| 2006-05-14 00:00:00 | ********* UNSAT ********** |
| | |
| | PLANS NOW SUBMITTED FOR REVIEW. PLEASE |
| | SEE COMMENTS BELOW. |
| | |
| | ** PLEASE SEE SUBMITTED PACKAGE AHS NOW |
| | COME BACK WITH OUT THE 2ND COPY OF SLAB |
| | PLANS/DETAIL. PLEASE SUBMIT BOTH COPIES, |
| | ONE IS NEED FOR FILE SET AND THEN ONE IS |
| | PROVIDED BACK TO CONTRACTOR ONCE PERMIT |
| | IS ISSUED AND DATE STAMPED. |
| | |
| | 1)NOTE: PLEASE PROVIDE LAYOUT ON |
| | SITE/ELECTRICAL FOR LOCATION OF ALL |
| | SERVICE EQUIPMENT. |
| | PLEASE SEE PLANS DO NOT INDICATE |
| | LOCATION OF EXISTING MAIN(S). |
| | PLEASE INDICATE ROOM THE ATS PANEL IS |
| | LOCATED. |
| | PLEASE SEE RISER AND PLANS DO NOT |
| | INDICATE ANY DISCONNECTING MEANS FOR |
| | FEEDERS COMING FROM THE GEN. THE |
| | DISCONNECT MEANS DOES NOT REQUIRE OCP, |
| | HOWEVER IS REQUIRED TO BE RATED FOR THE |
| | LOAD SERVED, GROUPED WITH EXISTING |
| | MAINS. |
| | PLEASE NOTE, THE BRKR LOCATED INSIDE THE |
| | GEN IS NOT ACCCEPTED AS THE MEANS OF |
| | DISCONNECT.110.27,225.31-225.39. |
| | PLEASE SEE THIS WAS NOTED ON PREVIOUS |
| | REVIEW. |
| | |
| | 2) NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | SUBMITTED WITH SPECS. |
| | ATS/PANEL IS SHOWN AS 100A'S AND 60A'S. |
| | |
| | |
| | 3) NOTE: PLEASE KNOW, ALL PLANS SHALL |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR |
| | DESIGN/PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |