| 2006-05-03 00:00:00 | *** UNSAT *** |
| | |
| | |
| | ** PLEASE SEE MOST COMMENTS FROM FIRST |
| | REVIEW HAVE BEEN ADDRESSED, HOWEVER |
| | PLEASE SEE NOTESBELOW. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS COMMENT |
| | WHICH REQUESTED CLARIFICATION OFTHE |
| | APS CONTAINING A MANUAL MEANS OF |
| | DISCONNECT LOCATED ON THE OUTSIDE OF |
| | EQUIPMENT RATED FOR THE LOAD SERVED. |
| | THE RESPONSE ONLY MENTIONED THE TRANSFER |
| | SWITCH CONTAIN MOLDED CASE BRKRS FOR |
| | MANUAL DISCONNECT, HOWEVER SPECS |
| | SUBMITTED DO NOT CORRELATE WITH THIS. |
| | PLEASE ALSO CLARIFYON THE OUTSIDE OF |
| | EQUIPMENT WITHOUT EXPOSURE OF LIVE |
| | PARTS. |
| | 110.27,230.76,230.79 |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS COMMENT |
| | WITH RESPECT TO LOAD ON GENERATOR, WHICH |
| | RESPONSE MENTIONS TO SEE A DETAIL ON E-3 |
| | FOR LOAD SHEDDING. |
| | THIS IS OK AND IS PERMITTED, HOWEVER |
| | DETAIL MENTIONS TO SEE E-6 FOR LOAD |
| | SHEDDING , HOWEVERNO SYSTEM DETAIL OR |
| | HOW THESE LOADS ARE BEING SHEDDED. |
| | PLEASE INDICATE EQUIPMENT BEING |
| | INSTALLED. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTE WHICH |
| | REQUESTED REFERENCE TO NFPA-110 2002. |
| | RESPONSE MENTIONS GEN DOES NOT FALL |
| | UNDER NFPA-110. |
| | PLEASE SEE FBC 2702.1 WHICH REQUIRES |
| | "STAND-BY" SYSTEMS TO ALSO BE INSTALLED |
| | PER NFPA-110. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS COMMENT |
| | WHICH REQUESTED TO INDICATE THE OCP AT |
| | GENERATOR. PLEASE SEE RESPONSE MENTIONS |
| | "SELF PROTECTED RELAY" ?? |
| | PLEASE INDICATE THE OCP AT GEN. |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE SEE COMMENT ONE, WHICH |
| | REQUESTED FOR VALUE FOR COMPLETE SCOPE |
| | OF WORK TO BE UPDATED. THE RESPINSE |
| | MENTIONS $137K, HOWEVER THIS WAS NOT |
| | DONE WHEN PLANS WERE RESUBMITTED, |
| | THEVALUE HAS SINCE BEEN INCREASED AND |
| | FEES ARE DUEAND MUST BE PAID BEFORE |
| | RESUBMITTING PLANS. |
| | 108.3 FBC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |