| 2006-08-06 00:00:00 | ***** UNSAT 2ND REVIEW ******* |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW. |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: OK, AS NO ARCHITECT IS BEING |
| | SHOWN ON TITLE BLOCKS FOR ELECTRICLA |
| | PLANS. PLANS ARE BEING DONE BY A |
| | DESIGNER/DRAFTMANS. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK. METER SHOWN IN FRONT OF THE |
| | PANEL 110.26 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS MENTIONS NEW |
| | PANEL BEING LOCATED OUTSIDE , HOWEVER |
| | PLANS ONLY SHOW THEMETER. PLEASE SHOW |
| | THE OUTDOOR PANEL. |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: NO, UNCLEAR AS THERE IS A GFI |
| | CIRCUIT SHOWN, BUT NOT SURE OF THIS IS |
| | FOR THE BATHRM? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH CIRCUIT PER 210.52D, |
| | 210.11C3, MUST BE 20A AND #12. |
| | |
| | 12) NOTE: NO, PLEASE SEE NOTE ON |
| | SCHEDULE NOW MENTIONS WASHER "OPT" |
| | PLEASE KNOW A LAUNDRY/WASHER CIRCUIT IS |
| | REQUIRED.210.11C2,220.16 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY WASHER AND DRYER AS PLANS |
| | SHOW A STACK UNIT AND PANEL/LOADS CALCS |
| | SHOWS INDIVIDUAL UNITS? |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE:NO, PLEASE SEE REDLINED |
| | PLANS. PLEASE SEE NEW NOTE FOR KIT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE SOME MISSING |
| | RECEPTS PER 210.52 ONLY MISSING A FEW, |
| | THESE ARE REDLINED ON PLANS AT LOCATIONS |
| | NEEDED. |
| | |
| | 15) NOTE: OK, SEEMS TO BE A CLOSET? |
| | |
| | 16) NOTE: OK. |
| | |
| | 17) NOTE: OK. |
| | |
| | 18) NOTE:NO, PLEASE SEE ONLY THE 2002 |
| | NEC WAS ADDED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOULD NOTE THE CURRENT |
| | CODE IN EFFECT. 2002 NEC , 2002 NFPA-72 |
| | |
| | 19) NOTE:NO, COULD NOT LOCATE THIS ON |
| | RISER OR PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE AIC RATINGS |
| | FOR NEW SERVICE EQUIPMENT/ MAINS. PER |
| | 110.9/215.5 |
| | |
| | ** NEW NOTES ** |
| | |
| | 20) NOTE: PLEASE SEE MISSING COUNTER |
| | SPACE GFI REQUIRED PER 210.52C1,210.8A6 |
| | |
| | 21) NOTE: PLEASE SEE MISSING RECEPT FOR |
| | DISPOAL AND DISHWASHER. PLEASE SEE IF |
| | THESE ARE GOING TO BE FED FROM THE SAME |
| | RECEPT, THEN A 2-POLE BRKR WILL BE |
| | REQUIRED. 210.4B |
| | PLEASE SHOW ON PLANS. |
| | |
| | 22) NOTE: PLEASE SEE THE ONLY "PANEL |
| | SCHEDULE " BEING SUBMITTED IS ACTUALLY |
| | PART OF THE LOAD CALCULATIONS. PLEASE |
| | KNOW, ONE WILL BE REQUIRED SHOWING ALL |
| | UNLESS THE LOAD CALCS ARE SET UP TO |
| | INDICATE ALL. |
| | 408.4, FBC 106.1.2 |
| | |
| | |
| | ** WHEN RE-SUBMITTING PLANS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |