Plan Review Notes
Plan Review Notes For Permit 06040067
Permit Number 06040067
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-05-31 00:00:00***DENIED***
  
 1) NOTE REGARDING ADDRESS AT REAR DOOR
 ACKNOWLEDGED. ADDRESS REQUIRED NEAR
 FRONT ENTRANCE DOOR, AND SHALL MEET CODE
 REQUIREMENTS FOR SIZE AND CONTRASTING TO
 BACKGROUND FOR VISIBILITY.
  
 2) DUCT SMOKE DETECTORS WHERE PROVIDED,
 ARE REQUIRED IN SUPPLY DUCT IN SYSTEMS
 GREATER THAN 2000CFM'S AND SHALL
 INITIATE A GENERAL FIRE ALARM IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) IN ADDITION TO FLORIDA FIRE
 PREVENTION CODE, LIFE SAFETY TO COMPLY
 WITH NFPA 101, 2003 EDITION.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL. ANY NEW SOFFITS SHALL NOT
 INTERFERE WITH FIRE SPRINKLER COVERAGE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722