| Plan Review Notes For Permit 06031445 |
| Permit Number |
06031445 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-11 00:00:00 | ********** UNSAT *********** | | | | | | 1) NOTE: PLEASE SEE NO ELECTRICAL DETAIL | | | WAS SUBMITTED FOR THE PROPOSED | | | ILLUMINATED SIGN. | | | BALLAST, TRANSFORMERS, DISCONNECT? | | | 215.5,600.6, | | | PLEASE SEE THE CABINET IS CHANGING AND | | | IS NOT ONNLY A FACE CHANGE. | | | | | | 2) NOTE: PLEASE SEE LETTER ATTACHED FOR | | | SIGN AUTHORIZATION IS TO BE NOTARIZED | | | PER FS 117.05. | | | MISSING COUNTY AND STATE INFORMATION.) | | | | | | 3) NOTE: PLEASE SEE VALUE SHALL REFELCT | | | ALL LABOR AND MATERIALS FOR THE SIGN, | | | EVEN IF SIGN IS OWNER SUPPLIED. | | | FBC , ADMINISTRATIVE SEC 108.3. | | | | | | 4) NOTE: PLEASE OBTAIN AND BRING IN | | | INFORMATION FOR OWNERSHIP OF PROPERTY AS | | | THE PBC PROPERTY APPR OFFICE INDICATES A | | | MR. WILLIAM LEWIS AND APPLICATION SHOWS | | | "FOREST HILL STATION INC" | | | PLEASE SEE PRINT OUT FROM PBC PROP APPR. | | | WHICH IS ATTACHED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|