Plan Review Notes
Plan Review Notes For Permit 06031445
Permit Number 06031445
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-11 00:00:00********** UNSAT ***********
  
 1) NOTE: PLEASE SEE NO ELECTRICAL DETAIL
 WAS SUBMITTED FOR THE PROPOSED
 ILLUMINATED SIGN.
 BALLAST, TRANSFORMERS, DISCONNECT?
 215.5,600.6,
 PLEASE SEE THE CABINET IS CHANGING AND
 IS NOT ONNLY A FACE CHANGE.
  
 2) NOTE: PLEASE SEE LETTER ATTACHED FOR
 SIGN AUTHORIZATION IS TO BE NOTARIZED
 PER FS 117.05.
 MISSING COUNTY AND STATE INFORMATION.)
  
 3) NOTE: PLEASE SEE VALUE SHALL REFELCT
 ALL LABOR AND MATERIALS FOR THE SIGN,
 EVEN IF SIGN IS OWNER SUPPLIED.
 FBC , ADMINISTRATIVE SEC 108.3.
  
 4) NOTE: PLEASE OBTAIN AND BRING IN
 INFORMATION FOR OWNERSHIP OF PROPERTY AS
 THE PBC PROPERTY APPR OFFICE INDICATES A
 MR. WILLIAM LEWIS AND APPLICATION SHOWS
 "FOREST HILL STATION INC"
 PLEASE SEE PRINT OUT FROM PBC PROP APPR.
 WHICH IS ATTACHED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  