| Plan Review Notes For Permit 06040040 |
| Permit Number |
06040040 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-16 00:00:00 | PROVISO: THESE PROBLEMS NEED TO BE FIXED | | | BEFORE FINAL OR NO POWER WILLL BE | | | RELEASED TO THE BUILDINGS.JLEAHY | | | | | | | | | RISER DIAGRAM ONLY SHOWS 2/0 WIRE IF THE | | | LOAD CALCULATION FOR THE UNITS IS A 138 | | | EACH THEN THE 2/0S ARE TOO SMALL. PLEASE | | | RESUBMIT NEW CLACULATIONS OR A NEW RISER | | | DIAGRAM. | | | | | | ON PAGE 4-7 RISER SHOWS TWO 200A AMIN | | | ACCORDING TO THE NOTES IN THE PANEL | | | SCHEDULE, BUT ON THE BUILDING YOU SHOW 1 | | | AT 200 AND 1 AT 150????? PLEASE FIX | | | BEFORE FINAL ELECTRICAL INSPECTION. | | | | | | PAGE 5-7 RISER SHOWS 200AMP MAIN, PANEL | | | SCHEDULR SHOWS 150AMP MAIN. PLEASE FIX | | | BEFORE FINAL INSPECTION. | | | | | | NEED THE PERSON WHO HAS DRAWN THESE TO | | | SIGN AND DATE THESE PLANS FOR THE ELEC. | | | | | | THESE ARE THE SAME COMMENTS THAT WHERE | | | GIVEN TO YOU ON 8/19 PLEASE FIX OR YOU | | | WILL NOT GET POWER TO THE UNITS/OR HAVE | | | POWER SHUT OFF TO THE UNITS!!!!!!!!!! |
|