Plan Review Notes
Plan Review Notes For Permit 06040045
Permit Number 06040045
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-04 00:00:00********* UNSAT **********
  
 1) NOTE: PLEASE SUBMIT INFORMATION ON
 EXISTING OR NEW ELECTRICAL CONNECTTIONS.
 IS THERE GOING TO BE A NEW FIRE PUMP
 CONTROLLER?
 PLEASE SUBMIT ELECTRICAL INFORMATION FOR
 EITHER TO CORRELATE WITH NEW PUMP FOR
 LOCKED ROTOR CURRENT, NEMA 2,ETC.
 NFPA-70 695, NFPA-20 CHAPTER 7
  
 2)NOTE: PLEASE SEE LOCATION OF FIRE PUMP
 IS BEING NOTED AS BEING LOCATED IN THE
 POOL EQUIPMENT ROOM?
 PLEASE KNOW, THIS DOES NOT SEEIT WILL
 BE PERMITTED TO GO BACK TO LOCATION AS
 SHOWN.UNLESS IDENTIFIED FOR USE IN THE
 OPERATING ENVIRONMENT, NO CONDUCTORS OR
 EQUIPMENT SHALL BE LOCATED IN DAMP OR
 WET LOCATIONS; WHERE EXPOSED TO GASES,
 FUMES, VAPORS, LIQUIDS, OR OTHER AGENTS
 THAT HAVE A DETERIORATING EFFECT ON THE
 CONDUCTORS OR EQUIPMENT; OR WHERE
 EXPOSED TO EXCESSIVE TEMPERATURES.
 PLEASE SEE NFPA-20 CHAPTER 7 FOR
 INSTALLATION. NFPA-70 110.11
 PLEASE SEE THERE ARE MANY LOCATIONS IN
 CHAPTER 7 WHICH APPLIES.
  
 3) NOTE: PLEASE SEE MISSING THE SPECS
 FOR THE FIRE PUMP CONTROLLER AND FIRE
 PUMP.
 IF ONLY THE FIRE PUMP IS BEING CHANGED,
 PELASE INDICATE THE FIRE PUMP CONTROLLER
 AND IS LISTED WITH THE FIRE PUMP BEING
 INSTALLED. PLEAS EKNOW, ALL MUST HAVE
 LISTED COMPONENTS AND LISTED FOR THE
 USE/ ASSEMBLY.110.3
  
 4) NOTE: PLEASE SEE TITLE BLOCK FOR WHAT
 APPEARS TO BE A FIRM AS THE PE IS LISTED
 IN THE SAME TITLE BLOCK.?
 PLEASE KNOW, IF THIS IS SO, PLEASE
 INDICATE THE MISSING CERTIFICATE OF
 AUTHORIZATION # AS REQUIRED PER FS
 471.023, FAC 61G15-23.002
 PLEASE KNOW, IF NOT PLEASE INDICATE THE
 PE'S TITLE BLCO SEPARATE AND PLEASE BE
 SURE ALL INFORMATION ON SAID TITLE BLOCK
 IS CLEAR AND VISABLE.
 PLEASE SEE TITLE BLOCK IS VERY SMALL AND
 INFORMATION ISUNREADABLE.
  
 5) NOTE: PLEASE SEE AS PER THE FIRE
 SAFETY EVALUATION REPORT AND THE EXECUTE
 ORDER AS SO NOTED; ALL STRUCTURAL FIRE
 RATED WALL AND COMPONENTS SHALL BE DONE
 BY A LICENSED CONTRACTOR AND IS NOT IN
 THE SCOPE OF WORK FOR THIE PERMIT
 PACKAGE.
 PLEASE SEE FBC ADMISTRATIVE SECTION
 105.1 AND 105.2
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]