| Plan Review Notes For Permit 06031561 |
| Permit Number |
06031561 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-07 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT, PER 2004 FBC | | | 13-600.3.ABC.2 . | | | | | | 2) PLEASE SUBMIT MANUAL D CALCULATIONS | | | FOR RESIDENTIAL DUCT DESIGN, PER 2004 | | | FBC/R M1601.1 AND FBC 13-610.1.ABC.1 . | | | (10" SUPPLY TRUNK LINE APPEARS TO SMALL) | | | | | | 3) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|