| 2006-04-13 00:00:00 | | | | DENIED | | | | | | THE LOADS INDICATED AS "OPERATED AT | | | OWNERS DISCRETION" ARE SUBJECT TO BE | | | ENERGIZED WHEN THE ATS IS ENERGIZED. | | | DISCRETIONARY LOADS ARE CONSIDERED ALL | | | CIRCUITS IN ANY PANELS ENERGIZED BY AN | | | AUTOMATIC SWITCH, SINCE THERE IS NO WAY | | | OF KNOWING WHAT CIRCUITS MAY ENERGIZE IN | | | THE OWNERS ABSCENCE. | | | LOAD SHEDDING IS PERMISIBLE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|