| 2006-04-12 00:00:00 | ******** UNSAT *********** |
| | |
| | 1) NOTE: PLEASE PROVIDE A SCHEDULE FOR |
| | THE TRANSFER PANEL FOR INTENDED LOADS |
| | AND PLEASE CLARIFY AHU LOAD. UNLESS |
| | AUTOMATIC LOAD SHEDDING IS DETAILED AND |
| | PROVIDED, AHU HEAT SHALL BE FIGURED AT |
| | 100%. |
| | 220, 702.5 |
| | PLEASE KNOW, MANY OF THE PRE-WIRED |
| | PANELS DO NOT CONTAIN THE OCP WHICH MAY |
| | BE NEEDED FOR THE INTENDED LOADS AND |
| | ALTERATION OF LISTED EQUIPMENT IS NOT |
| | PERMITTED. |
| | |
| | 2) NOTE: PLEASE RE-DRAWN RISER WITH OUT |
| | HAND DRAWN AND WHITE-OUT CHANGES. PLEASE |
| | INCLUDE DISCONNECTING MEANS FROM |
| | GENERATOR TO MAIN HOUSE AND THIS |
| | DISCONNECTING MEANS SHALL BE GROUPED |
| | WITH THE EXISTING MAIN. |
| | 225.31-225.39. |
| | |
| | 3) NOTE: PLEASE INCLUDE LOCATIONS OF ALL |
| | SERVICE EQUIPMENT AS SHOWN ON RISER ON |
| | THE PROVIDED SITE LAYOUT. PLEASE SEE |
| | PLANS, AT CURRENT TIME ONLY INDICATE THE |
| | ATS ON THE OUTSIDE OF DWELLING. |
| | 215.5 |
| | |
| | 4) NOTE: PLEASE SUBMIT SPECS FOR ATS/ |
| | PANEL BEING INSTALLED. |
| | PLEASE INDICATE THE AIC RAITNG FOR ATS. |
| | NFPA-110, 6.5.2, NEC 110.9 |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE BE SURE ALL SHEETS |
| | CONTAIN THE PRINTED NAME AND THE |
| | SIGNATURE OF THE PERSON TAKING |
| | RESPONSIBILITY FOR PLANS AND DESIGN. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW., IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |