Text |
| 2006-05-09 00:00:00 | ******** UNSAT *********** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED ALONG |
| | WITH SOME NEW COMMENTS DUE TO CHANGES IN |
| | PLANS MADE. |
| | |
| | 1) NOTE: NOTE #1, PLEASE SEE A SCHEDULE |
| | WAS PROVIDED , |
| | PLEASE SEE LOAD FOR AHU/ CU ON PANEL |
| | SCHEDULE, PLEASE CLARIFY WHERE HEAT LOAD |
| | IS ? WHEN THIS IS UNDER NORMAL POWER |
| | HEAT IS BEING FED FROM SOMEWHERE? OR IS |
| | HEAT NOW BEING COMPLETELY REMOVED.? |
| | PLEASE SEE OCP FOR DRYER IS SHOWN AT |
| | 40A'S FOR 5KW? |
| | PLEASE KNOW, GEN LT, APPL, RECEPTS MAY |
| | BE DERATED, ONLY THE HEAT MUST BE |
| | FIGURED AT 100%, UNLESS LOAD SHEDDING IS |
| | USED. |
| | |
| | ** PREVIOUS REVIEW ** |
| | PLEASE SEE PLEASE PROVIDE A SCHEDULE FOR |
| | THE TRANSFER PANEL FOR INTENDED LOADS |
| | AND PLEASE CLARIFY AHU LOAD. UNLESS |
| | AUTOMATIC LOAD SHEDDING IS DETAILED AND |
| | PROVIDED, AHU HEAT SHALL BE FIGURED AT |
| | 100%. |
| | 220, 702.5 |
| | PLEASE KNOW, MANY OF THE PRE-WIRED |
| | PANELS DO NOT CONTAIN THE OCP WHICH MAY |
| | BE NEEDED FOR THE INTENDED LOADS AND |
| | ALTERATION OF LISTED EQUIPMENT IS NOT |
| | PERMITTED. |
| | |
| | 2) NOTE: NOTE #2 NO, PLEASE SEE PLANS |
| | ARE RE-DRAWN AND ARE OK, HOWEVER PLEASE |
| | SEE RISER DOES NOT INDICATE A |
| | DISCONNECT? |
| | SOMETHING IS SHOWN, BUT NOT CLEAR WHAT |
| | THIS IS? |
| | |
| | ** PREVIOUS REVIEW ** |
| | PLEASE RE-DRAWN RISER WITH OUT |
| | HAND DRAWN AND WHITE-OUT CHANGES. PLEASE |
| | INCLUDE DISCONNECTING MEANS FROM |
| | GENERATOR TO MAIN HOUSE AND THIS |
| | DISCONNECTING MEANS SHALL BE GROUPED |
| | WITH THE EXISTING MAIN. |
| | 225.31-225.39. |
| | |
| | 3) NOTE:OK.P |
| | |
| | 4) NOTE:NOTE #4, PLEASE SEE SPECS |
| | SUBMITTED FOR PANEL/ ATS DOES NOT |
| | CORRELATE WITH PLANS AND UNIT BEING |
| | INSTALLED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SUBMIT SPECS FOR ATS/ |
| | PANEL BEING INSTALLED. |
| | PLEASE INDICATE THE AIC RAITNG FOR ATS. |
| | NFPA-110, 6.5.2, NEC 110.9 |
| | 215.5 |
| | |
| | 5) NOTE: NOTE #5 OK, BE SURE ALL REVISED |
| | ARE SIGNED ALSO. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE BE SURE ALL SHEETS |
| | CONTAIN THE PRINTED NAME AND THE |
| | SIGNATURE OF THE PERSON TAKING |
| | RESPONSIBILITY FOR PLANS AND DESIGN. |
| | |
| | ** NEW NOTE ** |
| | 1)NOTE: PLEASE SEE CALCS SHOW CITY OF |
| | "PALM BEACH GARDENS"? PLEASE ADJUST. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW., IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |