| Plan Review Notes For Permit 06031405 |
| Permit Number |
06031405 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-21 00:00:00 | REVISION TO MECH. PLANS PAGE M-1, M-2, & | | | M-3 | | | *** PROVISO *** | | | 1) AS PER 2004 FBC(M) 602.2.1, MATERIALS | | | EXPOSED WITHIN PLENUMS SHALL BE NON - | | | COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD | | | INDEX OF NOT MORE THAN 25 AND SMOKE - | | | DEVELOPED INDEX OF NOT MORE THAN 50 WHEN | | | TESTED IN ACCORDANCE WITH ASTM E 84. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|