| 2006-04-07 00:00:00 | *************** UNSAT *************** |
| | |
| | |
| | 1) NOTE: PLEASE SEE AN OWNER/ BUILDER |
| | PERMIT IS BEING APPLIED FOR , HOWEVER IT |
| | DOES APPEAR APPLICATION QUALIFIES FOR |
| | THE EXEMPTIONS UNDER FS 489. |
| | PLEASE SEE ATTACHED PRINT OUT FROM PALM |
| | BEACH COUNTY PROPERTY APPR'S OFFICE |
| | WHICH INDICATES NUMEROUS PROPERITES |
| | UNDER OWNERS INFORMATION INCLUDING WHAT |
| | IS BEING A USED A A PRIMARY RESIDENCE |
| | LOCATED IN PALM BEACH COUNTY. |
| | PLEASE ALSO KNOW, THIS OFFICE WILL |
| | VERIFY WITH THE OTHER JURISDICTIONS OF |
| | OWNED PROPERTIES TO ANY PERMITTED WORK |
| | FOR VERIFICATION OF O/B QUALIFICATION. |
| | ** IF IT IS THE INTEND TO LEASE/RENT OR |
| | SELL PROPERTY W/IN TIME LIMITS,OR NOT TO |
| | USE THIS PROPERTY FOR OWN USE AND |
| | OCCUPANCY,IT IS ADVISABLE TO OBTAIN A |
| | CONTRACTOR FOR SUCH PERMITTED WORK. |
| | |
| | 2) NOTE: PLEASE SEE SCOPE PF WORK |
| | MENTIONED ON APPLICATION AND SCOPE ON |
| | PLANS DO NOT CORRELATE. |
| | PLEASE ALSO SEE VALUE SHALL BE ADJUSTED |
| | FOR COMPLETE SCOPE PF REMODEL. THIS |
| | SHALL INCLUDE ALL LABOR AND MATERIALS. |
| | FBC ADMINISTRATIVE SECTION 108.3. |
| | PLEASE KNOW,IF AN APPROPRIATE VALUE IS |
| | NOT ADJUSTED, IT WILL BE ADJUSTED BY |
| | THIS OFFICE BASED ON FAIR MARKET VALUES |
| | SET FORTH IN THE FBC. |
| | |
| | 3) NOTE: PLEASE SEE PLANS MUST BE SIGNED |
| | , DATED AND SEALED BY THE ARCHITECT AS |
| | RECORD ON TITLE BLOCK OF SAID PLANS. |
| | PLEASE ALSO SEE BUILDING REVIEW COMMENTS |
| | WITH RESPECT TO PLANS BEING SIGNED AND |
| | SEALED BY AN ARCHITECT OR ENGINEER FOR |
| | SCOPE OF WORK. |
| | FS 481.221, FBC 106.3.4.3 |
| | |
| | 4) NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCK(S) AS REQUIRED |
| | UNDER FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004. |
| | PLEASE ALSO SEE FS 481.219 |
| | MISSING CERITIFICATE OF AUTHORIZATION |
| | NUMBER. |
| | |
| | 5) NOTE: PLEASE SEE FBC FOR EXISTING |
| | BUILDINS R313 WHICH REQUIRES ALL SD'S TO |
| | BE BROUGHT UP TO CODE FOR THIS LEVEL OF |
| | ALTERATION. |
| | PLEASE KNOW, ALL ARE TO BE WIRED |
| | INLINE/120V. |
| | PLEASE INDICATE ALL LOCATION PER NFPA-72 |
| | 11.5.1.1 |
| | ** PLEASE SEE THERE SEEMS TO BE A |
| | PARTIAL "RECEPT" SYMBOL LOCATED NEXT TO |
| | THE SD'S SHOWN, HOWEVER THIS SYMBOL |
| | COULD NOT BE LOCATED ON SCHEDULE? |
| | |
| | 6) NOTE: PLEASE SEE A MIN OF TWO GRND |
| | RODS WIL BE REQUIRED. 250.50,250.56 |
| | |
| | 7) NOTE: PLEASE SEE PLANS MENTIONS NEW |
| | PANEL BEING LOCATED OUTSIDE , HOWEVER |
| | PLANS ONLY SHOW THEMETER. PLEASE SHOW |
| | THE OUTDOOR PANEL. |
| | |
| | 8) NOTE: PLEASE VERIFY KW RATING OF |
| | RANGE AS THIS SEEMS VERY LOW FOR A MIN |
| | KW OF A RANGE. |
| | PLEASE ALSO SEE LOADS FOR RANGES AT A |
| | MIN IN 220.19. |
| | |
| | 9) NOTE: PLEASE SEE NEC 220.31, FOR MIN |
| | LOADS FOR A/C SYSTEM. PLEASE SEE LOADS |
| | AS SHOWN DO NOT CORRELATE WITH ANY LOAD |
| | CALCUALTIONS INNEC. SHOWS A 65% |
| | DE-RATING FOR BOTH THE CU AND AHU ??? |
| | PLEASE SEE AHU ALSO SHOWS 8KW AND 10KW? |
| | WHICH ONE? |
| | 215.5 |
| | |
| | 10) NOTE: PLEASE ALSO ADJUST MIN OCP FOR |
| | AHU PER 424.3B IF AHU HEAT IS 10KW. |
| | (125%). |
| | |
| | 11) NOTE: PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH CIRCUIT PER 210.52D, |
| | 210.11C3, MUST BE 20A AND #12. |
| | |
| | 12) NOTE: PLEASE VERIFY WASHER AND |
| | DRYER, AS PLANS SHOW A STACK UNIT, AND |
| | PANEL/LOAD CALCS SHOWS INDIVIDUAL UNITS? |
| | 215.5 |
| | |
| | 13) NOTE: PLEASE SEE MISSING FRONT AND |
| | REAR GFI PER 210.52E, 210.8A |
| | |
| | 14) NOTE: PLEASE SEE SOME MISSING |
| | RECEPTS PER 210.52 ONLY MISSING A FEW, |
| | THESE ARE REDLINED ON PLANS AT LOCATIONS |
| | NEEDED. |
| | |
| | 15) NOTE: PLEASE VERIFY NEW OR EXISTING |
| | MEANS OF EGRESS LIGHTING CONTROL FOR |
| | DOOR LEADING TO OUTSIDE MEANS OF EGRESS |
| | FROM EXISTIGN BEDRM. |
| | 210.70, LS 101 7.8 |
| | |
| | 16) NOTE: PLEASE SEE PLANS MENTIOSN ARC |
| | FAULT PROTECTION FOR RECEPTS ONLY. |
| | PLEASE SEE PLANS ARE TO BE DESIGNED |
| | UNDER THE 2002 NEC/ NFPA-70. PLEASE SEE |
| | 210.12B WHICH REQUIRESALL "OUTLETS" IN |
| | BEDRMS TO BE AFCI PROTECTED. |
| | |
| | 17) NOTE: PLEASE SEE MECHANICAL REVIEW |
| | COMMENTS WITH RESPECT TO NEW OR EXISTING |
| | EXHAUST FAN IN BATHRM. |
| | ** THIS WILL BE A MECHANICAL REVIEW |
| | COMMENT, HOWEVER MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | 18) NOTE: PLEASE SHOULD NOTE THE CURRENT |
| | CODE IN EFFECT. 2002 NEC , 2002 NFPA-72 |
| | |
| | 19) NOTE: PLEASE SUBMIT THE AIC RATINGS |
| | FOR NEW SERVICE EQUIPMENT/ MAINS. PER |
| | 110.9/215.5 |
| | |
| | ** WHEN RE-SUBMITTING PLANS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |