| Plan Review Notes For Permit 06040040 |
| Permit Number |
06040040 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-11 00:00:00 | DENIED; | | | 1.SANITARY RISER DIAGRAM AND FLAT | | | DRAWING DO NOT MATCH; | | | A.FIRST FLOOR TUB AND SHOWER ARE | | | | | | NOT VENTED. | | | B.FLAT DRAWING, SECOND FLOOR BATH- | | | ROOM SHOWER IS NOT VENTED. | | | C. KITCHEN SINK SHOULD BE DOWN | | | STREAM OF BATHROOM GROUP SEC. | | | 909.1 | | | D. RISER DIAGRAM DOES NOT MATCH | | | FLOOR PLAN. | | | 2. PLANS ARE BEING REVIEW UNDER THE | | | FBC-2004 EDITION NOT 2001 PLEASE CHANGE | | | NOTES. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|