| 2006-04-11 00:00:00 | ************ UNSAT ***************** |
| | |
| | 1) NOTE: PLEASE SEE PLAN SETS CONTAIN |
| | MANY AREAS ON ELECTRICLA AND OTHER |
| | SHEETS WHICH CONTAIN "HAND-DRAWN" ITEMS |
| | ON PLANS WHICH ARE SIGNED, DATED AND |
| | SEALED BY AN ENGINEER. PLEASE SEE FS |
| | 471.025, THIS IS NOT PERMITTED AND WILL |
| | NOT BE ACCEPTED. PLEASE HAVE SHEETS |
| | RE-PRINT WITH CHANGES AND ANY |
| | CORRECTIONS FROM PLAN REVIEW COMMENTS. |
| | 215.5 |
| | ** PLEASE KNOW, THIS COMMENTS IS FOR ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE SEE RISER MENTIONS NEW |
| | #10 FOR DRYER AND WATER HEATER, HOWEVER |
| | PLEASE SEE THE "BRIEF" PANEL SCHEDULE |
| | PROVODED DOES NOT CORRELATE WITH THIS. |
| | ALL CIRCUITS ON THE 4 CIRCUIT SCHEDULE |
| | SHOWS ONLY 1-POLE 20A CIRCUITS??? |
| | |
| | A) PLEASE SEE 220.18 FOR MIN KW AND |
| | CIRCUIT RATING FOR DRYER. |
| | 240.4,310.16 |
| | |
| | B) PLEASE SEE 422.13 FOR MIN SIZE AND |
| | OCP FOR WATER HEATER, 125% FOR |
| | NAMEPLATE. |
| | |
| | PLEAS ADJUST CONDUCTOR AND OCP SIZES. |
| | |
| | 3) NOTE: PLEASE VERIFY ON PLANS IF NEW |
| | LOADS ARE TAKING THE PLACE OF THE |
| | EXISTING WASHER, DRYER, WATER HEATER OR |
| | ARE THESE NEW ADDTIONAL LOADS. |
| | PLEASE PROVIDE MIN LOAD CALCUALTIONS FOR |
| | NEW ADDED LOADS. |
| | 215.5,220 |
| | |
| | 4) NOTE: PLEASE SEE WATER HEATER IS |
| | BEING SHOWN WITH A RECEPT FOR |
| | DISCONNECT/PLUG IN OF UNIT. PLEASE SEE |
| | 422.30 AS A DISCONNECTING MEANS IS |
| | REQUIRED AND MAY NOT PLUG IN UNIT. |
| | |
| | 5) NOTE: PELASE INCLUDE ANY NEW GFI |
| | RECEPTS ON PLANS (PRINTED) NOT DRAWN. |
| | 210.52D, 210.8A1,3 ETC. |
| | |
| | 6) NOTE: PLEASE SEE ELECTRICAL SYMBOL |
| | LEGEND, SHOWS 125A PANELAND RISER AND |
| | PLANS MENTIONS 200A PANEL EXISTING? |
| | PLEASE CORRELATE |
| | |
| | 7) NOTE: PLEASE SEE FBC R313, FOR SD'S |
| | TO BE ADDED TO THE EXISTING DWELLING FOR |
| | THE LEVEL OF ALTERATION TO THE EXISTING |
| | BUILDING. |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |