Text |
| 2006-06-16 00:00:00 | **** UNSAT 2ND REVIEW ***** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES DUE TO PLANS |
| | SUBMITTED. |
| | |
| | 1) NOTE:PLEASE SEE NOTE WITH RESPECT |
| | LISITNG OF CONTROLLER AS IT APPEARS |
| | EXISTING CONTROLLER WILL NEED TO BE |
| | CHANGED AND THE INFORMATION AS STATED IN |
| | NOTE ONE BELOEW FROM PREVIOUS REVIEW |
| | WILL BE IN NEED OF BEING ADDRESS. |
| | 215.5 |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SUBMIT INFORMATION ON |
| | EXISTING OR NEW ELECTRICAL CONNECTTIONS. |
| | IS THERE GOING TO BE A NEW FIRE PUMP |
| | CONTROLLER? |
| | PLEASE SUBMIT ELECTRICAL INFORMATION FOR |
| | EITHER TO CORRELATE WITH NEW PUMP FOR |
| | LOCKED ROTOR CURRENT, NEMA 2,ETC. |
| | NFPA-70 695, NFPA-20 CHAPTER 7 |
| | |
| | 2)NOTE: PLEAS KNOW, THE PLAN SUBMITTED |
| | FOR NEW SEPARATION WILL BE REVIEWED BY |
| | THE BUIDLIG REVIEWER. |
| | |
| | 3) NOTE: PLEASE SEE RESPONSE MENTIONS A |
| | NEW FIRE PUMP AND THE SPECS SUBMITTED |
| | WERE FOR AN EXISTING FIRE PUMP |
| | CONTROLLER WHICH IS NOT LISTED FOR USE |
| | WITH THE NEW PUMP. PLEASE SEE IT MAY BE |
| | LISTED FOR A 50HP PUMP, HOWEVER THESE |
| | ARE LISTED COMPONETS AND SHALL BE A |
| | LISTED ASSMENBLEY AS LOCKED ROTOR OCP, |
| | CURRENT RATIGS ETC FROM A FIRE PUMP |
| | CONTROLLER IS BASED ON THE MOTOR WHICH |
| | IT IS LISTED WITH . IE: CODE LETTER, EFF |
| | RATINGS ETC. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE MISSING THE SPECS |
| | FOR THE FIRE PUMP CONTROLLER AND FIRE |
| | PUMP. |
| | IF ONLY THE FIRE PUMP IS BEING CHANGED, |
| | PELASE INDICATE THE FIRE PUMP CONTROLLER |
| | AND IS LISTED WITH THE FIRE PUMP BEING |
| | INSTALLED. PLEAS EKNOW, ALL MUST HAVE |
| | LISTED COMPONENTS AND LISTED FOR THE |
| | USE/ ASSEMBLY.110.3 |
| | |
| | 4) NOTE:OK. |
| | |
| | 5) NOTE: OK, CONTRACTOR WILL BE REQUIRED |
| | TO APPLY FOR THE PERMIT FOR WALL. |
| | |
| | ** NEW NOTES ** |
| | |
| | 6) NOTE: PLEASE SUBMIT TWO COMPLETE NEW |
| | SETS FOR REVIEW AND STAMPING. PLEASE SEE |
| | OF THE SETS SUBMITTED, ONE SET IS OLD |
| | AND ONE SET IS NEW. PLEASE SUBMIT TWO |
| | COMPLETE NEW SETS FOR REVIEW AND |
| | STAMPING. |
| | FBC ADMIN SECT 106.1 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |