Plan Review Notes
Plan Review Notes For Permit 06031518
Permit Number 06031518
Review Stop E
Sequence Number 2
Notes
Date Text
2006-05-14 00:00:00********* UNSAT **********
  
 PLANS NOW SUBMITTED FOR REVIEW. PLEASE
 SEE COMMENTS BELOW.
  
 ** PLEASE SEE SUBMITTED PACKAGE AHS NOW
 COME BACK WITH OUT THE 2ND COPY OF SLAB
 PLANS/DETAIL. PLEASE SUBMIT BOTH COPIES,
 ONE IS NEED FOR FILE SET AND THEN ONE IS
 PROVIDED BACK TO CONTRACTOR ONCE PERMIT
 IS ISSUED AND DATE STAMPED.
  
 1)NOTE: PLEASE PROVIDE LAYOUT ON
 SITE/ELECTRICAL FOR LOCATION OF ALL
 SERVICE EQUIPMENT.
 PLEASE SEE PLANS DO NOT INDICATE
 LOCATION OF EXISTING MAIN(S).
 PLEASE INDICATE ROOM THE ATS PANEL IS
 LOCATED.
 PLEASE SEE RISER AND PLANS DO NOT
 INDICATE ANY DISCONNECTING MEANS FOR
 FEEDERS COMING FROM THE GEN. THE
 DISCONNECT MEANS DOES NOT REQUIRE OCP,
 HOWEVER IS REQUIRED TO BE RATED FOR THE
 LOAD SERVED, GROUPED WITH EXISTING
 MAINS.
 PLEASE NOTE, THE BRKR LOCATED INSIDE THE
 GEN IS NOT ACCCEPTED AS THE MEANS OF
 DISCONNECT.110.27,225.31-225.39.
 PLEASE SEE THIS WAS NOTED ON PREVIOUS
 REVIEW.
  
 2) NOTE: PLEASE CORRELATE RISER DIAGRAM
 SUBMITTED WITH SPECS.
 ATS/PANEL IS SHOWN AS 100A'S AND 60A'S.
  
  
 3) NOTE: PLEASE KNOW, ALL PLANS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 DESIGN/PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  