2006-04-11 00:00:00************ UNSAT *****************
  
 1) NOTE: PLEASE SEE PLAN SETS CONTAIN
 MANY AREAS ON ELECTRICLA AND OTHER
 SHEETS WHICH CONTAIN "HAND-DRAWN" ITEMS
 ON PLANS WHICH ARE SIGNED, DATED AND
 SEALED BY AN ENGINEER. PLEASE SEE FS
 471.025, THIS IS NOT PERMITTED AND WILL
 NOT BE ACCEPTED. PLEASE HAVE SHEETS
 RE-PRINT WITH CHANGES AND ANY
 CORRECTIONS FROM PLAN REVIEW COMMENTS.
 215.5
 ** PLEASE KNOW, THIS COMMENTS IS FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE RISER MENTIONS NEW
 #10 FOR DRYER AND WATER HEATER, HOWEVER
 PLEASE SEE THE "BRIEF" PANEL SCHEDULE
 PROVODED DOES NOT CORRELATE WITH THIS.
 ALL CIRCUITS ON THE 4 CIRCUIT SCHEDULE
 SHOWS ONLY 1-POLE 20A CIRCUITS???
  
 A) PLEASE SEE 220.18 FOR MIN KW AND
 CIRCUIT RATING FOR DRYER.
 240.4,310.16
  
 B) PLEASE SEE 422.13 FOR MIN SIZE AND
 OCP FOR WATER HEATER, 125% FOR
 NAMEPLATE.
  
 PLEAS ADJUST CONDUCTOR AND OCP SIZES.
  
 3) NOTE: PLEASE VERIFY ON PLANS IF NEW
 LOADS ARE TAKING THE PLACE OF THE
 EXISTING WASHER, DRYER, WATER HEATER OR
 ARE THESE NEW ADDTIONAL LOADS.
 PLEASE PROVIDE MIN LOAD CALCUALTIONS FOR
 NEW ADDED LOADS.
 215.5,220
  
 4) NOTE: PLEASE SEE WATER HEATER IS
 BEING SHOWN WITH A RECEPT FOR
 DISCONNECT/PLUG IN OF UNIT. PLEASE SEE
 422.30 AS A DISCONNECTING MEANS IS
 REQUIRED AND MAY NOT PLUG IN UNIT.
  
 5) NOTE: PELASE INCLUDE ANY NEW GFI
 RECEPTS ON PLANS (PRINTED) NOT DRAWN.
 210.52D, 210.8A1,3 ETC.
  
 6) NOTE: PLEASE SEE ELECTRICAL SYMBOL
 LEGEND, SHOWS 125A PANELAND RISER AND
 PLANS MENTIONS 200A PANEL EXISTING?
 PLEASE CORRELATE
  
 7) NOTE: PLEASE SEE FBC R313, FOR SD'S
 TO BE ADDED TO THE EXISTING DWELLING FOR
 THE LEVEL OF ALTERATION TO THE EXISTING
 BUILDING.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  