Plan Review Notes
Plan Review Notes For Permit 06031561
Permit Number 06031561
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-22 00:00:00****** PROVISO *******
  
  
 ***** REVISION NEEDED BEFORE ROUGH *****
  
  
 1) NOTE: PLEASE SEE MISSING PANEL
 SCHEDULE INDICATING ALL MINIMUM REQUIRED
 BRANCH CIRCUITS SHOWING THE OCP AND MIN
 CONDUCTOR SIZES PER 240.4,310.16,408.4
 **REQUESTED ON PREVIOUS REVIEWS**
  
 2) NOTE: PLEASE SEE BATH GFI MUST BE 20A
 #12 MIN PER 210.52D,210.11C3
 NOT INDICATED AT THIS TIME.
 **REQUESTED ON PREVIOUS REVIEWS**
  
 3) NOTE: PLEASE SEE 110.26 AS THE
 DISCONNECT FOR THE CU IS SHOWN BEHIND
 UNIT.
  
 4) NOTE: PLEASE SEE MISSING LAUNDRY
 CIRCUIT REQUIED PER 210.52F,210.11C2,
 220.16.
 ** REQUESTED ON PREVIOUS REVIEWS**
  
 PLEASE REVISE AND SUBMIT THE ABOVE ALONG
 WITH AMY OTHER REVISIONS BEFORE THE
 ROUGH ELECTRICAL INSPECTION IS CALLED
 IN.
 PLEASE KNOW, THE NEW REVISED STAMPED
 PLANS AFTER BEING REVIEWED, SHALL BE ON
 SITE FOR THE ROUGH INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]