Plan Review Notes
Plan Review Notes For Permit 06031563
Permit Number 06031563
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-13 00:00:00DENIED;
 1.PAGE 4 SIZE ROOF SCUPPER AND EMERGENCY
 SCUPPERS USING FBC-2004 PLUMBING TABLE
 1106.7. SHOW CAULK'S.
 2.EMERGENCY SCUPPERS TO BE 2" TO 4"
 ABOVE FINISH ROOF. IN SOME ELEVATION
 VIEWS EMERGENCY SCUPPERS ARE THE SAME
 HIGHT AS SCUPPERS. SHOW TOTAL SQ.INS. OF
 OPEN AREA.
 3.SANITARY RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN, AND CODE VIOLATIONS EXIST.
 4.SECOND FLOOR FIXTURES CANNOT DUMP INTO
 THE VENT OF THE FIRST FLOOR FIXTURES.
 5.SHOWERS ARE NOT VENTED (WHERE
 HIGHLIGHTED)
 6.C.O. REQUIRED ON WASHER STACK 48"
 AFF.
 7.PRINTED AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLANS IS REQUIRED BY
 FBC-2004 CHAPTER 1 ADMINISTRATION CODE
 SEC.106.3.4.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695