPANCY SENSOR TYPE DEVICE (30MINS |
| | MAX). PLEASE SEE AREAS WITH SEPARATE |
| | SPACES. |
| | PLEASE ALSO SEE 13-415.1.AB.1, AND |
| | 13-415.2.ABC.1 FOR MAX LIGHTING |
| | DENSITIES PERMITTED. |
| | PLEASE SEE BOTH TABLES AND INDICATE. |
| | PLEASE PROVIDE ALL CONTROLLED CIRCUITING |
| | ON TIME/PANEL SCHEDULE. PLEASE ALSO |
| | PROVIDE THE SCHEDULING TIMES. |
| | |
| | ** WHEN RESUBMITTING PLANS, PLEASE |
| | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | DPALMER@WPB. |