Plan Review Notes
Plan Review Notes For Permit 06031571
Permit Number 06031571
Review Stop P
Sequence Number 3
Notes
Date Text
2007-07-30 07:34:46DENIED;
 1. REVISIONS MUST BE APPROVED, SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD.
 2. A SANITARY RISER DIAGRAM IS REQUIRED, SEE FBC-2004
 BUILDING CHAPTER 1 ADMIINISTRATION AMENDMENTS SECTION
 106.3.5.4( 9).
 3. AUTOMATIC CLOTHES WASHER BRANCH DRAIN MUST DISCHARGE
 UP OR DOWN STREAM OF THE BATHROOM GROUP. SEE FBC-2004
 PLUMBING SECTION 909.1.
 4. AUTOMATIC CLOTHES WASHER TO BE 3" NOT 2" SEE SECTION
 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695