Plan Review Notes
Plan Review Notes For Permit 06031571
Permit Number 06031571
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-12 00:00:00DENIED;
 1.ENGINEER'S PRINTED LICENSE NUMBER
 REQUIRED IN TITLE BLOCK PER. FAC
 61G15-23.002.
 2.HAND WRITEN ITEMS ON DRAWINGS ARE NOT
 EXCEPTABLE.
 3.AUTOMATIC CLOTHES WASHER DRAIN TO BE
 3" FBC-2004 SEC. 406.3.
 4.C.O. REQUIRED ON W/M STACK AT 48" AFF.
 5.W/M DISCHARGE SHALL BE DOWN STREAM OF
 THE BATHROOM GROUP. LAVATORY VENT SHOULD
 BE UP STREAM OF SHOWER SO SHOWER IS
 VENTED. SEC. 909.1.
 6.THERMAL EXPANSION CONTROL IS REQUIRED
 PER SEC.607.3 LIST ON PLANS MEANS OF
 CONTROL.
 7.A TWO WAY CLEANOUT IS REQUIRED OUT
 SIDE NEW ADDITION BEFORE BUILDING SEWER
 TIE-IN. SEC.708.3.5