| Plan Review Notes For Permit 06031571 |
| Permit Number |
06031571 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-12 00:00:00 | DENIED; | | | 1.ENGINEER'S PRINTED LICENSE NUMBER | | | REQUIRED IN TITLE BLOCK PER. FAC | | | 61G15-23.002. | | | 2.HAND WRITEN ITEMS ON DRAWINGS ARE NOT | | | EXCEPTABLE. | | | 3.AUTOMATIC CLOTHES WASHER DRAIN TO BE | | | 3" FBC-2004 SEC. 406.3. | | | 4.C.O. REQUIRED ON W/M STACK AT 48" AFF. | | | 5.W/M DISCHARGE SHALL BE DOWN STREAM OF | | | THE BATHROOM GROUP. LAVATORY VENT SHOULD | | | BE UP STREAM OF SHOWER SO SHOWER IS | | | VENTED. SEC. 909.1. | | | 6.THERMAL EXPANSION CONTROL IS REQUIRED | | | PER SEC.607.3 LIST ON PLANS MEANS OF | | | CONTROL. | | | 7.A TWO WAY CLEANOUT IS REQUIRED OUT | | | SIDE NEW ADDITION BEFORE BUILDING SEWER | | | TIE-IN. SEC.708.3.5 |
|