Plan Review Notes
Plan Review Notes For Permit 06031563
Permit Number 06031563
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-11 00:00:00************ UNSAT ***************
  
 1) NOTE: PLEASE SUBMIT COMPLETE PANEL
 SCHEDULES WITH ALL MININNUM REQUIRED
 DEDICATED CIRCUITS AND ALL CIRCUITS
 SHOWN ON PLANS WITH MIN OCP, AWG PER
 240.4,310.16,215.5
 THERE ARE MANY ITEMS MISSING AT THIS
 TIME TO LIST ALL.
  
 2) NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 WHICH MEET THE MININUM NEC COMPLIANCE TO
 2002 NEC 220.31B.
 PLEASE KNOW, THE LOADS AS SHOWN ARE NOT
 COMPLIANT.
  
 3) NOTE: PLEASE SHOW AND INDICATE ALL
 AREA AND ROOM DESIGNATIONS ON ELECTRICAL
 PLANS.
 THISWILL AFFECT REVIEW FOR CODE
 COMPLIANCE OF AREAS.
 215.5
  
 4) NOTE: PLEASE SEE NUMEROUS MISSING
 RECEPTS PER 210.52
  
 5) NOTE: PLEASE SEE MISSING RECEPTS FOR
 HALLWAYS PER 210.52H
  
 6) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52E
  
 7) NOTE: PLEASE SEE NOTE WHICH MENTIONS
 RECEPTS W/IN 15' OF POOL TO BE GFI DOES
 NOT MEET 680.22
  
 8) NOTE: PLEASE SEE NOET WHICH MENTIONS
 RECEPTS W/ IN 6' OF KITCHEN SINK TO BE
 GFI IS FROM THE "1993" NEC.PLEASE
 KNOW, THE REQUIREMENTS FOR KITCHEN
 COUNTERSPACE RECEPTS CHANGED IN 1996.
 PLEASE SEE 210.8A6, 2002
  
 9) NOTE: PLEASE SEE MISSING DISCONNECTS
 FOR ALL A/C EQUIPMENT, CU'S AND AHU'S
 NEW AND EXISTING ARE TO BE SHOWN WITH
 MIN CLEARENCES.
 440.11,110.26, 215.5
  
 10) NOTE: PLEASE CLARIFY GFI RECEPT
 BEHIND EACH CU AND GEN? THIS IS OK,
 HOWEVER UNCLEAR?
  
 11) NOTE: PLEASE SEE GENERATOR SHOWN ON
 PLANS CAN NOT BE PART OF THIS PERMIT AS
 NO INFORMATION WAS SUBMITTED FOR UNIT
 NOR IS IT SHOWN IN THE ELECTRICAL RISER
 DIAGRAM.
 PLEASE REMOVE FROM PLANS, OR SUBMIT ALL
 INFORMATION AND COMPLETE PLANS FOR
 INSTALLATION.
 215.5
  
 12) NOTE: PLEASE SEE THAT ALL CURRENT
 APPLICABLE CODES ARE NOTED ON ELECTRICAL
 PLANS.
 2002 NFPA-70 ( NEC ) , 2002 NFPA-72
  
 13) NOTE: PLEASE SEE NFPA-72 11.5.1.1
 FOR ALL MIN LOCATIONS REQUIRED FOR SD'S.
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS,
 LOCATED IN THE IMMEDIATE VICINITY OF
 BEDRM DOORS AND LOCATED ON EACH LEVEL OF
 A MULTI-LEVEL RESIDENCE IN CLOSE
 PROXIMITY LEADING TO THE FLR ABOVE AND
 ON 2DN FLR LEVEL AT THE TOP OF STAIRS.
 PLEASE ALSO SEE 11.8.3.5 FOR OTHER
 LOCATIONS PERMITTED AND LOCATIONS NOT
 PERMITTED.
  
 14) NOTE: PLEASE SHOW THE LOCATION OF
 THE METER/SERVICE.
 215.5
  
 15) NOTE: PLEASE SEE PLANS INDICATE A
 TANKLESS WH, YET THIS IS NOT ON PANEL
 SCHEDUL, LOADSETC?
 215.5
  
 16) NOTE: PLEASE SEE THAT THE PLANS
 SHALL CONTAINTHE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS AND DESIGN.
 FBC ADMINISTRATIVE CODE.
 106.3.4.3
 PLANS SHALL CONTAIN ALL INFORMATION FOR
 CODE COMPLIANCE AS SET FORTH BY THE FBC
 2004, AND NATIONAL ELECTRICAL CODE.
 PLANS MAY BE REQUIRED TO BE DONE BY A
 LICENSED DESIGN PROFESSIONAL FOR
 COMPLIANCE. 106.1.2, 106.3.5.4
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT THE NEW REVISEDSHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW