| 2006-09-27 00:00:00 | *** DENIED *** |
| | 1) PLEASE SEE 2004 FBC 13-101.5.1 |
| | EXISTING BUILDINGS EXCEPT THOSE |
| | CONSIDERED RENOVATED BUILDINGS. THIS |
| | PERMIT IS FOR A RENOVATED BUILDING . |
| | |
| | 2) AS REQUESTED IN LAST REVIEW 8-7-06. |
| | (1) ENERGY CALCULATIONS NEED TO BE |
| | SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC |
| | 13-600.3.ABC.2 . |
| | |
| | (2) PLEASE SUBMIT MANUAL D |
| | CALCULATIONS FOR RESIDENTIAL DUCT |
| | DESIGN, PER 2004 FBC/R M1601.1 AND FBC |
| | 13-610.1.ABC.1 . (10" SUPPLY TRUNK LINE |
| | APPEARS TO SMALL FOR 955 CFM'S). PLEASE |
| | BE ADVISED THERE ARE NO EXEMPTIONS |
| | REGARDING MANUAL D CAL'S. IN THE 2004 |
| | FBC THAT I KNOW OF, AND THAT I DID NOT |
| | REQUEST A MANUAL J CAL. BE SUBMITTED IN |
| | MY LAST REVIEW. |
| | |
| | (3) ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | SHALL BEAR THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. PER |
| | FBC 104.2.1 . (NO STAMPS). |
| | |
| | 3)SEE ATTACHED NOTICE FS 553.80(2)(B) |
| | REGARDING FOUR TIMES THE FEE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |