| 2006-09-22 00:00:00 | ****** PROVISO ******* | | | | | | | | | ***** REVISION NEEDED BEFORE ROUGH ***** | | | | | | | | | 1) NOTE: PLEASE SEE MISSING PANEL | | | SCHEDULE INDICATING ALL MINIMUM REQUIRED | | | BRANCH CIRCUITS SHOWING THE OCP AND MIN | | | CONDUCTOR SIZES PER 240.4,310.16,408.4 | | | **REQUESTED ON PREVIOUS REVIEWS** | | | | | | 2) NOTE: PLEASE SEE BATH GFI MUST BE 20A | | | #12 MIN PER 210.52D,210.11C3 | | | NOT INDICATED AT THIS TIME. | | | **REQUESTED ON PREVIOUS REVIEWS** | | | | | | 3) NOTE: PLEASE SEE 110.26 AS THE | | | DISCONNECT FOR THE CU IS SHOWN BEHIND | | | UNIT. | | | | | | 4) NOTE: PLEASE SEE MISSING LAUNDRY | | | CIRCUIT REQUIED PER 210.52F,210.11C2, | | | 220.16. | | | ** REQUESTED ON PREVIOUS REVIEWS** | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE ALONG | | | WITH AMY OTHER REVISIONS BEFORE THE | | | ROUGH ELECTRICAL INSPECTION IS CALLED | | | IN. | | | PLEASE KNOW, THE NEW REVISED STAMPED | | | PLANS AFTER BEING REVIEWED, SHALL BE ON | | | SITE FOR THE ROUGH INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|