2006-08-06 00:00:00***** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW.
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK, AS NO ARCHITECT IS BEING
 SHOWN ON TITLE BLOCKS FOR ELECTRICLA
 PLANS. PLANS ARE BEING DONE BY A
 DESIGNER/DRAFTMANS.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK. METER SHOWN IN FRONT OF THE
 PANEL 110.26
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS MENTIONS NEW
 PANEL BEING LOCATED OUTSIDE , HOWEVER
 PLANS ONLY SHOW THEMETER. PLEASE SHOW
 THE OUTDOOR PANEL.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: NO, UNCLEAR AS THERE IS A GFI
 CIRCUIT SHOWN, BUT NOT SURE OF THIS IS
 FOR THE BATHRM?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 DEDICATED BATH CIRCUIT PER 210.52D,
 210.11C3, MUST BE 20A AND #12.
  
 12) NOTE: NO, PLEASE SEE NOTE ON
 SCHEDULE NOW MENTIONS WASHER "OPT"
 PLEASE KNOW A LAUNDRY/WASHER CIRCUIT IS
 REQUIRED.210.11C2,220.16
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY WASHER AND DRYER AS PLANS
 SHOW A STACK UNIT AND PANEL/LOADS CALCS
 SHOWS INDIVIDUAL UNITS?
  
 13) NOTE: OK.
  
 14) NOTE:NO, PLEASE SEE REDLINED
 PLANS. PLEASE SEE NEW NOTE FOR KIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SOME MISSING
 RECEPTS PER 210.52 ONLY MISSING A FEW,
 THESE ARE REDLINED ON PLANS AT LOCATIONS
 NEEDED.
  
 15) NOTE: OK, SEEMS TO BE A CLOSET?
  
 16) NOTE: OK.
  
 17) NOTE: OK.
  
 18) NOTE:NO, PLEASE SEE ONLY THE 2002
 NEC WAS ADDED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOULD NOTE THE CURRENT
 CODE IN EFFECT. 2002 NEC , 2002 NFPA-72
  
 19) NOTE:NO, COULD NOT LOCATE THIS ON
 RISER OR PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE AIC RATINGS
 FOR NEW SERVICE EQUIPMENT/ MAINS. PER
 110.9/215.5
  
 ** NEW NOTES **
  
 20) NOTE: PLEASE SEE MISSING COUNTER
 SPACE GFI REQUIRED PER 210.52C1,210.8A6
  
 21) NOTE: PLEASE SEE MISSING RECEPT FOR
 DISPOAL AND DISHWASHER. PLEASE SEE IF
 THESE ARE GOING TO BE FED FROM THE SAME
 RECEPT, THEN A 2-POLE BRKR WILL BE
 REQUIRED. 210.4B
 PLEASE SHOW ON PLANS.
  
 22) NOTE: PLEASE SEE THE ONLY "PANEL
 SCHEDULE " BEING SUBMITTED IS ACTUALLY
 PART OF THE LOAD CALCULATIONS. PLEASE
 KNOW, ONE WILL BE REQUIRED SHOWING ALL
 UNLESS THE LOAD CALCS ARE SET UP TO
 INDICATE ALL.
 408.4, FBC 106.1.2
  
  
 ** WHEN RE-SUBMITTING PLANS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  