| Date |
Text |
| 2007-07-30 11:07:16 | |
| | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE THAT THE DESIGNER OF RECORD SHALL |
| | SIGN PLANS. IF THE DESIGNER OF RECORD HAS CHANGED |
| | PLEASE SUBMIT NOTARIZED LETTERS FOR CHANGE OF |
| | DESIGNER. |
| | FBC 106.1.2 |
| | FS 481, 471, 489 |
| | |
| | 2) NOTE: PLEASE SHOW A REVISED ELECTRICAL RISER |
| | DIAGRAM. PLEASE INCLUDE THE EQUIPMENT GROUNDING |
| | CONDUCTOR TO NEW SUB PANEL. |
| | PLEASE SEE 250.122, 250.110 ETC. |
| | |
| | 3) NOTE: PLEASE SUBMIT A LAYOUT OF THE NEW SMOKE ALARMS |
| | IN DWELLING INSIDE AND OUTSIDE SLEEPING ROOMS. |
| | R313, NFPA-72 11.5.1.1, 11.8.3 |
| | PLEASE SHOW LOCATIONS. |
| | |
| | 4) NOTE: PLEASE SPECIFY NEW LIGHTS IN CLOSET AS THE |
| | SYMBOL/FIXTURE LEGEND DOES NOT CORRELATE OR INDICATE |
| | TYPE OF FIXTURE. BASED ON SCALE ON PLANS AND LOCATIONS, |
| | IT NOT APPEAR 410.8 IS MET? |
| | |
| | 5) NOTE: PLEASE SEE PLANS NOW INCLUDE THE RELOCATED CU |
| | YET NOT GFI IS SHOWN FOR THIS AS REQUIRED PER 210.63, |
| | 210.8A |
| | |
| | 6) NOTE: PLEASE REVISE LOAD CALCULATIONS TO COORDINATE |
| | WITH PANEL SCHEDULE. SEE KITCHEN SMALL APPLIANCE |
| | CIRCUITS FOR EXAMPLE. |
| | PLEASE SEE 210.52B1, 210.11C1, 220.16. |
| | |
| | 7) NOTE: PLEASE SEE REDLINED PLANS AS OF OCT 06 |
| | REQUIRED THE PANEL SCHEDULE TO BE REVISED TO BE |
| | SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. |
| | *PLEASE SEE 408.4. *SECTION 408.4 WAS REVISED FOR THE |
| | 2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | |
| | |
| | * PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |