Plan Review Notes
Plan Review Notes For Permit 06031561
Permit Number 06031561
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-07 00:00:00*************** UNSAT ***************
  
  
 1) NOTE: PLEASE SEE AN OWNER/ BUILDER
 PERMIT IS BEING APPLIED FOR , HOWEVER IT
 DOES APPEAR APPLICATION QUALIFIES FOR
 THE EXEMPTIONS UNDER FS 489.
 PLEASE SEE ATTACHED PRINT OUT FROM PALM
 BEACH COUNTY PROPERTY APPR'S OFFICE
 WHICH INDICATES NUMEROUS PROPERITES
 UNDER OWNERS INFORMATION INCLUDING WHAT
 IS BEING A USED A A PRIMARY RESIDENCE
 LOCATED IN PALM BEACH COUNTY.
 PLEASE ALSO KNOW, THIS OFFICE WILL
 VERIFY WITH THE OTHER JURISDICTIONS OF
 OWNED PROPERTIES TO ANY PERMITTED WORK
 FOR VERIFICATION OF O/B QUALIFICATION.
 ** IF IT IS THE INTEND TO LEASE/RENT OR
 SELL PROPERTY W/IN TIME LIMITS,OR NOT TO
 USE THIS PROPERTY FOR OWN USE AND
 OCCUPANCY,IT IS ADVISABLE TO OBTAIN A
 CONTRACTOR FOR SUCH PERMITTED WORK.
  
 2) NOTE: PLEASE SEE SCOPE PF WORK
 MENTIONED ON APPLICATION AND SCOPE ON
 PLANS DO NOT CORRELATE.
 PLEASE ALSO SEE VALUE SHALL BE ADJUSTED
 FOR COMPLETE SCOPE PF REMODEL. THIS
 SHALL INCLUDE ALL LABOR AND MATERIALS.
 FBC ADMINISTRATIVE SECTION 108.3.
 PLEASE KNOW,IF AN APPROPRIATE VALUE IS
 NOT ADJUSTED, IT WILL BE ADJUSTED BY
 THIS OFFICE BASED ON FAIR MARKET VALUES
 SET FORTH IN THE FBC.
  
 3) NOTE: PLEASE SEE PLANS MUST BE SIGNED
 , DATED AND SEALED BY THE ARCHITECT AS
 RECORD ON TITLE BLOCK OF SAID PLANS.
 PLEASE ALSO SEE BUILDING REVIEW COMMENTS
 WITH RESPECT TO PLANS BEING SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER FOR
 SCOPE OF WORK.
 FS 481.221, FBC 106.3.4.3
  
 4) NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK(S) AS REQUIRED
 UNDER FLORIDA ADMINISTRATIVE CODE
 61G1-16.004.
 PLEASE ALSO SEE FS 481.219
 MISSING CERITIFICATE OF AUTHORIZATION
 NUMBER.
  
 5) NOTE: PLEASE SEE FBC FOR EXISTING
 BUILDINS R313 WHICH REQUIRES ALL SD'S TO
 BE BROUGHT UP TO CODE FOR THIS LEVEL OF
 ALTERATION.
 PLEASE KNOW, ALL ARE TO BE WIRED
 INLINE/120V.
 PLEASE INDICATE ALL LOCATION PER NFPA-72
 11.5.1.1
 ** PLEASE SEE THERE SEEMS TO BE A
 PARTIAL "RECEPT" SYMBOL LOCATED NEXT TO
 THE SD'S SHOWN, HOWEVER THIS SYMBOL
 COULD NOT BE LOCATED ON SCHEDULE?
  
 6) NOTE: PLEASE SEE A MIN OF TWO GRND
 RODS WIL BE REQUIRED. 250.50,250.56
  
 7) NOTE: PLEASE SEE PLANS MENTIONS NEW
 PANEL BEING LOCATED OUTSIDE , HOWEVER
 PLANS ONLY SHOW THEMETER. PLEASE SHOW
 THE OUTDOOR PANEL.
  
 8) NOTE: PLEASE VERIFY KW RATING OF
 RANGE AS THIS SEEMS VERY LOW FOR A MIN
 KW OF A RANGE.
 PLEASE ALSO SEE LOADS FOR RANGES AT A
 MIN IN 220.19.
  
 9) NOTE: PLEASE SEE NEC 220.31, FOR MIN
 LOADS FOR A/C SYSTEM. PLEASE SEE LOADS
 AS SHOWN DO NOT CORRELATE WITH ANY LOAD
 CALCUALTIONS INNEC. SHOWS A 65%
 DE-RATING FOR BOTH THE CU AND AHU ???
 PLEASE SEE AHU ALSO SHOWS 8KW AND 10KW?
 WHICH ONE?
 215.5
  
 10) NOTE: PLEASE ALSO ADJUST MIN OCP FOR
 AHU PER 424.3B IF AHU HEAT IS 10KW.
 (125%).
  
 11) NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH CIRCUIT PER 210.52D,
 210.11C3, MUST BE 20A AND #12.
  
 12) NOTE: PLEASE VERIFY WASHER AND
 DRYER, AS PLANS SHOW A STACK UNIT, AND
 PANEL/LOAD CALCS SHOWS INDIVIDUAL UNITS?
 215.5
  
 13) NOTE: PLEASE SEE MISSING FRONT AND
 REAR GFI PER 210.52E, 210.8A
  
 14) NOTE: PLEASE SEE SOME MISSING
 RECEPTS PER 210.52 ONLY MISSING A FEW,
 THESE ARE REDLINED ON PLANS AT LOCATIONS
 NEEDED.
  
 15) NOTE: PLEASE VERIFY NEW OR EXISTING
 MEANS OF EGRESS LIGHTING CONTROL FOR
 DOOR LEADING TO OUTSIDE MEANS OF EGRESS
 FROM EXISTIGN BEDRM.
 210.70, LS 101 7.8
  
 16) NOTE: PLEASE SEE PLANS MENTIOSN ARC
 FAULT PROTECTION FOR RECEPTS ONLY.
 PLEASE SEE PLANS ARE TO BE DESIGNED
 UNDER THE 2002 NEC/ NFPA-70. PLEASE SEE
 210.12B WHICH REQUIRESALL "OUTLETS" IN
 BEDRMS TO BE AFCI PROTECTED.
  
 17) NOTE: PLEASE SEE MECHANICAL REVIEW
 COMMENTS WITH RESPECT TO NEW OR EXISTING
 EXHAUST FAN IN BATHRM.
 ** THIS WILL BE A MECHANICAL REVIEW
 COMMENT, HOWEVER MAY AFFECT ELECTRICAL
 PLANS.
  
 18) NOTE: PLEASE SHOULD NOTE THE CURRENT
 CODE IN EFFECT. 2002 NEC , 2002 NFPA-72
  
 19) NOTE: PLEASE SUBMIT THE AIC RATINGS
 FOR NEW SERVICE EQUIPMENT/ MAINS. PER
 110.9/215.5
  
 ** WHEN RE-SUBMITTING PLANS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  