Plan Review Notes
Plan Review Notes For Permit 06031571
Permit Number 06031571
Review Stop M
Sequence Number 1
Notes
Date Text
2006-04-11 00:00:00*** DENIED ***
 1) ENGINEER'S PRINTED LICENSE NUMBER
 MUST APPEAR IN THE TITLE BLOCK, PER FAC
 61G15-23.002 .
  
 2) PLEASE SHOW THE SIZE OF THE DUCT FROM
 THE EXISTING TRUNK LINE TO THE MIXING
 BOX (IF FLEX) OR SHOW AS A RIDGE DUCT.
  
 3) PLEASE SHOW BATHROOM EXHAUST FAN ON
 MECHANICAL PLANS.
  
 4) PLEASE SHOW THE CLOTHES DRYER VENT ON
 MECH. PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.