Plan Review Notes
Plan Review Notes For Permit 06040067
Permit Number 06040067
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-04 00:00:00IN ELEC FOR REVIEW
 ******** UNSAT **********
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
 1) NOTE: PLEASE ADJUST AND REFLECT ALL
 CURRENT CODES IN AFFECT.
 PLEASE SEE WE ARE UNDER THE 2002
 NFPA-70( NEC), 2003 NFPA-101, 2002
 NFPA-72.
 PLEASE KNOW,THESE CODES AT A MININUM
 SHALL BE REFERENCED ON ARCHITECTURALS
 AND ELECTRICAL/ FIRE PLANS.
 PLEASE SEE PLANS REFLECT 1999 NEC, 1997
 SBC, THE SBCCI ETC.
 PLEASE SE COMMENTS FROM OTHER TRADES
 WITH RESPECT TO CODES. (BUILDING).
  
 2) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR ARCHITECT AND
 ARCHITECTURAL FIRM. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 ANF
 FLORIDA STATUES 481.219.
 MISSING THE PRINTED NAME AND LICENSE #
 OF THE ARCHITECT, MISSING THE FIRM
 LICENSE # FOR THE ARCHITECTURAL FIRM.
  
 3) NOTE: PLEASE VERIFY ELECTRICAL PLANS
 WHICH ARE NOTED AS BEING DONE BY A
 PROFESSIONAL ENGINEER, HOWEVER TITLE
 BLOCK REFLECT "MECHANICAL" . PLEASE SEE
 FS 471 FOR WORKING WITHIN SCOPE OF
 LICENSURE. PLEASE CLARIFY.
  
 4) NOTE: PLEASE SEE MININUM OCP FOR AHU,
 HEAT. PLEASE SEE MIN OCP IS 125%.
 PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 700.12E, WHICH
 REQUIRES THE EM/EXT LTS TO BE CIRCUITED
 TO THE LOCAL LIGHTING BRNACH CIRCUIT IN
 ANY ONE AREA.
 PLEASE SEE AS INDICATED ON PLANS FOR
 LAYOUT, CIRCUITS ETC. IT DOES NOT SEEM,
 PLANS MEET THE EXCEPTION TO USE A
 "LOCK-OFF" DEVICES.
 **PLEASE ALSO KNOW, ANY PROPOSED
 "LOCK-OFF DEVICES" MUST BE APPROVED BY
 THE AHJ. MANY OF THESE DEVICES ARE NOT
 ACCEPTABLE TO THIS AHJ.
  
 6) NOTE: PLEASE LABEL/NOTE COLOR CODING
 FOR 277/480V PER LOCAL AHJ AS BROWN ,
 PURPLE , YELLOW.
  
 7) NOTE: PLEASE SEE MISSIG EQUIPMENT
 GROUNDING CONDUCTOR FROMNEW PANEL "A"
 TO TRANSFORMER.
 250.122,250.110 ETC.
  
 ** WHEN RESUBMITTING PLANS, PLEASE
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  