| Date |
Text |
| 2006-04-11 00:00:00 | ************ UNSAT *************** |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETE PANEL |
| | SCHEDULES WITH ALL MININNUM REQUIRED |
| | DEDICATED CIRCUITS AND ALL CIRCUITS |
| | SHOWN ON PLANS WITH MIN OCP, AWG PER |
| | 240.4,310.16,215.5 |
| | THERE ARE MANY ITEMS MISSING AT THIS |
| | TIME TO LIST ALL. |
| | |
| | 2) NOTE: PLEASE SUBMIT LOAD CALCUALTIONS |
| | WHICH MEET THE MININUM NEC COMPLIANCE TO |
| | 2002 NEC 220.31B. |
| | PLEASE KNOW, THE LOADS AS SHOWN ARE NOT |
| | COMPLIANT. |
| | |
| | 3) NOTE: PLEASE SHOW AND INDICATE ALL |
| | AREA AND ROOM DESIGNATIONS ON ELECTRICAL |
| | PLANS. |
| | THISWILL AFFECT REVIEW FOR CODE |
| | COMPLIANCE OF AREAS. |
| | 215.5 |
| | |
| | 4) NOTE: PLEASE SEE NUMEROUS MISSING |
| | RECEPTS PER 210.52 |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | HALLWAYS PER 210.52H |
| | |
| | 6) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52E |
| | |
| | 7) NOTE: PLEASE SEE NOTE WHICH MENTIONS |
| | RECEPTS W/IN 15' OF POOL TO BE GFI DOES |
| | NOT MEET 680.22 |
| | |
| | 8) NOTE: PLEASE SEE NOET WHICH MENTIONS |
| | RECEPTS W/ IN 6' OF KITCHEN SINK TO BE |
| | GFI IS FROM THE "1993" NEC.PLEASE |
| | KNOW, THE REQUIREMENTS FOR KITCHEN |
| | COUNTERSPACE RECEPTS CHANGED IN 1996. |
| | PLEASE SEE 210.8A6, 2002 |
| | |
| | 9) NOTE: PLEASE SEE MISSING DISCONNECTS |
| | FOR ALL A/C EQUIPMENT, CU'S AND AHU'S |
| | NEW AND EXISTING ARE TO BE SHOWN WITH |
| | MIN CLEARENCES. |
| | 440.11,110.26, 215.5 |
| | |
| | 10) NOTE: PLEASE CLARIFY GFI RECEPT |
| | BEHIND EACH CU AND GEN? THIS IS OK, |
| | HOWEVER UNCLEAR? |
| | |
| | 11) NOTE: PLEASE SEE GENERATOR SHOWN ON |
| | PLANS CAN NOT BE PART OF THIS PERMIT AS |
| | NO INFORMATION WAS SUBMITTED FOR UNIT |
| | NOR IS IT SHOWN IN THE ELECTRICAL RISER |
| | DIAGRAM. |
| | PLEASE REMOVE FROM PLANS, OR SUBMIT ALL |
| | INFORMATION AND COMPLETE PLANS FOR |
| | INSTALLATION. |
| | 215.5 |
| | |
| | 12) NOTE: PLEASE SEE THAT ALL CURRENT |
| | APPLICABLE CODES ARE NOTED ON ELECTRICAL |
| | PLANS. |
| | 2002 NFPA-70 ( NEC ) , 2002 NFPA-72 |
| | |
| | 13) NOTE: PLEASE SEE NFPA-72 11.5.1.1 |
| | FOR ALL MIN LOCATIONS REQUIRED FOR SD'S. |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS, |
| | LOCATED IN THE IMMEDIATE VICINITY OF |
| | BEDRM DOORS AND LOCATED ON EACH LEVEL OF |
| | A MULTI-LEVEL RESIDENCE IN CLOSE |
| | PROXIMITY LEADING TO THE FLR ABOVE AND |
| | ON 2DN FLR LEVEL AT THE TOP OF STAIRS. |
| | PLEASE ALSO SEE 11.8.3.5 FOR OTHER |
| | LOCATIONS PERMITTED AND LOCATIONS NOT |
| | PERMITTED. |
| | |
| | 14) NOTE: PLEASE SHOW THE LOCATION OF |
| | THE METER/SERVICE. |
| | 215.5 |
| | |
| | 15) NOTE: PLEASE SEE PLANS INDICATE A |
| | TANKLESS WH, YET THIS IS NOT ON PANEL |
| | SCHEDUL, LOADSETC? |
| | 215.5 |
| | |
| | 16) NOTE: PLEASE SEE THAT THE PLANS |
| | SHALL CONTAINTHE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | PLANS AND DESIGN. |
| | FBC ADMINISTRATIVE CODE. |
| | 106.3.4.3 |
| | PLANS SHALL CONTAIN ALL INFORMATION FOR |
| | CODE COMPLIANCE AS SET FORTH BY THE FBC |
| | 2004, AND NATIONAL ELECTRICAL CODE. |
| | PLANS MAY BE REQUIRED TO BE DONE BY A |
| | LICENSED DESIGN PROFESSIONAL FOR |
| | COMPLIANCE. 106.1.2, 106.3.5.4 |
| | |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT THE NEW REVISEDSHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE COPY OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE ONLY. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |