Text |
| 2006-04-11 00:00:00 | ********** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE CORRELATE ELECTRICAL |
| | PLANS WITH LOAD CALCUALTIONS SUBMITTED. |
| | PLEASE SEE PLANS INDICATE THREE LTS. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE COMPLETE MIN WIRING ON |
| | ELECTRICAL WIRING DIAGRAM FOR EQUIPMENT. |
| | PLEASE SEE PUMP, HEATER, ETC DO NOT |
| | INDICATE ANY SIZES ETC. |
| | 240.4,310.16,215.5 |
| | |
| | 3) NOTE: PLEASE SEE SPECS SUBMITTED FOR |
| | POOL HEATERARE FOR A GAS HEATER AND |
| | PLANS MENTIONS AN ELECTRICAL HEAT PUMP? |
| | PLEASE ADJUST PLANS,OR LOADS AND PANEL |
| | SCHEDULE ACCORDINGLY. |
| | PLEASE SUBMIT SPECS FOR THE HEAT PUMP |
| | BEING INSTALLED IN THIS HOUSE AND FOR |
| | THIS JOB. SPECS AND CALCS SHALL NOT BE |
| | GENERIC AS THE CODE REQUIRES EACH |
| | JOBSITE SCOPE TO BE SPECIFIC. |
| | ALL SPECS SHALL INDICATE A NRTL. |
| | 215.5 |
| | |
| | 4) NOTE: PLEASE SEE HEATER AS LISTED ON |
| | PANEL SCHEDULE SHOWS 2-POLE 60A ON#8. |
| | PLEASE SEE 240.4,310.16,240.6, AS THIS |
| | MUST BE # 6 AWG OR LARGER. |
| | |
| | 5) NOTE: PLEASE INDICATE ALL CONTINUOUS |
| | LOADS AT 125%. LOADS ONLY SHOWTHE |
| | LARGEST MOTOR LOAD AT 125%. |
| | PLEASE KNOW THE HEAT PUMP WILL RUN 3 OR |
| | MORE HRS AND WILL BE CONSIDERED |
| | CONTINUOUS. 215.3,230.42 |
| | |
| | 6) NOTE: PLEASE SEE PLANS MISSING THE |
| | REQUIRED EQUIPMENT GROUNDING CONDUCTOR |
| | FEEDING NEW SUB PANEL. |
| | |
| | 7) NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR THE EXISTING SERVICE AND THE |
| | ADDITION OF THE NEW LOADS. PLEASE SEE |
| | ONLY THE LOADS FOR THE NEW SUB PANEL |
| | WERE SUBMITTED AND NO INFORMATION FOR |
| | SIZE AND EXISTING PANEL/SERVICE LOAD WAS |
| | GIVEN. |
| | 220.31B,215.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |