| Date |
Text |
| 2006-08-17 00:00:00 | DENIED |
| | |
| | |
| | 1.PERMIT VALUATION IS TO LOW AND |
| | SHOULD INCLUDE ALL MATERIALS AND LABOR. |
| | ADDITIONAL PERMIT FEES ARE DUE.FEES |
| | PAID TO DATE REFLECT ONLY A $12,000 |
| | VALUATION.ADJUST VALUE AND PAY FEES |
| | PRIOR TO RESUBMITTING PLANS. |
| | |
| | 2."R" VALUES ON ENERGY CALS DO NOT |
| | MATCH THOSE ON PLANS. |
| | |
| | A.STATE PRODUCT APPROVALS REQUIRED FOR |
| | STANLY DOOR. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | B.SUBMIT PRODUCT APPROVALS FOR |
| | MULLIONS. |
| | |
| | C.COMPLETE A SHUTTER SCHEDULE, SEE |
| | SAMPLE ATTACHED. |
| | |
| | D.SUBMIT PRODUCT APPROVALS FOR AN |
| | INSWING ENTRY DOOR. |
| | |
| | E.SUBMIT PRODUCT APPROVALS FOR ALL |
| | STRAPS AND TIE-DOWNS USED.INFORMATIONS |
| | SUBMITTED IS ONLY SIMPSON SPEC. SHEETS. |
| | |
| | F.WINDOW AND DOOR PRESSURES NOT SHOW |
| | ON ALL ELAVATIONS. |
| | |
| | G.SUBMIT PRODUCT APPROVALS FOR |
| | OVERHEAD DOORS. |
| | |
| | H.PLANS SHALL BE DESIGNED TO THE 2004 |
| | FORIDA RESIDENTIAL CODE.SEE PLUMBING |
| | PAGE NOTE. |
| | |
| | I.SMOKE ALARMS SHALL BE INSTALLED IN |
| | THE FOLLOWING LOCATIONS: R 313.1 |
| | 1.IN EACH SLEEPING ROOM. |
| | 2.OUTSIDE EACH SEPARATE SLEEPING |
| | AREA IN THE IMMEDIATE VICINITY OF THE |
| | BEDROOMS. |
| | 3.ON EACH ADDITIONAL STORY OF THE |
| | DWELLING, INCLUDING BASEMENTS BUT NOT |
| | INCLUDING CRAWL SPACES AND UNINHABITABLE |
| | ATTICS. IN DWELLINGS OR DWELLING UNITS |
| | WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT |
| | LEVELS, A SMOKE ALARM INSTALLED ON THE |
| | UPPER LEVEL SHALL SUFFICE FOR THE |
| | ADJACENT LOWER LEVEL PROVIDED THAT THE |
| | LOWER LEVEL IS LESS THAN ONE FULL STORY |
| | BELOW THE UPPER LEVEL. |
| | WHEN MORE THAN ONE SMOKE ALARM IS |
| | REQUIRED TO BE INSTALLED WITHIN AN |
| | INDIVIDUAL DWELLING UNIT THE ALARM |
| | DEVICES SHALL BE INTERCONNECTED IN SUCH |
| | A MANNER THAT THE ACTUATION OF ONE ALARM |
| | WILL ACTIVATE ALL OF THE ALARMS IN THE |
| | INDIVIDUAL UNIT. THE ALARM SHALL BE |
| | CLEARLY AUDIBLE IN ALL BEDROOMS OVER |
| | BACKGROUND NOISE LEVELS WITH ALL |
| | INTERVENING DOORS CLOSED. |
| | ALL SMOKE ALARMS SHALL BE LISTED AND |
| | INSTALLED IN ACCORDANCE WITH THE |
| | PROVISIONS OF THIS CODE AND THE |
| | HOUSEHOLD FIRE WARNING EQUIPMENT |
| | PROVISIONS OF NFPA 72. |
| | |
| | J.SAFETY GLASS REQUIRED IN WINDOWS IN |
| | BATHROOM NEAR TUB LOCATIONSR-308.1 |
| | |
| | K.SCOPE OF WORK IS STILL NOT CLEAR AND |
| | DOES NOT MATCH PERMIT APPLICATION. |
| | CLEARLY SHOW ON PLANS AREAS THAT WILL |
| | NOT HAVE ANY WORK DONE AND SHOW AS |
| | EXISTING.APPLICATION SHOWS ROT REPAIR |
| | YET PLANS SHOW FIRE DAMAGE? |
| | |
| | L.THOSE PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.WPB |
| | AMENDMENT TO FBC 106.3.3. |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| | OLD PAGES FOR REFERENCE. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ART LANGE |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | BUILDING PLANS EXAMINER |
| | 561-805-6672 |