| 2006-05-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS, THE TITLE BLOCK FOR THE |
| | ARCHITECT MUST, AT A MINIMUM, CONTAIN |
| | THE FOLLOWING INFORMATION: |
| | 61G1-16.004(2)(5). THE FIRM LICENSE |
| | NUMBER, AND A SPACE FOR THE PRINTED NAME |
| | OF THE PERSON SEALING THE DOCUMENT. FS |
| | 481.219 481.2055. |
| | |
| | 2. SHT A-0 ACCESSIBILITY CODE TO READ |
| | FBC-2001 CHAPTER 11. |
| | |
| | 3. SHT A-3 FINISH PLAN. PLEASE EXPLAIN |
| | HOW PAINTED WALLS MEETS THE CODE |
| | REQUIREMENT FOR NONABSORBENT MATERIAL |
| | PER SECTION 1210.2 |
| | |
| | 4. SHT AC-1 DETAIL 6 - W/C DETAIL. SHOW |
| | HEIGHT PER SECTION 11-4.16.3. |
| | |
| | 5. SHT AC-1 DETAIL 3 - LAV CLEARANCE. |
| | SHOW REQUIREMENTS FOR EXPOSED PIPES AND |
| | SURFACES PER 11-4.19.4 AND FAUCETS PER |
| | 11-4.19.5. |
| | |
| | 6. SUBMIT A DETAIL FOR THE DRINKING |
| | FOUNTAIN SHOWING COMPLIANCE WITH 11-4.15 |
| | AND ALL SUBSECTIONS, AS WELL AS SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO |
| | HAVE DIFFICULTY BENDING OR STOOPING. - |
| | WALL MOUNTED OR CANTILEVERED UNITS SHALL |
| | HAVE FORWARD APPROACH CLEAR FLOOR SPACE. |
| | |
| | 7. SHT P-1 SUBMIT MANUF. SPECIFICATIONS |
| | FOR THE INSTANTANEOUS WATER HEATER. |
| | LISTING REQUIRED. SECTION 303.4 |
| | |
| | 8. SHT P-1 DETAIL #3 TOILET ROOM WATER |
| | RISER DIAGRAM. RPZV BACKFLOW SHALL BE |
| | LOCATED A MAXIMUM 4' ABOVE THE FLOOR FOR |
| | SERVICING AND CERTIFICATION. INDIRECT |
| | WASTE RECEPTOR SHALL RECIEVE DISCHARGE |
| | FROM BACKFLOW. |
| | |