| 2006-06-21 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE THE RECEPT FOR NEW |
| | WASHER IS NOT SHOWN ON PLANS. PANEL |
| | SCHEDULE ETC SHOWS NEW , HOWEVER NOT |
| | SHOWN. |
| | PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS |
| | 40A OCP FOR THE RANGE WHICH IS BEING |
| | SHOWN AS 12KW. PLEASE KNOW, WITH THE |
| | LOAD SHOWN AS 12KW, THE 40A CIRUIT AS |
| | SHOWN EXCEEDS SAFE OPERATION AND OCP FOR |
| | PROTECTION OF BRANCH CIRCUIT. |
| | 240.4,310.16.ETC. |
| | PLEASE VERIFY AND ADJUST. |
| | |
| | 3) NOTE: PLEASE SEE BATH RECEPTS SHALL |
| | BE GFI/ GFI PROTECTED PER 210.8A1 |
| | |
| | 4) NOTE: PLEASE CORRELATE WATER HEATER |
| | SHOWN ON PANEL SCHEDULE AND KW RATING ON |
| | LOAD CALCULATIONS. |
| | PLEASE SEE ONE SHOWS 4.5 KW AND THE |
| | OTHER SHOWS 3KW? |
| | PLEASE BE SURE TO SEE IF THE KW IS |
| | 4500VA, THEN PLEASE ADJUST OCP AND AWG |
| | SIZES. PER 240.4,310.16 ETC |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE VERIFY CIRCUITING AS |
| | SHOWN. PLEASE SEE MAX VA PERMITTED ON |
| | #14AWG AND 15A OCP. PLEASE SEE A MAX OF |
| | 1440VA. |
| | 215.5. PLEASE SEE OTHER CIRCUITS. |
| | |
| | 6) NOTE: PLEASE SEE NEC 2002 FOR CORRECT |
| | LOAD CALCULATIONS. PLEASE SEE SOME |
| | APPEAR TO BE SHOWN FOR COMMERCIAL AND |
| | SOME FOR RESIDENTIAL?? |
| | |
| | 7) NOTE: PLEASE SEE A LIGHTING CONTROL |
| | SWITCH WILL BE REQUIRED IN THE PATH OF |
| | EGRESS WHEN ENTERING THE LAUNDRY RM. |
| | PLEASE SEE A 3-WAY SW MAY BE USED TO ADD |
| | TO THE OTHER SW AS SHOWN. |
| | PLEASE KNOW, THE SWITCHING SHOULD BE |
| | LOCATED IN THE PATH OF EGRESS AND ALWAYS |
| | WITH THE DIRECTION OF EGRESS TRAVEL. |
| | 210.70, 2002 NEC, NFPA-101 CHAPT 24, |
| | CHAPT 8 7.8 |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFETC THE |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE PLANS REFLECT THE |
| | CURRENT CODES IN EFFECT 2004 FBC , 2002 |
| | NEC AT A MIN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |