| Plan Review Notes For Permit 06040040 |
| Permit Number |
06040040 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-19 00:00:00 | *** DENIED *** | | | 1) AS REQUESTED IN LAST REVIEW 4-10-06 | | | NOTE #1, ENERGY CALCULATIONS NEED TO BE | | | SIGNED BY THE PREPARER ALSO. | | | | | | 2) AS REQUSTED IN LAST REVIEW 4-10-06 | | | NOTE #2 ENERGY CALCULATIONS ARE CALLING | | | FOR UNIT #2 HEATER TO BE 5 KW, | | | MECHANICAL PLANS ARE CALLING FOR UNIT #2 | | | HEATER TO BE 8.5 KW, THE TWO MUST | | | COINSIDE PLEASE CORRECT THE ENERGY | | | CAL'S. OR THE MECHANICAL PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|