| Plan Review Notes For Permit 06040040 |
| Permit Number |
06040040 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-14 00:00:00 | PAGE 5-7 | | | | | | RISER SHOWS TWO MAINS OFF ONE RISER | | | WIRE IS GOOD FOR 200A, HOW IS SECOND | | | METER FED? | | | | | | NO PANEL SCHEDULE SHOWN FOR SECOND | | | PANEL.NO LOAD CALCULATION SHOWN FOR | | | THE SPACE INVOLVED!!!!!!!!! | | | | | | NO LOAD CALCULATION FOR BOTH UNITS SHOWN | | | PER NEC. | | | | | | YOU HAVE TWO PAGES 5-7 PLEASE CHANGE ONE | | | OR YOU WILL FAIL AGAIN. | | | | | | IF STORAGE UNIT IS FOR BOTH TENANTS YOU | | | NEED A SEPARATE METER AND PANEL FOR THAT | | | ROOM!!!! | | | | | | CHECK YOUR LOAD CALCULATIONS SHOW THAT | | | BOTH UNITS ARE 1200 SQFT??????????????? | | | | | | NEED THE PERSON WHO DESIGNED THIS PLAN | | | TO SIGN IT AND DATE IT. |
|